Park West CC(4)-LR 9401201 ~~rracon CONSULTANTS, INC. 12801 Stemmons Freeway, Suite 907 Dallas, Texas 75234 (214) 243-8838 Fax (214) 243-4014 January 20, 1994 Gerald W. Finn, P.E. Clement B. Bommarito, PE. Lewis Daniel Israel, P.E. Eric J. Cleveland, P.E. Dupey Management Corporation 9015 Sterling Street Irving, Texas 75063 Attn: Mr. Robert McCann Re: M J Designs Distribution Center Coppell, Texas lob No. 17931033 Dear Mr. McCann: A representative of Terracon Consultants, Inc. has continued to perform earthwork observation and testing services for the referenced project. This report covers the services performed from January 3 to January 15, 1994. Services provided during this period consisted of performing field density tests on compacted fill and observing water injection operations. Clay fill is being placed in the storm sewer excavation and in the northeast parking lot. We understand that clay fill below parking areas is to be compacted to at least 95% of it's maximum standard Proctor dry density (ASTM D-698) at a moisture content at least 3 % above it's optimum. Select fill is being placed in the building area and is to be compacted to at least 95 of it's maximum standard Proctor dry density at a moisture content of ±2%. Results of the field density tests performed during this period along with two standard Proctor tests performed on fill are attached. Tests 178 to 187 were performed on the northeast parking lot and tests 209-214, 225-227, 248-250, and 271-273 were performed in the storm sewer excavation. The remaining tests were performed on select fill and were referenced to the northeast building corner which was given an assumed station of 0 south and 0 east. Offices of The Terracon Companies, Inc. Geotechnical, Environmental and Materials Engineers Arizona: Tucson ^ Colorado: Colorado Springs, Denver, Ft. Collins, Greeley, Longmont ^ Idaho: Boise ^ Illinois: Bloomington, Chicago. Rock Island ^ Iowa: Cedar Falls, Cedar Rapids, Davenport, Des Moines, Storm Lake ^ Kansas: Lenexa, Topeka, Wichita ^ Minnesota: St. Paul ^ Missouri: Kansas City ^ Nebraska: Lincoln, Omaha ^ Nevada: Las Vegas ^ Oklahoma: Oklahoma City, Tulsa ^ Texas: Dallas, Fort Worth ^ Utah: Salt Lake City ^ Wyoming: Cheyenne QUALITY ENGINEERING SINCE 1965 Dupey Management Corporation Job No. 17931033 January 20, 1994 Terracon If you have any questions regarding this report or in need of any further services, please do not hesitate to contact this office. Sincerely, TERRA N CON', c J. leveland, P Project Engineer EJC:kms Attachments Copy To: James, Harwick + Partners, Inc. Mr. Mark Wolf Albert Halff & Associates, Inc. Mr. Dennis Chovan Bob Moore Construction, Inc. Mr. Phil Bell City of Coppell Mr. Larry Davis 2 .