Loading...
ST9801-LR000805 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: Project: Contractor: Reported To: 97 Job No.: 1520COP03 Driveway at 217 Block of Coppell Rd Coppell Road Paving and Drainage Improvements Ed Bell Construction City of Coppell- Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area -28.27 SQ. IN. Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: Field Number: CP080501 CP080502 CP080503 Test Date: 08/12/00 09/02/00 09/02/00 Maximum Load, LBS: 101610 130330 129230 Age When Tested, Days: 7 28 28 Compressive Strength, PSh 3210 4610 4570 Average Strength, PSI: 4590 Type Break: Conical (U.N.O.) Remarks: 08/05/00 4000 psi @ 28 days 20 of 50 M. Yahezedah CP080504 DISCARD DISCARD Temperature: Ambient Time of Sample: Source of Concrete: 100 ° F 9:45 AM TXI - 8274 Mix 92 ° F Air Content 5.2 % Slump Pick-Up Charge: Yes N/A Ticket No.: 271873 4.5 Inches Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: City of Coppell - Larry Davis Unit Weight PCF Yield CF/CY Sig , of 1 Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH.