Park West CC(18)-SY 891005 GEOTECHNICAL INVESTIGATION PARK WEST COMMERCE CENTER TRACT NO. 1 COPPELL, TEXAS -,.~ 9~'-,,-.¢'4, ,,_ MASON - JOHNSTON & ASSOCIATES, ~Nc. geotechnicai consultants 235 Morgan Ave., Dallas, Texas 75203-1088 (214) 941-3808 GEOL OGI&T~) GEOTECHNICAL INVESTIGATION -- PARK WEST COMMERCE CENTER - TRACT NO. 1 COPPELL, TEXAS FOR -- Prentiss Properties Limited, Inc. Dallas, Texas INTRODUCTION In accordance with the authorization of our proposal dated 15 -- May 1989, we have compieted a geotechnica± investigation for the captioned project. Plans provide for the design and construction of a one-s~ory office/~renouse building to ~e I located on Tract No. 1 of Park ~est Commerce Center in Coppell, [ Texas. tract No. 1 is on the south side of Air±ine Drive and -- west of Freeport Parkway. SCOPE The scope of the geotechnicmi investigative activities reported includes subsurface exploration and iaDoratory testing on _ seiected samples from the borings, rne resu~tzng data were used to develop general recommendations to guide design and construction of the new facility. T~is report has been prepared for the exclusive use of Prentiss _ Properties Limited, Inc. for specific application to the Park MA$ON--JOHN~OH & A~OC,ATE~, INC. DAJ.~_A~ TEX4$ ~es~ Commerce Center, Tract ~o. ~ in ~ceordance ~it~ general±¥ accepted soii and foundation engineering practices. No other warranty, expressed or implied, is made. SUBSURFACE INVESTIGATION Subsurface conditions at the site of the proposed construction -- were evaluated by six (6) NX-size core borings ~rii~ed at the approximate locations shown on P£ate 1. r~e borings were drilled and located in the field by Mason-Johnston personnel _ using a tape measure and site plan. The boring locations should be considered accurate only to the degree imp±led ~y the -- method used. ~he borings were advanced to depths on the order of 44 to 48 feet below existing grade by a truck mounted rotary drizling rig w~icn uses water as a driixing fluid. Undisturbed sampies -- of cohesive soils encountered were o~tained by a thin-walled, seamless, Shelby-tuoe sampler advanced into the soil by a rapid, continuous thrust from two balanced hydraulic rams on the drilling rig. Continuous cores of the primary sediments encountered were obtained using a double-tube core barrel equipped with a suitaoie cut~ing bit. Samples obtained from the borings were wrapped in polyethylene _ plastic to prevent changes in moisture content and to preserve · ~ MASOf~--JOHNSTON & ASSOCIATES. INC. 0~LLA.~. TEXAS in situ physical properties. All samp±es were classified as to basic type and texture in the field, labeled as to appropriate boring number and depth, and placed in core boxes for transport to the laboratory. LABORATORY TESTING -- Ali samples were c±assified in the laboratory by an experienced technician. To aid in the classification process, series of Atterberg Limits, ~oisture Contents and pH £ests were performed on representative samples. ~nese test data are presented on Plate 2. Strength properties were investigated by a series of Unconfined Compression Tests. In this test, an axial ~oad is app±ied to a latera±±y unsupported cylindrical core sample until failure occurs within the sample. ~hese test data are presented on _ Piates 3 tnrougn 11. rne expansive cnaracteristics of the overburden soils and weathered primary material were investigated in the ~aooratory by conducting Absorption-Pressure and Swell 'rests. ~hese tests provide a measure of the maximum pressure that may be expected to be generated when the soil sample is exposed to water and restrained from movement and a measure of the maximum free swel± wren vertical restraint is removed. Graphical results of these tests are presented on Plates 12 through 15. MASON--JOHNSTON & ASSOCIATES. INC. OALLA$. TEXAS SUBSURFACE CONDITIONS -- Detailed descriptions of the types, depths and thicknesses of the various strata encountered may be seen on the attached "Log of Borings". In general, from the ground surface down, .