Loading...
ST9801-LR000713 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 63 Job No.: Coppell Road, Retaining Wall Contractor: Ed Bell Construction Reported To: City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN. 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: Field Number: CP071301 CP071302 CP071303 Test Date: 07/20/00 08/10/00 08/10/00 Maximum Load, LBS: 99150 108100 113390 Age When Tested, Days: 7 28 28 Compresslye Strength, PSI: 3510 3820 4010 Average Strength, PSI: 3920 Type Break: Conical (U.N.O.) Remarks: 07/13/00 3500 psi @ 28 days 10 of 13 D. Lenard CP071304 HOLD HOLD Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 99 ° F 2:30 PM Pioneer/9339 City of Coppell- Larry Davis Mix 97 o F Air Content 3.50 % Slump 2.25 Pick-Up Charge: Yes N/A Ticket No.: 510112 Inches Unit Weight PCF Yield CF/CY Sign Pa~ Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LE'FI'ERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 63 Job No.: Coppell Road, Retaining Wall Contractor: Ed Bell Construction Reported To: City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SO. IN. Field Number: Test Date: Maximum Load. LBS: Age When Tested, Days: Compressive Strength, PSh Average Strength, PSI: Type Break: Conical (U.N.O.) Remarks: 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: 07/13/00 3500 psi @ 28 days 10 of 13 D. Lenard CP071301 CP071302 CP071303 CP071304 07/20/00 08/10/00 08/10/00 HOLD 99150 7 28 28 HOLD 3510 Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 99 o F Mix 97 o F Air Content 3.50 % Slump 2:30 PM Pick-Up Charge: Yes Pioneer/9339 N/A Ticket No.: 510112 Unit Weight PCF 2.25 Inches Yield CF/CY City of Coppell - Larry Davis ~gne~~~t~ Page 1 Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LE'R'ERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH. bibleering b. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: Location: 63 Job No,: Coppell Road, Retaining Wall Contractor: Ed Bell Construction Reported To: City of Coppell - Kenneth Griffin, P.E. (6 x 12 Inch) Nominal Cylinder Size: Area - 28.27 SQ. IN. 1520COP03 Date Cast: Specification: Quantity Represented: Sampled By: By Order Of: Field Number: Test Date: Maximum Load, LBS: Age When Tested, Days: Compressive Strength, PSI: Average Strength, PSh Type Break: Conical (U.N.O.) Remarks: 07/13~00 3500 psi @ 28 days 10 of 13 D. L. enard CP071301 CP071302 CP071303 CP071304 07/20/00 08/10/00 08/10/00 HOLD 99150 7 28 28 HOLD 3510 Temperature: Ambient Time of Sample: Source of Concrete: Fine Aggregate: Coarse Aggregate: Water: Cement: Fly Ash: Admixture(s): Distribution: 99 o F Mix 97 ° F Air Content 3.50 % Slump 2:30 PM Pick-Up Charge: Yes Pioneer/9339 N/A Ticket No.: 510112 Unit Weight PCF 2.25 Inches Yield CF/CY City of Coppell - Larry Davis ,/81,.,gned------ Page. 1 Test Methods: ASTM C 31, C 39, C 173, C 192, C 231 and C 1064 OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED AND APPLY ONLY TO THE SAMPLES TESTED. TEST RESULTS ARE NOT NECESSARILY INDICATIVE OF THE QUALITY OF APPARENTLY IDENTICAL OR SIMILAR SAMPLES. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL WITHOUT THE APPROVAL OF STANTECH.