ST9801-LR000724 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 81A Job No.: Coppell Road Paving at Sta. 10+50 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SO. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: CP072410 07/27/00 112550 3 3980 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/24~00 4000 psi @ 28 days 103 of 500 S. Adli Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 85 o F Mix 85 ° F Air Content 3.50 % Slump 9:15 AM Pick-Up Charge: Yes Ed Bell 01MW NIA Ticket No.: N/A Unit Weight PCF 2.00 Inches Yield CF/CY City of Coppell - Kenneth Griffin City of Coppell - Larry Davis · Page __~_~ Test Methods: ASTM C 31, C 39, C 173, C 192. C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED, TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES, THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 82A Job No.: Coppell Road Paving at Sta. 8+00 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SO. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: CP072415 07/27/00 99890 3 3530 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/24/00 4000 psi @ 28 days 226.5 of 500 S. Adli Temperature: Ambient Time of Sample: Source of Concrate: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 97 o F Mix 95 o F 11:35 AM Ed Bell 01 MW Unit Weight Air Content 4.00 % Slump Pick-Up Charge: Yes N/A Ticket No.: NIA PCF 3.00 Inches Yield CF/CY City of Coppell - Kenneth Gdffin City of Coppell - Larry Davis age 0 Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED, TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-.4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 83A Job No.: Coppell Road Paving at Sta. 5+68 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSh Type Break: Conical (U.N.O,) Remarks: CP072420 07/27/00 96770 3 3420 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/24/00 4000 psi @ 28 days 312 of 500 S. Adli Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 98 o F Mix 95 o F 1:20 PM Ed Bell 01MW Unit Weight Air Content 5.00 % Slump Pick-Up Charge: Yes N/A Ticket No.: N/A PCF 3.00 Inches Yield CF/CY City of Coppell - Kenneth Griffin City of Coppell - Larry Davis Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LE'FrERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 84A Job No.: Coppell Road Paving at Sta. 3+50 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area -28.27 SO. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: CP072425 07/27/00 93500 3 3310 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/24/00 4000 psi @ 28 days 416.5 of 500 S. Adli Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 97 o F 3:00 PM Ed Bell 01MVV Mix 95 ° F Air Content 4.50 % Slump 3.00 Inches Pick-Up Charge: Yes N/A Ticket No.: N/A PCF Unit Weight Yield CF/CY City of Coppell - Kenneth Griffin City of Coppell - Larry Davis Z-'~) g /L~-'~~'~gned Z-- 1 Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 80 Job No.: Coppell Road at Sta. 11+50 Contractor: Ed Bell Construction Reported To: City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SO. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSI: Type Break: Conical (U.N.O.) Remarks: 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: CP072401 CP072402 CP072403 07/31/00 08~1/00 08/21~0 109870 128890 132650 7 28 28 3890 4560 4690 4630 07/24/00 4000 psi @ 28 days 65 of 500 S. Adli CP072404 HOLD HOLD Temperature: Ambient Time of Sample: Source of Concrete: 85 o F Mix 8:15 AM Ed Bell - 01MW 85 o F Air Content 4.00 % Slump 2.50 Inches Pick-Up Charge: Yes N/A Ticket No.: N/A Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: City of Coppell - Larry Davis Unit Weight PCF Si Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES, THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 81 Job No.: Coppell Road at Sta. 10+50 Contractor: Ed Bell Construction Reported To: City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN, 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: Field Number: CP072406 CP072407 CP072408 Test Date: 07/31/00 08/21/00 08/21/00 Maximum Load, LBS: 130220 142930 147400 Age When Tested, Days: 7 28 28 Compressive Strength, PSI: 4610 5060 5210 Average Strength, PSh 5140 Type Break: Conical (U.N.O.) Remarks: 07/24/00 4000 psi @ 28 days 103 of 500 S. Adli CP072409 HOLD HOLD Temperature: Ambient Time of Sample: Source of Concrete: 85 ° F Mix 9:15 AM Ed Bell - 01MW 85 o F Air Content 3.50 % Slump Pick-Up Charge: Yes N/A Ticket No.: N/A 2.00 Inches Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: City of Coppell- Larry Davis Unit Weight PCF Yield CF/CY Sign Pa Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LE~'I'ERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH, '[' I' ! T 9200 King Arthur Drive Dallas. Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: 82 Job No.: Location: Coppell Road at Sta. 8+00 Contractor: Ed Bell Construction Reported To: City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN. 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: Field Number: CP072411 CP072412 CP072413 Test Date: 07/31/00 08/21/00 08/21/00 Maximum Load, LBS: 116410 136990 139930 Age When Tested, Days: 7 28 28 Compressive Strength, PSI: 4120 4850 4950 Averag e Strength, PSI: 4900 Type Break: Conical (U.N.O.) Remarks: 07/24/00 4000 psi @ 28 days 226.5 of 500 S. Adli CP072414 HOLD HOLD Temperature: Ambient Time of Sample: Source of Concrete: 95 ° F Mix 11:35 AM Ed Bell - 01MW 97 ° F Air Content 4.00 % Slump Pick-Up Charge: Yes N/A Ticket No.: N/A 3.00 Inches Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: City of Coppell - Larry Davis Unit Weight PCF Yield CF/CY Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C ,, Si ~~1 106 OUR LE'Fi'ERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Ddve Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: 83 Job No.: Location: Coppell Road at Sta. 5+68 Contractor: Ed Bell Construction Reported To: City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSI: Average Strength, PSI: Type Break: Conical (U.N.O.) Remarks: 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: CP072416 CP072417 CP072418 07/31/00 08~1/00 08~1/00 103100 132180 134470 7 28 28 3650 4680 4760 4720 07/24/00 4000 psi @ 28 days 312 of 500 S. Adli CP072419 HOLD HOLD Temperature: Ambient Time of Sample: Source of Concrete: 98 o F Mix 1:20 PM Ed Bell - 01MW 95 ° F Air Content 5.00 % Slump Pick-Up Charge: Yes N/A Ticket No.: N/A 3.00 Inches Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: City of Coppell - Larry Davis Unit Weight PCF Yield CF/CY Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. I' l' : T 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631.4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 80A Job No.: Coppell Road Paving at Sta. 11 +50 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN. 