Loading...
ST9801-LR0008157 ' 464 8C blinerlml 9200 King Arthur Ddve Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 Report No.: Location: CONCRETE COMPRESSION TEST REPORT 101 Job No.: Coppell Road, Inlet at Eastwick Contractor: Ed Bell Construction Reported To: City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SO. IN. Field Number: CP081501 Test Date: 08/22/00 Maximum Load, LBS: 100720 Age When Tested, Days: 7 Compressive Strength, PSh 3560 Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: CP081502 CP081503 09/12/00 09/12/00 136110 138850 28 28 4810 4910 4860 08/15/00 4000 psi @ 28 days 10 of 10 M. Yahyazadeh CP081504 DISCARD DISCARD Temperature: Ambient Time of Sample: 2:00 PM Source of Concrete: 102 °F Mix 98 °F TXI-8205 Air Content 4.2 % Slump Pick-Up Charge: Yes N/A Ticket No.: 2710321 3.0 Inches Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: City of Coppell - Larry Davis Unit Weight PCF Yield CF/CY Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEFT IN FULL WITHOUT THE APPROVAL OF STANTECH.