__ materials present at the site consist of varying thicknesses of moderate to highly plastic clay underlain by ~ne primary -- geologic strata identified as the Eag±e Ford Shale Formation. ~he overburden soi±s present at the proposed site are for tne _ most part residual in nature having been derived from differential weathering of the Eagle Ford Shale Formation -- during previous geologic time. ~he resulting soil cover is of varying thickness, from 6 to 9 feet. After penetrating the residual overburden materials and weathered shale, the core borings drilled at the site -- I encountered and terminated in the compact clayey shale of the Eagle Ford Shale Formation of Cretaceous Age. ~ypically, and in its unweathered state, the Eagke Ford Shale Formation generaiiy consists of dar~ to medium gray, firm, thinly iaminated, well compacted ciayey sha±e strata. £he borings _ encountered occasiona± thin oentonite or bentonitic clay seams, and thin, hard to very har~ limestone seams as noted on the -- logs. Throughout the project area, the uppermost layer of Eagle Ford Shale, ranging in thickness from about 17.5 to 28.0 feet, is tan to light gray in color, having experienced _ differential weathering in the form of leaching. '--- MASON--JONNSTON & ASSOCIATES. IN.~.. ~IALLA~. I't~XAS the Absorption-Pressure and Swell 'rests performed indicate a low to moderate potential for heave with variation in soil moisture content. Maximum swell pressure was less than 1600 psf and the maximum free-swe±l was less than 2.2 percent. -- To observe the groundwater condition at the site, an auger boring was placed next to the original Boring 5 on 21 June 198~. This boring did not produce water and caved at a deptA of ? feet. -- FOUNDATION DESIGN CONSIDERATIONS Based on the results of this investigation, structural loads :nay be transferred into tne firm, unweathered, gray shale of the Eagle Ford Shale Formation by means of straight-wal±ed auger excavated, cast-in-place, concrete shafts, dnit _ allowable loading intensities for end-bearing stress transfer . and side shear stress transfer are summarized as foilows: End Bearing Stress Transfer = 11.9 tsf Side Shear Stress Transfer, Compression = 3.8 tsf _ Side Shear Stress '£ransfer, tension = 1.9 csf -- Side-shear stress transfer is limited to the perimeter portion of the pier snaft in intimate contact with firm, gray unweathered shale extending below the base of any temporary __ casing that may be required to instaii the shafts. '' MASON--JOHNSTON & A~SOCI&TI~,. iNC. OAL. LAS. TEXAfi Accordingly, it is recommended that the upper two (2) feet of the shale formation De neglected in computing required penetrations. The side shear values provided are direct±y applicable for isolated drilled shaft foundations separated in _ plan by a clear distance of at least two (2) shaft diameters. If this spacing cannot be maintained, this office should be '-- contacte~ so tnat additional studies can be accomplished and reduced design values developed to compensate for stress over±ap oetween adjacent foundations. Settlement of shafts ~nsta±~ed in the sha~e formation should be -- less than about one-half inch. ;4uch of the settlement will occur as elastic deformation and shouid be substantially complete at the end of construction. 