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSI: Average Strength, PSi: Type Break: Conical (U.N.O.) Remarks: CP072405 07/27/00 99480 3 3520 07/24/00 4000 psi @ 28 days 65 of 500 S. Adli Temperature: Ambient 85 o F Mix 85 o F Air Content 4.00 % Slump 2.50 Inches Time of Sample: 8:15 AM Pick-Up Charge: Yes Source of Concrete: Ed Bell 01MW N/A Ticket No.: N/A Fine Aggregate: Unit Weight PCF Coarse Aggregate: Water: Yield CF/CY Cement: Fly Ash: Admixture(s): Distribution: City of Coppell - Kenneth Griffin City of Coppell o Larry Davis Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 81A Job No.: Coppell Road Paving at Sta. 10+50 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SO. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: CP072410 07/2750 112550 3 3980 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/24/00 4000 psi @ 28 days 103 of 500 S. Adli Temperature: Ambient Time of Sample: Source of Concrate: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 85 o F 9:15 AM Ed Bell 01MW Mix 85 ° F Air Content 3.50 % Slump 2.00 Inches Pick-Up Charge: Yes N/A Ticket No.: N/A PCF Unit Weight Yield CF/CY City of Coppell - Kenneth Griffin City of Coppell - Larry Davis ~ Page Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Ddve Dallas, Texas 75247-3610 Phone 214/6314372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 82A Job No.: Coppell Road Paving at Sta. 8+00 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSI: Average Strength, PSI: Type Break: Conical (U.N.O.) Remarks: CP072415 07/27/00 99890 3 3530 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/24/00 4000 psi @ 28 days 226.5 of 500 S. Adli Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 97 ° F 11:35 AM Ed Bell 01MW Mix 95 ° F Air Content 4.00 % Slump 3.00 Inches Pick-Up Charge: Yes N/A Ticket No.: N/A PCF Unit Weight Yield CF/CY City of Coppell - Kenneth Griffin ,._~j~~ City of Coppell - Larry Davis Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IOENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. ~ l" T T 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 83A Job No.: Coppell Road Paving at Sta. 5+68 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28,27 SQ. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSI: Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: CP072420 07~7/00 96770 3 3420 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/24/00 4000 psi @ 28 days 312 of 500 S. Adli Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 98 ° F Mix 95 o F 1:20 PM Ed Bell 01MW Unit Weight Air Content 5.00 % . Slump Pick-Up Charge: Yes N/A Ticket No.: N/A PCF 3.00 Inches Yield CF/CY City of Coppell - Kenneth Griffin City of Coppell ~ Larry Davis Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/"o31-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 84A Job No.: Coppell Road Paving at Sta. 3+50 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: CP072425 07/27/00 93500 3 3310 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/24/00 4000 psi @ 28 days 416.5 of 500 S. Adli Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 97 ° F Mix 95 o F 3:00 PM Ed Bell 01MW Unit Weight Air Content 4.50 % Slump Pick-Up Charge: Yes N/A Ticket No.: N/A PCF 3.00 Inches Yield CF/CY City of Coppell - Kenneth Griffin City of Coppell - Larry Davis ~i'~gned age I Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH, r m' T t 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone214/631-4372 Fax214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 80A Job No.: Coppell Road Paving at Sta. 11 +50 Contractor: Ed Bell Construction Reported To: Ed Bell - Gary Pryor (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SO. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: CP072405 07/27/00 99480 3 3520 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/24/00 4000 psi @ 28 days 65 of 500 S. Adli Temperature: Ambient 85 o F Mix 85 o F Air Content 4.00 % Slump 2.50 Inches Time of Sample: 8:15 AM Pick-Up Charge: Yes Source of Concrete: Ed Bell 01MW N/A Ticket No.: N/A Fine Aggregate: Coarse Aggregate: Unit Weight PCF Water: Yield CF/CY Cement: Fly Ash: Admixture(s): Distribution: City of Coppell - Kenneth Griffin City of Coppell - Larry Davis Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LE'FrERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. illlllnl'iq h. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/6314372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: 84 Job No.: Location: Coppell Road at Sta. 3+50 Contractor: Ed Bell Construction Reported To: City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SO. IN. Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSI: Type Break: Conical (U.N.O.) Remarks: 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: CP072421 CP072422 CP072423 07/31/00 08/21/00 08/21/00 101970 123110 126450 7 28 28 3610 4350 4470 4410 07/24/00 4000 psi @ 28 days 416.5 of 500 S. Adli CP072424 HOLD HOLD Temperature: Ambient 97 ° F Mix 95 o F Air Content 4.50 % Slump 3.00 Inches Time of Sample: 3:00 PM Pick-Up Charge: Yes Source of Concrete: Ed Bell - 01MW N/A Ticket No.: N/A Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: City of Coppell - Larry Davis Unit Weight PCF Yield CF/CY Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C Pa e of 1 OUR LETI'ERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL W~THOUT THE APPROVAL OF STANTECH.