~, FIELD COMPACTION REPORT Job No. 17931033 Job Name and Location M.J. DESIGNS DISTRIBUl'ION CF3JI`II2 Date 1-15-94 Architect or Engineer JAMES HAFd~IICK + PAR'1'NIIZS INC. Contractor BOB MOORS CONSTRUCTION INC. Datum SITE DATiAK Lift No. Maximum In-Place In-Place Test Date Location or Mtl. Lab Dry Wet Water Dry Percent Comments No. Elev. Mark Densit Densit Content Densit Co . 205 1-5 220 - E LIFT 1 D 125 5 133 0 9 1 121 9 97 190 - S . . . . 206 1-5 280 - E 230 - S LIFT 1 D 125.5 132.1 9.5 120.6 96 207 1-5 160 - E LIFT 1 0 125.5 132 5 9.6 120.8 96 280 - S . 208 1-5 60 - E LIFT 1 D 125 5 132 0 8 8 121 3 97 230 - S . . . . 209 1-5 25 FT EAST OF LIFT 1 C 98.5 119.1 25.2 95.1 97 STORM INLET 210 1-5 50 FT EAST OF LIFT 1 C 98.5 118.7 25.1 94.9 96 STORM INLET 211 1-5 75 FT EAST OF LIFT 1 C 98.5 119.5 25.4 95.3 97 STORM INLET 212 1-5 25 FT EAST OF LIFT 2 C 98.5 117.3 25.2 93.7 95 STORM INLET 213 1-5 50 FT EAST OF LIFT 2 C 98 5 118.0 25.3 94.2 96 S70RM INLET . 214 1-5 75 FT EAST OF LIFT 2 C 98 5 117 5 25 1 93 9 95 STORM INLET . . . . 215 1-b 270 - S LIFT 1 D 125 5 6 132 9 5 121 0 96 30-E . . . . 216 1-b 290 - S LIFT 1 D 125 5 133 3 9.0 122.2 97 80 - E . . 217 1-b 260 - S 140 - E LIFT 1 D 125.5 132.5 9.5 121.0 96 218 1-b 290 - S LIFT 1 D 125 5 132 8 9 0 121.8 97 200 - E . . . 219 1-6 280 - S LIFT 1 D 125 5 134 2 8 6 123 5 98 290 - E . . . . 220 ~-b 260 - S LIFT 1 D 125 5 133.5 9.0 122.4 98 370 - E . 221 1-b 290 - S LIFT 1 D 125 5 132 2 9 4 120 8 96 410-E . . . . 222 1-6 260 - S LIFT 1 D 5 125 134 0 1 9 122 8 98 470 - E . . . . 223 1-b 290 - S L[FT 1 D 125 5 6 131 8.7 121.0 96 530 - E . . 224 1-6 270 - S 580-E LIFT 1 D 125.5 132.5 9.4 121.1 96 225 1-7 25 FT EAST OF LIFT 3 C 98.5 119.7 25.3 95.5 97 STORM INLET 226 1-7 50 FT EAST OF LIFT 3 C 98.5 118.9 25.0 95.1 97 STORM INLET 227 1-7 75 FT EAST OF LIFT 3 C 98.5 119.2 26.0 94.6 96 STORM INLET 228 1-7 320 - S LIFT 1 D 125 5 132.2 9.5 120.7 96 30-E . 229 1-7 360 - S 10 0 - E LIFT 1 D 125.5 132.0 9.0 121.1 96 230 1-7 310 - S LIFT 1 D 125 5 133.0 9.2 121.7 97 190 - E . 231 1-7 360 - S LIFT 1 D 125 5 131 7 6 8 121 2 97 250 - E . . . . NOTES: Densities shown: pounds per cubic foot eater Content: Percent of dry weight ~ ~~ ~~~~ Percent Compaction: Based on maximum dry density obtained on sample indicated by material mark. ~, FIELD COMPACTION REPORT Job No. 17931033 Job Name and Location M.J. DESIGNS DISTRIBUTION CENTER Date 1-15-94 Architect or Engineer JAMES, HAFdn1IQC + PARTNERS, INC. Contractor BOB MOORE OONSTRUCTION INC. Datum SITE DATUM Lift No. Maximum In-Place In-Place Test Date Location or Mtl. Lab Dry Net Water Dry Percent Comments No. Elev. Mark Densit Densit Content Densit Co . 232 1-7 310 - S 310-E LIFT 1 D 125.5 134.0 9.4 122.4 98 233 1-7 360 - S 380-E LIFT 1 D 125.5 133.6 9.0 122.5 98 234 1-7 310 - S 450 - E LIFT 1 D 125.5 132.5 9.2 121.3 97 235 1-7 350 - S 490 - E LIFT 1 D 125.5 131.8 9.5 120.3 96 236 1-7 320 - S 570-E LIFT 1 D 125.5 133.0 9.1 121.9 97 237 1-7 350 - S 580 - E LIFT 1 D 125.5 133.3 9.0 122.2 97 238 1-8 390 - S 20-E LIFT 1 D 125.5 133.1 9.4 121.6 97 239 1-8 440 - S 70 - E LIFT 1 D 125.5 131.0 9.0 120.1 96 240 1-8 380 - S 130-E LIFT 1 D 125.5 131.6 8.5 121.2 97 241 1-8 440 - S 210-E LIFT 1 D 125.5 132.2 9.3 120.9 96 242 1-8 380 - S 290 - E LIFT 1 0 125.5 134.0 9.6 122.2 97 243 1-8 430 - S LIFT 1 D 125 5 132 5 9 6 120 8 96 330 - E . . . . 