'me overburden soils and weathered shale strata to be -- penetrated by the drilled shafts nave a nigh sweii potential particularly within the upper zones; thus the shafts will be potential±y subjected to uplift forces caused by expansion of ~ne adjacent materials. ~he norma~ "ruLe of thumb" for SUCh conditions is to provide lioerai shaft reinforcement to resist -- these potentia± forces. ~inimum reinforcement on tne order of one percent of the shaft area is recommended. CONSTRUCTION PROCEDURES Each shaft insta±±ation should be vertical (within acceptable - tolerances), placed in proper plan location and cleaned prior MASON--JOHNSTON & ASSOCIATES. INC DALLAS, TEXAS to concrete placement. Reinforcing steel cages should be prefabricated in a rigid manner to allow expedient p±acement of oocn steel and concrete into the excavation. It is essential that the placement of both stee~ and concrete oe completed as -- soon as practical after completion of the excavation. This wiii insure that the maximum Oenefit of the bearing stratum rebound properties are utilized. In ail cases, no portion of the stratum ~eing counted on to provide structural support I should be exposed to atmospheric conditions for more than eight _ (8) hours prior to the p±acemenc of ~e concrete. The use of temporary casing should be anticipated to control groundwater seepage. ~ne casing should be instal±ed a sufficient distance into the bearing stratum to insure a water tight seal; normal~y a distance of 1 to 2 feet is adequate for t~is purpose. After the satisfactory installation of any .... temporary casing, the required shaft penetration may be excavated by machine auger ~ithin the casing in a conventional manner. If the groundwater ±evei is above the base of any temporary casing oeing uti±ized, extreme care shoui~ be taken at all times to maintain the ~ead of the plastic concrete - nigher than the static groundwater level outside the casing. In actual practice, it is desirable that the head of tne plastic concrete be appreciably above the static groundwater __ level prior to breaking of the seal between the temporary casing and the Dearing stratum. Once the seal is broken, the -- temporary casing may be slow±y removed in a vertical direction MASON--JOHNSTON & ASSOCIATES, INC- DALLAS. TF~(AS only (no rotation permitted) while additional concrete is e£evated to the top of the casing and placed through a tremie in order to connect witn the existing concrete contained within the lower portion of the shaft. FLOOR SLAB AND GRADE BEAMS Structural elements in direct contact with the natural clay soils will be potentially subject to movements associated with soil moisture variations. The magnitude of movements will vary depending on sustained pressure, soil moisture ieveis at the time of construction, and moisture variations actually experienced following construction. From plans currently available to tnis office, the finished floor elevation is 532 (~SL). ~his indicates that cutting and filling will ce needed to level the site. _ Swell calculations, which include a layer of inert fill, indicate tnat about 0.5 inches of swei± should be anticipated. -- It should be noted that the soil samples were taken in the spring during the rainy season and are therefore already partially to fully saturated. This phenomenon reduces the ._ current laboratory swell potential. If the site dries before construction of the floor slab begins, higher swell potential may be encountered at a later time when the soil enters a new seasonal cycle of wetting and drying. · ~ MASON--JOHNSTON & ASSOCIATES- INC. DAi. LA$. TEXAS GEOLOG~gT$ If this magnitude of swell cannot be tolerated by the structures, ~hen alternate schemes can be discussed at a later date in conference once perfomance and economic objectives are more firmiy estaD£isned. Alternatative