Riverchase (6.4)-CS 950823Coppell, Texas 75019
Mr. Eugene Middleton, P.E.
Winkelmann & Associates, Inc.
12800 Hillcrest Rd., Suite 200
Dallas, Texas 75230
P.O. Box 478
Coppell, Texas 75019
214-462-0022
August 23, 1995
Healthways Family Medical Center
Riverchase Plaza Lot B-R
Dear Mr. Middleton:
The City of Coppell has received and reviewed the referenced plans and has the following comments
to offer:
1. The abstract number shown on the title sheet is shown incorrectly.
2. Standard details should not be included in the plans unless they are being modified. If
details are modified, provide note stating the changes.
3. Change general note (10) to require silicone joint sealant.
4. All dimensions need to be shown on Dimensional Control Paving Plans.
5. Tree islands are required every 12 spaces as per the Zoning Ordinance. If you have any
questions or comments contact Gary Sieb, Planning Director, at 304-3675.
6. Provide an on-site drainage system.
7. On water/sanitary sewer utility plan sheet address the following comments:
a. Provide a cleanout adjacent to Riverchase Drive as shown on Sheet 4,
b. Label sanitary sewer line,
c. A double check valve is required at water meter located on MacArthur Blvd. Also,
this needs to be placed in the right-of-way or easement,
d. Provide a note that all water taps will be wet taps.
8. Howard Pafford, utilities Superintendent, has a comment regarding the proposed slope of
4" sanitary sewer line. The maximum allowable velocity in sewer line is 15 fps. If you
have any questions contact Howard at 304-3545.
There are various other minor comments throughout the plans. Once these comments have been
addressed, the revised set of plans should be resubmitted to the City for review. If you should have
any questions concerning these comments, please contact me at 304-3681.
Sincerely,
Michael A. Martin, E.I.T.
Graduate Engineer