244 1-8 380 - S 410-E LIFT 1 D 125.5 132.0 9.2 120.8 96 245 1-8 440 - S 470-E LIFT 1 D 125.5 131.3 9.5 119.9 96 246 1-8 380 - S LIFT 1 D 125 5 132 8 9 5 121 2 97 540 - E . . . . 247 1-8 440 - S LIFT 1 D 125 5 133 5 10 2 121 1 96 580-E . . . . 248 1-10 25 FT EAST OF LIFT 4 C 98.5 118.2 26.4 93.5 95 STORM INLET 249 1-10 50 FT EAST OF LIFT 4 C 98.5 118.5 26.0 94.0 95 STORM INLET 250 1-10 75 FT EAST OF LIFT 4 C 98.5 119.1 26.6 94.1 96 STORM INLET 251 1-10 470 - S 20-E LIFT 1 E 125.0 133.6 9.3 122.2 98 252 1-10 520 - S LIFT 1 E 125 0 132 2 9.0 121.2 97 80-E . . 253 1-10 460 - S LIFT 1 E 125 0 133 0 9 0 122 0 98 150-E . . . . 254 1-10 520 - S LIFT 1 E 125 0 132 5 9 5 121 0 97 190 - E . . . . 255 1-10 460 - S 250-E LIFT 1 E 125.0 134.2 9.6 122.4 98 256 1-10 310 - E LIFT 1 E 125.0 132.2 9.5 120.7 97 257 1-10 460 - S LIFT 1 E 125 0 133 1 9 0 122 1 98 380 - E . . . . 258 1.10 510 - S LIFT 1 E 125 0 132 8 9 8 120 9 97 430 - E . . . . NOTES: Densities shown: pounds per cubic foot Hater Content: Percent of dry weight Percent Compaction: Based on maximum dry density obtained on ~rr~con sample indicated by material mark. FIELD COMPACTION REPORT Job No. 17931033 Job Name and Location M.J. DESIGNS DISTRIBUTION CII~1TII2 Date 1-15-94 Architect or Engineer JAMES, HARWICK + PARTNERS, INC. Contractor BOB MOORE CONSTRITCTION, INC Datum SITE DATUM Lift No. Maximum In-Place In-Place Test Date Location or Mtl. Lab Dry Net Water Dry Percent Comments No. Elev. Mark Densit Densit Content Densit C . 259 1-10 470 - S 480 - E LIFT 1 E 125.0 132.5 9.3 121.2 97 260 1-10 490 - S 550 - E L1FT 1 E 125.0 133.1 9.5 121.5 97 261 1_12 550 - S 30-E LIFT 1 E 125.0 132.6 9.2 121.4 97 262 1_12 590 - S 80-E LIFT 1 E 125.0 130.4 9.0 119.6 96 263 1-12 550 - S 15 0 - E L1FT 1 E 125.0 135.1 9.5 123.3 99 264 1-12 590 - S 230-E LIFT 1 E 125.0 133.7 9.5 122.1 98 265 1-12 540 - S 290 - E LIFT 1 E 125.0 132.5 9.0 121.5 97 266 1.12 590 - S 340-E LIFT 1 E 125.0 133.3 10.2 120.9 97 267 1_12 540 - S 410-E LIFT 1 E 125.0 132.6 9.7 120.8 97 268 1-12 590 - S 480-E LIFT 1 E 125.0 131.4 9.2 120.3 96 269 1-12 540 - S 530 - E LIFT 1 E 125.0 133.5 9.5 121.9 98 270 1_12 590 - S 580-E LIFT 1 E 125.0 132.6 9.3 121.3 97 271 1.13 50 FT EAST OF INLET LIFT 4 C 98.5 119.3 26.5 94.3 96 STORM 272 1.13 75 FT EAST OF INLET LIFT 4 C 98.5 120.4 26.0 95.6 97 STORM 273 1.13 100 FT EAST OF LIFT 4 C 98.5 118.9 27.2 93 5 95 STORM INLET . 