measures include one or more of the following: stabi±ization with hydrated lime, more extensive cutting and fii±ing, presweliing the site, and structural floor system. To furtner reduce tne effects of movement associated with swelling clay, we recommend creating positive voids of at least 4 inches beneath grade and interior beams. -- EARTHWORK Earthwork recommendations are as follow: 1. Excavate and remove from site organic topsoil present in the construction area. 2. Scarify soils exposed in fill areas and transitional areas (cut to fil£ and fill to cut) to a depth of approximately six (6) inches, add moisture (if required), mix and recompact to a density of 92 to 98 percent of the maximum density obtained by the Standard Proctor Compaction 'rest (AS~M D-698). ~ne moisture .... content of the compacted soils should be maintained ~etween optimum and plus four percent of the optimum value (determined from ASTM D-698) until covered by fiixs. -.- MaSON--JOHNSTON & ASSOCIATES- INC. Odi. LAS, TEXAS '-- 3. P±ace fi±l soils in loose lifts not exceeding nine (~) inches and compact to a density of at ieast 75 percent of the maximum density obtained by the Standard Proctor Compaction Test (AST~ D 698). The moisture con~enc of I tne compacted so±is should Oe maintained between optimum and plus four percent of the optimum value (determined from ASr~ D 698) until covered by construction. Ii 4. Select fill material under s~ruc~ures snouid be inorganic, having ~ Liquid Limit less tnan 35 and a -- PLasticity ~ndex Detween 3 and 12. Soi±s present at the site may be used to manufacture fill material meeting ~e aoove requirements; however, substantial quantities of sand or other suitable material will be required to obtain these limits. PAVING AND DRAINAGE 'fo enhance pavement performance, it is recommended t~at clay soils exposed at grade be stabilized with hydrated lime for use as subbase. A minimum treatmenc depth of six (6) inches should _ Oe contemplated. Subject to modification during construction, a hydrated lime content of six (6) percent by dry soil weight -- (approximately 6 pounds of lime per cubic foot of SOiL treated) would be expected to effectively stabilize the subgrade soil. Soils treated with hydrated lime for use as subbase should be -- compacted to a minimum value of 95 percent of the maximum density as defined by 'texas Highway Department rest Hethod ~EX-113E and at a moisture content at ~east two (2) percentage _ points above Optimum Moisture content. This requirement is important in minimizing pos~ construccion movement and in - assuring complete hydration of the lime treated soils. Pavemenc grades should be established in anticipation of some _ vertical movement associated with expansion or concraction of the near surface clay soils. Ic is important to establish good -- surface drainage to provide for rapid removal of surface water away from ~he building and paved area. '~ne fo±lowing minimum pavement sections nave been developed for your consideration: ASPHALTIC CONCRETE L~ght Vehicular ~raffic (Parkin~L~_~D~es, Etc.) 1-1/2 inch H~AC Surface ~earing Course 3 1/2 incn HMAC Base Course -- 6 inch Lime Stabi±ized, Compacced Subgrade --- MASON--JOHN~?ON & A$$OCIAi,:S- lNG- DALLAS, TEXAS Hea~y Venicular Traffic (Service Drives, Trucks, Etc.) -- 1-1/2 inch HMAC Surface ~earing Course 5 inch HMAC Base Course 8 inch Lime Stabi±ized, Compacted Su~grade REINFORCED CONCRETE -- ~i_~n~ Venicular Traffic (Park~_~L.o~ts, Dr~ves~ Etc.) 5 inch Reinforced Concrete Paving (Re-Steel: #3 at 18 inches on center) 6 inch Lime Stabilized, Compacted Subgrade - I Heavy Vehicular traffic (Truc~s2 Service Drives2 Etc.) 7 inch Reinforced Concrete Paving (Re-Steel: #3 at -' 18 