Loading...
Park West CC(4)-CS 931019 _,-- _,.-.~-~,. _ ..... ' ..... ~ P.O. Box 478 The City With A Beautiful Future '-~...._~ Coppell, Texas 75019 214-462-0022 October 19, 1993 Albert H. Halff Associates 8616 Northwest Plaza Dr. Dallas, TX 75225 RE: Park West Commerce Center M.J. Designs Dear Sir: The City of Coppell has received and reviewed the referenced plans and has the following comments to offer: 1. An erosion control plan and a Notice of Intent should be submitted. 2. You may want to reconsider the width of your driveway on the west side of this development. You are currently showing a 20 foot driveway to service approximately 473 parking spaces. 3. A minimum 24 foot fire lane should be provided around the entire building with fire hydrants every 300 feet. 4. Based on the contours, it appears as though a portion of the area on the east side of this development could be carried to the existing 54" stub out in Grapevine Creek when the property is developed. This would eliminate the need for yet another headwall connection in Grapevine Creek in the future. It appears as though the 54" was originally sized to convey water from the south side of Airline Drive. At sometime in the past, the water was taken in a 60" pipe in a westward direction to Grapevine Creek. I would request that you reevaluate your design and see if you can accommodate the area to the east (approximately 9 acres). This most likely will require installing a larger line running east and west south of the creek and then teeing into it to pick up your onsite water. 5. On sheet STM-1 please notice what portions of the stormdrain system will be private. Basically, only the portions in the Grapevine Creek drainage area will be public and a system running east and west on the south side of Grapevine Creek in the northeast comer of the property will be public. 6. The 100-year water surface should be shown. Also, the grade line should be projected to the inlet to determine if the inlet will function in a 100-year storm. That information should be provided at all outfalls. 7. It appears as though additional manholes should be provided along line A of the sanitary sewer. 8. Notice what portions of the sewer and water system are private as shown on sheet WS-1. 9. The fire lane detector checks should be shown. Also, notice the comment concerning the domestic and irrigation meters. 10. Please note that Airline Drive should be bored to make the water line connection. 11. Southwestern Blvd. should be bored to make the connection for the sanitary sewer. 12. I realize that a portion of line B is not part of this contract. However, it is being designed with this contract to show that it will work with these improvements in the future. I would comment that the grade being proposed for the 10" sewer line is too flat. This should be reevaluated to determined if additional grade can be obtained in the system. There is also a portion of sanitary sewer line A that has inadequate cover. These two items could lead to the need to lower the existing 24* water line in Southwestern Blvd. so a steeper grade connection can be made to the existing manhole on the north side of Southwestern Blvd. There are various other minor comments contained within the plans. Once all comments have been addressed, the revised set of plans plus the mark-ups should be provided to the City along with a cover letter that addresses the comments. If you should have any questions concerning these comments please feel free to contact me at your convenience. Sincerely, Kenneth M. Griffin, P.E. City Engineer file/kgriffin/mjdesign.ltr