Riverview Estates-LR 970408ALPHA TESTINL'~. ~NC.
2209 Wisconsin St., Suite 100
Dallas, Texas 75229
(972) 620-8911
REPOHT OF FIELD
COMPACTION TESTS
HUFFINES & PARTNERS
TESTED FOR C/O CCM ENGINEERING DATE
04/08/97
PROJECT
RIVERVIEW ESTATES
COPPELL, TEXAS
OUR REPORTNO. 97224-7
TEST DATA:
TEST DATE ~ SOIL ID O~MUM M~I~M ~S IN PLACE IN PLACE PERCE~ COMMENT
~ISTURE ~Y DENSI~ ~IS~RE ~Y DENS~ COM~I~
NO. NUMBER % ~F % ~F
1t 04/08 FG-3.0 2 20.5 99.5 22.4
12 04/08 FG-1.0 2 20.5 99.5 22.4 96 96 1-A
13 04/08 FG-3.0 2 20,5 99,5 21.6 97 98 1-A
14 04/08 FG-1.0 2 20.5 99.5 22.5 95 96
15 04/08 FG-3.0 2 20,5 99.5 22.1 97 97 1-A
16 04/08 FG-i.O 2 20.5 99.5 22.3 96 9'/
TEST LOCATION:
11 SANITARY SEWER BACKFILL - LINE ~A" AT STATION #13+00
12 SANITARY SEWER BACKFILL - LINE ~A" AT STATION #13+00
13 SANITARY SEWER BACKFILL - LINE "E" AT STATION # 0+75
14 SANITARY SEWER BACKFILL - LINE ~E# AT STATION # 0+75
15 SANITARY SEWER BACKFILL - LINE ~B" AT STATION # 2+00
16 SANITARY SEWER BACKFILL - LINE ~B" AT STATION # 2+00
1. FILL
2. NATURAL SUBGRADE
3. LIME STABILIZED
4. CEMENT TREATED
CG01083-18
* A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS ~
B. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS / Respectfully
C. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONS / /
D. RETEST Pat Ste~ST~N~' INC.