incnes on center) 6 inch Lime Stabilized, Compacted Subgrade _ In tne event reinforced concrete paving is used, it is essential that any and all reinforcing be placed so as to -- insure a minimum of 1 1/2 inch cover. It is be±ieved that one or more of the above suggested pavement sections, or some combination thereof, may be entirely suitab±e for use on this _ project. Selection of the proper section should be based on anticipated traffic ±oads, frequency, and ~ong term -- maintenance, as well as project economics. In general, asphaltic concrete sections have a ~ower initial cost, but require more frequent maintenance than the concrete surface. --- MASON--./OHNSTON & A,~OClAT6S- I~C: CJAL. LAS TEXAS Alternatively, the fol±owing pavement section may be -- considered: 1. Scarify six (6) inches of existing subgrade and __ recompact to at least 95 percent of the maximum density determined by the Standard Proctor Compaction -- Test (ASr~ D 698) at a moisture content between optimum and plus four percent of the optimum value determined by tne aoove test. 2. Cover the compacted subgrade with ground stabilization . -- fabric sucn as Mirafi 600X or 700X or equivalent ~aid to manufacturer's specification. 3. Pave with reinforced concrete at least 6 inches tnic~ providing reinforcing steel of at least No. 3 at 18 -- inches on centers both ways. Concrete cover s~ou±d be I at least 1 1/2 inches as described above. It is recommended that the soil and foundation engineer be provided the opportunity for a general review of final design and specifications in order that earthwork and foundation recommendations may be properly interpreted and implemented in -- the design and specifications. In the event that any changes in the nature, design or location of the building are planned, the conclusions and MASON--JOHNSTON & ASSOCIATES, INC, DALLAS, TEXAS recommendations contained in tnis report shall not be - considered valid unless the changes are reviewed and conclusions of this report modified or verified in writing. We appreciate the opportunity to assist in this phase of the I project. Please call us if we can oe of further service during -- later stages of design or during construction. Respectfully suOmitted, R~. .~-,~:;~ /'~ Mason-Jonnston & Associates, Inc ~J No. 5566 · AIRLINE DRIVE .... _ I ,., LEGEND N ~ CORE Bo~,~G -- MASON-JOHNSTON & ASSOCIATES, INC. GEOLOGISTS · ENGINEERS DALLAS. Tlr XAS _. LOCATION OF BORINGS PARKWEST COMMERCE CENTER TRACT. NO. I Scole: I" = IOO' COPPELL:, TEXAS '-- MJA NO. ,,5566 I DATZ 6/89 I PLAT( I .... ~ MASON--JOHNSTON & ASSOCIATES. J~C. DALLAS. TEXAS GIOLOG~&TS PARK WEST COMMERCE CENTER COPPELL, TEXAS SUGARY OF CLASSIFICATION 'rESTS Boring Depth LL PI pH ~IC UDW Unified Soil Number (Ft.) (%) (%) (pcf) Classification 1 0.0- 1.5 60 27 r~ . 8 29.8 '~'4H or OH 1 3.0-4.5 30.4 89.4 1 4.5-6.0 70 35 31.6 MH or OH 2 0.0-1.5 27.5 2 1.5-3.0 64 30 7.8 30.9 MH or OH -- 2 1.5-3.0 60 13 4% LiME 2 1.5-3.0 60 15 6% LIME 2 4.5-6.0 73 44 30.2 CH 2 4.5-6.0 65 20 5% LI~4E 2 4.5-6.0 66 17 7% LiME 3 0.0-1.5 29.1 -- 3 3.0-4.5 63 33 28.6 CH 3 4.5-6.0 7.8 28.1 3 7.5-9.0 71 36 32.4 MH or OH ' 4 0.0-1.5 57 25 7.9 30.6 [~H or OH 4 0.0-1.5 56 12 4% LIME 4 0.0-1.5 56 11 6% L~E - 4 1.5-3.0 70 34 35.4 ~H or OH I 4 3.0-4.5 29.6 89.0 - 5 0.0-1.5 31.3 5 1.5-3.0 63 31 30.6 88.6 '~H or OH 5 3.0-4.5 8.1 26.1 _ 5 4.5-6.0 71 41 29.2 CH 5 7.5-9.0 31.9 90.1 6 0.0-1.5 57 30 28.9 CH - 6 1.5-3.0 8.0 29.1 6 3.0-4.5 26.4 94.1 6 4.5-6.0 70 41 28.8 92.7 CH -- 6 13.5-15.0 30.1 91.4 Plate 2 MASON--JOHNSTON & A$SOCIaT£S. INC. O~,~.L~.~. TEX.