274 1-14 590 - S 310-E LIFT 2 E 125.0 132.5 9.6 120.8 97 275 1-14 580 - S 420 - E LIFT 2 E 125.0 134.8 10.4 122.1 98 276 1-14 580 - S 560 - E LIFT 2 E 125.0 132.2 9.2 121.0 97 277 1.14 520 - S 580 - E LIFT 2 E 125.0 134.0 9.6 122.2 98 278 1.14 530 - S 460 - E LIFT 2 E 125.0 133.6 9.1 122.4 98 279 1-14 520 - S 340 E LIFT 2 E 125.0 134.5 9.3 123.0 98 280 1-14 470 - S 320 - E LIFT 2 E 125.0 132.8 9.8 120.9 97 281 1.14 470 - S 440 - E LIFT 2 E 125.0 133.5 9.4 122.0 98 282 1.14 570 - S 550 - E LIFT 2 E 125.0 134.2 9.2 122.8 98 283 1-15 430 - S 330-E LIF7 2 E 125.0 133.6 9.4 122.1 96 284 1-15 430 - S 420 - E LIFT 2 E 125.0 132.2 9.2 121.0 97 285 1-15 430 - S 520 - E LIFT 2 E 125.0 134.0 9.5 122.3 98 NOTES: Densities shown: pounds per cubic foot Hater Content: Percent of dry weight Percent Compaction: Based on maximum dry density obtained on ~rr~can sample indicated by material mark. FIELD COMPACTION REPORT Job No. 17931033 Job Name and Location M.J. DESIGNS DISTRIBUTION CENTII2 Date 1-15-94 Architect or Engineer JAMES HAFtSn1ICK + PARTNIIZS INC. Contractor BOB MOORE CONSTRUCTION INC. Datum SITE DATt]NI Test No. Date Location Lift No. or Elev. Mtl. Mark Maximum Lab Dry Densit In-Place Net Densit Water Content In-Place Dry Densit Percent Co Comments 286 1-15 370 - S 580-E LIFT 2 E 125.0 133.4 9.1 122.2 98 287 1.15 370 - S 450 - E LIFT 2 E 125.0 134.2 9.2 122.8 98 288 1.15 360 - S 330-E LIFT 2 E 125.0 134.1 9.5 122.4 98 289 1-15 310 - S 380 - E LIFT 2 E 125.0 133.7 9.7 121.8 97 290 1-15 310 - S 460 - E LIFT 2 E 125.0 134.3 9.4 122.7 96 291 1-15 310 - S 570 - E LIFT 2 E 125.0 133.1 9.0 122.1 98 NOTES: Densities shown: pounds per cubic foot Hater Content: Percent of dry weight ~ ~~ ~~~~ Percent Compaction: Based on maximum dry density obtained on sample indicated by material mark. 1 f~ rr acon 13s MOISTURE-DENSITY RELATIONSHIP Job No. 17931033 Date 114/94 t3o Project MT DESIGNS DTSTRTBUTION CENTER - COPPELL, TEXAS Source of Material OFF SITE-FORT WORTH 125 Description of Material TAN CLAYEY SAND t20 ~~ Material Designation D Test Method ASTM D-698 (METHOD Al 1t5 TEST RESULTS ° o ~ Maximum Dry Density 125.5 PCF Optimum Watec Content 10.0 °~n u 110 .a ATTERBERG LIMITS ~ a N ~ 18% 13°k 5°k 0 a_ ~ CURVES OF 100% SATURATION r 100 FOR SPECIFIC GRAVITY EQUAL TO: F- H 80 2 N Z . O 2 70 . >- 95 o l 2.60 90 85 80 75 30 WATER CONTENT (Percent Dry Weight) 1 I'~ rr acon 135 MOISTURE-DENSITY RELATIONSHIP Job No. 17931033 Date t /10/94 Project M.T DESIGNS DTSTRIBUTION 13o CENTER - COPPELL. TEXAS Source of Material OFF SITE-FORT WORTH 125 Description of Material TAN CLAYEY SAND/SANDY CLAY Material Desi nation E t2o g T t M th d ASTM D 698 METHOD Al es e o - ( 11 s TEST RESULTS ~- ° o w Maximum Dry Density 125.0 PCF Optimum Water Content 9.0 % u uo .a ATTERBERG LMTS ~, a los ~~ ~,_ ~L ~ c 23% 15% S% 0 a `~ CURVES OF 100`% SATURATION ' ~,,, 100 H FOR SPECIFIC GRAVTI Y EQUAL TO: N 80 2 z . w 0 2 70 >- s . 9 0 2 60 . 90 S S 80 75 0 5 10 15 20 25 30 35 40 45 WATER CONTENT (Percent Dry Weight>