Peninsulas-LR 950325 ALPHA TESTING, }C.
2209 Wisconsin St., Sutte 100
Dallas. Texas 75229 DALLY FIELD REPORT
(214) 620-8911
TESTED FOR PERRY HOMES INC. OA~'E 03/25/95
HOUSTON, TEXAS
PROJECT McARTHUR PARK OUR REI~OI~IT NO. 94526--3
COPPELL , TEXAS
WEATHER' CLOUDY
TEMPERATURE RANGE: 70 TO: 80
ALPHA Rel~'elentalive:
THE ALPHA TECHNICIAN TRAVELED TO THE PRO3ECT SITE AS REQUESTED BY THE
CLIENT'S REPRESENTATIVE, TO PERFORM FIELD DENSITY TESTING AND VERIFY
SUBGRADE PREPARATION.
SUBGRADE FOR BUILDING PAD AREAS NAS VISUALLY INSPECTED TO ASSURE THAT ALL
VEGETATION HAD BEEN PROPERLY REMOVED AND THAT PAD AREAS HAD BEEN PREPARED
IN ACCORDANCE WITH GEOTECHNICAL RECOMMENDATIONS. LOTS THREE THROUGH SEVEN
AND TEN THROUGH FOURTEEN (~) WERE INSPECTED AND APPEARED TO COMPLY WITH
GEOTECHNICAL RECOMMENDATIONS.
A TOTAL OF FIVE FIELD DENSITY TESTS WERE PERFORMED ON NATURAL SUBGRADE
SOILS FOR THE LOT FILL AREAS. SEE ATTACHED REPORT OF FIELD COMPACTION
TESTS.
BUCK L. WAS INFORMED OF TEST RESULTS WHICH APPEARED TO COMPLY WITH PRO3ECT
SPECIFICATIONS.
TECHNICIAN RETURNED TO THE LABORATORY UPON COMPLETION OF SCHEDULED TESTING
AND INSPECTIONS.
(~) 8LOCK IDENTIFICATION NOT PROVIDED.
ALPHA TESTING. '~C.
2209 Wisconsin St.. Sb,,~ 100 REP-J:ITOF FIELD
Dallas, exas 7 229 COMPACTION TESTS
(214) 620-8911
TESTED FOR: PERRY HONES DATE: 03/25/95
HOUSTON, TEXAS
PROJECT: NcARTHUR PARK OUR REPORT NO. 94526--3A
COPPELL, TEXAS
TEST DATA:
TEST I r ELEV. SOIL ID OPTIMUM MAXIMUM LA, IN PLACE IN PLACE PERCENT
/
MOISTURE DRY OENSITY MOISTURE DRY DENSITY COMPACTION COMMENT*
NO. DATE DEPTH NUMBER % PCF % PCF
I 03/25 SG 1 20.0 102.0 20.7 97 95 2-A
2 03/25 SG I 20.0 102.0 21.8 99 97 2-A
3 03/25 SG i 20.0 102.0 20.6 100 98
4 03/25 SG I 20.0 102.0 21.8 101 99 2-A
5 03/25 SG 1 20.0 102.0 22.4 98 96
TEST LOCATION:
1 LOT FILL AREA LOT 3
2 LOT FILL AREA LOT 5
3 LOT FILL AREA LOT 7
4 LOT FILL AREA LOT 11
5 LOT FILL AREA LOT 13
1. FILL A. TEST RESULTS COMPLY WITH SPECIFICATIONS Respec~
2. NATURAL SUBGRADE B. COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS
3. LIME STABILIZED C. MOISTURE DOES NOT COMPLY WITH SPECIFICATIONS ~,,~~eT' i
4. CEMENT TREATED D. RETEST