~.S PARK WEST COMMERCE CENTER COPPELL, TEXAS SUF~ARY OF STRENGTH TESTS ON ROCK CORE -- ~oring Dep~n Qu Strain ME Number (ft.) (tsf) _{~) _ (ksi) Description _ 1 26.4-27.5 52.4 SHALE, mod. hd., with ccc. thin L.S. ! lenses, gray 1 36.3-37.2 62.1 2.0 37.9 SHALE, mod. nd., with -- ccc. thin L.S. Lenses, gray 1 42.3-43.8 2].0 SHALE, mod. nd., with ccc. thin b.S. lenses, gray 2 31.4-31.7 62.2 1.7 36.3 SHALE, mod. nd., with -- ccc. thin ~.S. [enses, gray 2 38.1-38.6 5'3.S SHALE, [uod. hd., with -- ccc. thin L.S. ienses, gray 2 44.$-45.5 1T.3 SHALE, mod. hd., ~itn ccc. thin L.S. lenses, gray 3 34.4-35.0 60.0 SHALE, mod. hd., with -- ccc. thin L.S. ±enses, gray 3 39.6-40.4 53.4 2.2 22.8 SHALE, mod. nd., with ', -- ccc. thin L.S. lenses, gray 3 43.6-44.6 13.5 SHALE, mod. hd., with ccc. thin L.S. Lenses, gray 4 30.9-32.0 72.0 SHALE, mod. hd., with -- ccc. thin L.S. Lenses, gray 4 33.6-34.5 35.6 SHALE, mod. nd., with _ ccc. thin L.S. lenses, gray 5 30.9-31.4 69.8 SHALE, mod. hd., with '- ccc. thin L.S. Lenses, gray 5 38.2-36.6 42.1 SHA~E, mod. hd., with -- ccc. thin U.S. lenses, gray -- Plate 3 MASON--JOHNSTON & A~*SOCIATES. INC. DALLAS. TEXAS PARK WEST COMMERCE CENTER __ COPPELL, TEXAS SUMMARY OF STRENGTH TESTS ON ROCK CORE --~ Boring Depth Qu Strain ME Number (ft.) (tsf) (%) (ksi) ~escr£ption -- 6 35.3-36.0 87.3 SHALE, mod. hd., with occ. thin L.S. lenses, gray ..... 6 40.7-41.6 41.5 1.9 18.0 SHALE, mod. hd., with occ. thin L.S. lenses, gray 6 42.4-q3.2 7.3 SHALE, mod. hd., with -- occ. thin C.S. lenses, gray Plate 4 - 8.96 (.~ GO 7.99 -- '~' ii ~ - 6.59 -- ~ II - ~.~ _ - 4.5~ ~ - 4.98 z ~~ - 3.58 - 3.~ -- - 2.~ - 2.~ - ~.~ -- - - 6.~ 6.~ STRESS (TSF) MASON-JOHNSTON & ASSOCIATES. INC. GEOLOGISTS-ENGINEERS DALLAS. TEXAS PARKWEST COMMERCE CENTER "- STRESS-STRAIN PLOT DATE~ 6-2-89 [JOB # 5566 Plate 5 _ ?-cs) - 1.56 o-~°3 - 1.46 ~_. - 1.19 :~ C_) 9.99 _ (_0 .7 ~ 9.86 9.69 -- 6.56 9.46 6.36 -- 9.29 9.]9 ! I I I I I I I I I I I 9.99 STRESS (TSF) H^SON-3OHNSTON & ASSOCIATES, INC. GEOLOGISTS-ENGINEERS DALLAS, TEXAS PARKWEST COHHERCE CENTER STRESS-STRAIN PLOT D^TE~ 6-2-89 I$OB # 5566 Plate 6 - 3.2{} - 2.2B - 2.~ Z~ L28 8.88 8.68 8.28 STRESS (TSF) MASON-JOHNSTON & ASSOCIATES. INC. GEOLOGISTS-ENGINEERS DALLAS, TEXAS PARKWEST COMMERCE CENTER - STRESS-STRAIN PLOT DATEr 6-2-89 IJOB # 5566 Plate 7 - 3,28 I co - 2.88 '?' - 2.68 _ LLJ C3 - 2.48 - 2,28 - 2.88 - 8.88 - 8.68 -- - 8.48 - 8.28 ~ ~ 8.88 SIR[SS MASON-JOHNSTON & ASSOCIATES. INC. GEOLOGISTS-ENGINEERS DALLAS, TEXAS PARKWEST COMMERCE CENTER - STRESS-STRAIN PLOT DATE: 6-2-89 {JOB # 5566 Plate 8 · - 3.26 ct) - 2.89 ~ - 2.66 '- O - 2,46 - 2.26 - 2.66 -I.~ _ ~ -1.~ Z 1.46 - 1.29 - 6.86 - 9.66 -- - 6.46 - 9.29 STRESS [TSF) MASON-JOHNSTON & ASSOCIATES. INC. GEOLOGISTS-ENGINEERS DALLAS. TEXAS PARKWEST COHHERCE CENTER - STRESS-STRAIN PLOT DATE~ 6-2-89 IJOB # 5566 Plate 9 - 3.26 I -- ~.D - 3.99 - 2.86 - 2;. ~ - 2.66 -- D - 2.49 - 2.29 - 1.89 - 6.88 -6.~ -- - 8.48 - 6.28 SI [SS MASON-JOHNSTON & ASSOCIATES. INC. GEOLOGISTS-ENGINEERS DALLAS. TEXAS PARKWEST COMMERCE CENTER - STRESS-STRAIN PLOT OATE~ 6-2-89 IJOB # 5566 Plate 10 · - 1.92 I _ ~ - 1,88 ~ - 1,68 I - 1.56 -- o - 1.44 - 1.92 - 1.28 -I.~ _ ~ - 8.96 z ~ - 8.84 - 8.72 -- -8.~ -8.~ - 8.98 - - 8.24 - 8.12 I I I I I I I I I I I ~ 8.88 SIR[SS MASON-JOHNSTON & ASSOCIATES. INC. GEOLOGISTS-ENGINEERS D^LL^S. TEX^S , P^RKWEST COMMERCE CENTER - STRESS-STR^IN PLOT DATE: 6-2-89 IJOB # 5566 Plate 11 MASON-JOHNSTON & ASSOCIATES. INC. GEOLOGISTS-ENGINEERS DALLAS. TEXAS ',.-.~ PARKWEST COMMERCE CENTER - PRESSURE-SWELL TEST DATE: 6-2-89 [JOB # 5566 Plate 12 /-11~.~ SWELL (~) MASON-JOHNSTON & ASSOCIATES. INC. GEOLOGISTS-ENGINEERS DALLAS. TEXAS PARKWEST COMMERCE CENTER - PRESSURE-SWELL TEST OATE: 8-16-89 IJOB # 5586 Plate 13 MASON-JOHNSTON & ASSOCIATES. INC. - GEOLOGISTS-ENGINEERS DALLAS. TEXAS ~-~ PARKWEST COMMERCE CENTER PRESSURE-SWELL TEST DATE: 6-2-89 IJOB # 5566 Plate 14 .... I-- U') U') rt- a:>-dd~z - 788.88 ~ - fl88.88 - -588.88 -188.88 SWELL (~) MASON-JOHNSTON & ASSOCIATES. INC. GEOLOGISTS-ENGINEERS DALLAS, TEXAS · ...~ PARKWEST COMMERCE CENTER - PRESSURE-SWELL TEST DATE: 6-16-89 [JOB # 5566 Plate 15 · - Mf~SON-JOt4NSTON (~ ASSOCIATES, INC. OALLAS, TEXAS __ KEY TO CLASSIFICATION USED ON LOGS ¢~ ' Gravel or Sandy Grovel GW __ o..-~ well - graded .e Gravel or Sandy Grovel GRAVEL GP ,, poor~y- eroded .... AND o. , GRAVELLY :~:~ Sl,y Gravel o, __ ~!4~; Silly Sandy Gravel COARSE GC ~ Clayey Orave~ or -- Clayey Sandy Gravel GRAINED ~ *, Sand or Gravelly Sand -- · 4 well- graded SAND SP ::'...?.'.. poetry- g,oded -- AND :.... .:.::., SAN DY '.'4: SOILS SM "-~-' S, ty Sand or · .:.: Silty Gravelly Sand SC ~ Clayey Sandy or -- ~ Clayey Gravelly Sand $11ts~ Sandy SIIts~ Gravelly -- ML SIItet or Diatomaceous Soils LOW CL ; / Lean Clays Sandy Clays, PLASTICITY / / o~ Gravelly Clays -- '~ I Organic Silts or FINE aL , ,, ,, , Or. ganic Silty Clays GRAINED -- SOILS M H Micaceous Clays or Diatomaceous Soil _ HIGH CH ~ Fat Clays PLASTICITY -' OH ~" Fat Organic Clays > -- FI L L v Reworked Soil or other ~, Miscellaneous Fill Materials __ Classification based on Cosagrande System (Proc. ASCE June,1947) HR~nN--dQHMSTI]M ~ RF~nC., INC. LOG OF' BnR I NE ~aT~CH~, CRL Cn~SULZn~TS ~LL~S, ~£XRS PARKWEST COMMERCE CENTER s~ i ar ~ ~R'rE.' 5--~-89 COPPELL TEXAS r.,._nu~ ~. ~.8 MRING wn. ! pRadr'cr: ~ TYPE: rJ~RE LDCRTIDN: SEE PI.~ .-- STANDARD PENETRATION (BPF) ~' ZNFILTRATION TEST ~-- Ln -- ~ PQ CKE'I' PEX.-'CTRDH£TER :2 ~ ~" HRTER i RL DESCE I PT 1 ON ~ .j n- ~ ~ ~ERD, INB X, TSF /~ CT.AY, v. stiff, brown × --5.B- CLAY, stiff, lt. brown CLAY, v. stiff, sli. sandy, X tan & lt. gray - 7.5 ~__~ SHALE, wea., med. firm, ~A~_i tan & lt. gray ~.- H~nN.-,JOH~TnN & n~nc.~ iNC. LnG DF' BORIN~ __ b~LRS, TCXRS PARKWEST COMMERCE CENTER ~RT(: ~ COPPELL TEXAS ~Ri~ ND. 1 PR~dECT: ~ TYPE: ~E ~ CORE ZNRILT~ATION TEST m -- ~ ~ ~ HRTER 1 RL ~ESCR I PT 1 OH SHALE, mod. hard, w/occ. thin L.S. lenses, gray --~.5 __ ._~ - bentonitic clay band - -- ~- -traco of bontonitic clay - ~.5~- ~-- 9. B B.B - 4B.B - - ~.S ~ " ~TAL ~ e - - 45.8-- HP, SDN-dDHI~TQN & R':JSO¢., INC. LnG nF BnRING I~RLLRC6 'I'EXRS PARKWEST COMMERCE CENTER SH~-r I Or 2 ~:,R'rE= 5'-25-89 COPPELL TEXAS ~.r,u~ .EL-~. PRDdECT: ~ TYPE= C0~E LDCRTInN: SEE PLAN __ STANDARO PENETRATION (8PF) "~ =~ CRRE TNFNmTRA?mON TEST Ul ~ ~ PO~KE'r PE~L"TRnNETEI~ ~ RERI~ INB X, TSF WW ~- rr .J6J ~~ --- CLAY, hard, brown X --5. B-'~ CLAY, v. stiff, sli. sandy, tan & lt. gray _~ SHALE, wea., med. firm, L tan & lt. gray -- 7.5 -~+~ HRSnN-dJ:]HIdSTI]N t FI5513¢., INC. LnG rlF BnR 1 NE b"EDTE:CHId] CRL ¢[LNSLJLTRNTS ri:IR _._ OFILLRS, T£XRS PARKWEST COMMERCE CENTER sHc~r 2 D? 2 DRTE: 5-P.5-8,9 COPPELL TEXAS GP. OUND ~LE'V. 8.8 PROd£¢T: 5566 TYPE: CORE LDCRTIDN: SEE PLAN -'- STANDARD PENETRATION ~ CORE INFILTRATmON ~ "~ "" HBTER l RL 5ESCR ~ PT 1 ON m- tan & lt. gray - 38.8-S-? SHALE, mod. :hard, ~/occ. _ ---~ th±n T..$. lenses, g:ay _ __ - bentoni~ic clay band 45.~S_~~ - bentonitic clay band ~nsn~-da~STn~ ~ Rssnc., i~C. LnG DF BOR 1 NE ~aZ~ C.. ~ C~ C~SU~TR~TS .... DRLLRS, ZCXRS PARKWEST COMMERCE CENTER ~ t ar 2 ~mc: ~ CDPPELL TEXAS ~Du~ ~. PRDdECT: ~ TYPE: ~E LD~RTIDN: S~ ~ '--' STANDARD PENETRATI~ (BPF) ZNFILTRATiON TEST m -- ~ PDCK~ ~ ~ ~ HRTEE I RL DESC~ I PT 1 ON _ ~ ~ ~ ~ ~ RE~ lNG X/ _ CLAY, v. stiff, brown X -- - 2.5 X X - X / CLAY, v. stiff, sli. sandy, X 7.5_.-/,-/' tan & lt. gray ~ × -- ~--~ SHALE, wea., med. firm, --18. B-~_+~ tan & it. gray - 15. B --'t~ - 17.5 -~q~.~ HF~I:IN.-dnH~TnN ~, R~n¢., INC. LnG nF' Bnl~ 1 NE b*~QT£¢H~I ('RL CGN~-'LILTRNT5 I:*GR I~RLLRS, ~XRS PARKWEST COMMERCE CENTER smt-r 2 or' 2 ~m'z= 5-25-89 COPPELL TEXAS r=,,.nu,~ e.~. ~1~ ~1~. 3 PRfldECT: ~ TYPE;: CORE LflCRT I rllq-' SEE PLAN .--- STANDARD PENETRATION (BPF} ~ CORE ~NRIL?RATmON T~'$T ~ ~ ~ P0 CK'------------------~T ~ ..j r-t- ,.. t.. R~RI)ING X, ,-% I, Ltl IJ'l L~J t, "~ ~ t I ~ I ~ ~ I SHALE, wea., med. firm, tan & lt. gray -- _ 27.5 ~__~.~,~ ~.~ SHAT.E, sli. wea., med. 5±rm '~-~ to firm, gray & tan -- ~. ~ --~_~. _ ~_~ SHALE, mod. hard, w/occ. ~--' thin L.S. lenses, gray -- -- ~.5 ~--' - ~.§ ....__ iow angle fracture -~.§----- = bentonitlc clay band -- ---- - Bentonitic clay band 8oB 15.1 -- - ~5. B --~_'-= - TOTAL DEPTH , 47.15 HF~nN-,JnH~Tnlq ~ R~n¢., INC. LEG G~ ~G~ lNG ~QTE~HNI ~L ~G~TRNTS ._. 6RLLR3, ~XR~ P~NEST COH~E~CE CENTE~ ~ ~ ~¢ 2 ~R~: ~ COPPELL TEX~S ~u~ ~. $TANOARO PENETRATION (8PF) ZNFILTRATION TEST ~ ~ ~ HRTE~ I RL bE5~ 1 PT I ON ._ ~ ~ ~ ~ ~ RERb lNG X/ TSF -- ~; C~A~, v. s~, b~o~ X ~ CgY, v. stiff, dk. brown --5.8 CLAY, v. stiff, sli. sandy, X It. tan & lt. brown -'- ~ SHOE, sev. wea., med. firm, 2~ tan & lt. gray - - 7.5~-- 8H~BE, weathored, firm, tan -- 1~.~ . _. -15.8 r_~ .... 'T~ '- - HRSn~-dnHNSTn. ~ R~n¢., 1.¢. LOG OF ~0~ i NG __ 5~LRS, ~X.S PARKWEST COMMERCE CENTER ~ 2 nr 2 ~RTE= ~ COPPELL TEXAS ~ou~ ~. 8.8 ~i~ ~o. 4 PR0dECT: ~ TYP~: ~E ~CRT In~ S~ -'- ~TANDARD ~ENETR~TI~ (BPF) ZNFILTRATION TEST m -- ~ PD~K~ ~ ~ ~ HHTEE i HL DESCR I PT 1 ON ~ ~ ~ S~, mod. ha~, ~/occ. v. thin t.S. le~ses, - ~.5-~ 3.5 3.5  - be~tonitic cla~ -~.B -- bentonitic cl~y se~ .... ~.5 ~2 - ~ 18.8 -- - hard limostone band -~.5 -- -~= = bentonitic clay band -,,., ~5 -- - -C-~ 7.s 1.5 -- ~ - th~n hard l~mostone band k'~. - 47.5-- ~TAL ~ , 47.8 v HRsnN-JnHX.GTDX t R~D¢., INC. LnG []F RnR I NG G[:DT£CHI41 ~L O]NSLJLTRNTS _ ORLLRS, TEXRS PARKWEST COMMERCE CENTER ~ I nF' 2 DRTE: 5"~ COPPELL TEXASm3RIN~, ND. 5n~'nU~ ~LE-'V. 6.6 PRndECT: ~ TYPE: C{]RE LDCRT ION: SEE PLAN -- STANDARD PENETRA?ION (BPF) ~ CDRE ZNFILTRA?ION TEST cn -- P., PnCKL-r PENL'rRnHE'TER _~_ .~ ud HRTE:R I RL ])ESCR I PT I DN ~ " _ c:] ._J n- ,-, cd RE:RI) IN6 X/ TSF' -- ~., CLAY, v. stiff, brown -- 2.5 , X -- ~CLAY, v. stiff, tan & it.gray ~ SHALE, weathered, med. firm, ~ tan & lt. gray -- HFL~ON-OnHNSTON & RSSO(., INC. LO~ OF BORING ~L.S, ~x.s PARK~EST COMMERCE CENTER ~ ~ ar 2 0n~: ~ COPPELL TEXAS~.~.~ ~u. 5~uu~ ~. 8.8 PROdECT: ~ TYP~: ~E ~CRT ION: S~ ~N ...... STANOARO PENETRATION (BPF) · ~ C~R~ ZNFILTRATION T~T m -- ~ P~C~ ~ ~ ~ HRTEE I RL DESCR 1 PT i DN ~ ~ .... ~ SHALE, ~ea~he~ed, med. - ~.5 -~ -~-~ SHALE, mod. ha~d, ~/occ. -- ~ thin L.S. lenses, gray - - ~.5~- ~-~ i8.8 9.7 ~8 - ~.5 -~ ~ bentonitic clay band -- ~.5 ---' - bentonitic clay band 9. B 8.8 -- _ TOIAL ~ ' 47.8  - 47.5-- HFLSDN-dnHIdSTI]N ~ R55nC., INC. LnG nF BnR I NE; b-'EDT£CHI~I GL CDNSULTRNTS ._ I)RLLRS, T£XR5 PARKWEST COHHERCE CENTER sH~-? ] nr 2 ORTI~: ~ COPPELL TEXASMRIN6 MD. 6GP'nu"~ ~LEV. pRnd£cr: ~ TYPE= CORE LDCRT ION = SEE P~N STANDARD PENETRA?ION (BPF) ~ CORE '~' ZNFILTRATION TEST m -- ~ PG CC .L"I' P~NETRflHETER ::2 '-~ '" HRTE~ I IlL I)ESCR 1 PT ~ ON ~' .-. c,: __ r:] ._l cc rd ~ Rl~Rl)ildl~ X, TGI:' cc [.d '~'" '~" Ldb. J ~ ~. ........ .-- CLAY, stiff, lt. brown X - 2.5 X CLAY, v. stiff, lt. tan X - 5.8 x ~ SHALE weathered, med. firm, ~-- tan & lt. gray _ 17.5 ._-_~_~- .~.._- I~RsnN-dnHNSTnN ~ Rssn¢., ~NC. LnG rlF' Bt]RING b"ErITI~CHId I OIL CDI45'LILTRNT5 F'DR ...... I)RLLRq, ~XRS PARKWEST COHIgERCE CENTER sd~-r 2 or 2 r)R*r~.' 5-25-89 COPPELL TEXAS r,~_nu,e ~L~V. e.e PRDd£¢T: SS6~ TYPE~: C0~E Ln(~RTIDM: SEE PLAN STANOARO PENETRATION (SPF) + =~ CDEE 'r NFILTR~,? ION T[$'r Ltl ~ ~ PO(~KE'r PEN[*TRrlH ETmEI~ ::2 "J '" HRTER I RL D, ESCR I PT 1 ON ~- -- .~_w~ SHAT.~., weathered, med. 5±tm, ~_-~ tan & lt. gray -~.8 -- th'in ~.$. lonses, gray