SC-Coppell HS-LR 991129FUGRO SOUTH, INC. ~
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484-8301: Fax (972) 620-7328
STRUCTURAL STEEL INSPECTION REPORT
CLIENT: Coppell lSD c/o Dal - Mac DATE: November 29, 1999
PROJECT: Coppell High School PROJECT NO: 0791-2208
REPORT NO: 5 PAGE 1
Owner:. Coppell lSD
Architect: SHW Group
Engineer: SHW Group
Contractor: Dal - Mac
Fabricator: Alpha Industries
Location of Project: Coppell, Texas
Inspection Performed At: Job Site X Fabrication Shop
DESCRIPTION OF INSPECTION: Structural Steel Inspection } Visual Inspection of Welds on ~Str I Steel - Metal Deck Units} or
Ultrasonic Testing or Magnetic Particle In~pection of Weid~ and Inspection of Bolted Connections for compliance to Project
specifications, Contract Documents, Drawings, and Governing Code~ } AWS, AISC, ASTM, SJI, ASNT, ANSI.
See attached Field Re~orta for Soeciflc Items Inseected or Tested and Tyee of InSl}ection or Testing oerformed
Location of Inspection: See attached Field reports for Specific Areas Inspected or Tested.
Results of Inspection: Project Complete Project Incomplete
Fabrication Is:
Erection Is: : Area A / X
In Compliance Area A
Non Compliance
Note: Workmanship type deviations noted dudng Inspection. which are being corrected at time of Inspection. are not being listed on Report.
NOTE: Inspection was performed to vedfy compliance to Project specifications, Contract Documents. Drawings. and Governing
Codes} AWS. AISC. ASTM. SJL, ASNT. ANSI
Inspected By: Doug Post, AWS/Certifled Welding Inspector, ASNT/Certified Level 2 (UT. MT)
Distribution: DaI-Mac Construction - Damon Norman
City of Coppell - Larry Davis /
Coppell lSD - Mickey Harper
SHW Group - Joe Craddock
SHW Group - Mike Elmore
JRJ Paving - Jeff Williford
Doug Post
STR-"
FUGRO SOUTH, INC. ~
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
NON - COMPLIANCE REPORT
CLIENT: Coppell lSD c/o Dal- Mac DATE: November 29, 1999
PROJECT: Coppell High School PROJECT NO-' 0791-2208
REPORT NO: 5 PAGE2
Number Description Location Deviate Corrective Action Taken
From
I Misiocation of bolt holes Area A, 2nd level Drawings Beam connection, angles have
on beam to column been welded @ (3) places to
11/9/99 connection, bolts could AM I~ A5, A6 column flange. (No RFI)
not be installed
2 Mislocation of anchor Area H G 10 (~ Drawings Corrections have been made per
bolts on column base GH, attachment C RFI III, except bolt spacing was
1 1/18/99 plate on RFI Iii moved I 1/2 wider due to rebar in
C.I.P floor. Depth of holes are in
compliance. New RFI has been
submitted by DaI-Mac showing a
change in bolt pattern width.
NOTE: Architect and Engineer should advise on acceptability of all noted deviations
Inspected By: Doug Post, AWSICertifled Welding Inspector, ASNTICertified Level 2 (UT, MT)
STR-".
FUGRO SOUTH, INC.
2880 Virgo Lane: Dallas. Texas 75229
Ph (972) 484.-8301; Fax (972) 620-7328
FIELD ERECTION - MEMBERS INSPECTED or TESTED
CLIENT: ~_~p~-/I '~ t% DATE: '(( ~-'
~,,.~,~. _~..~_...L~,.,.,~ PROJECT Nb:
PROJECT: (:::-,}, ~...-- !: ;"
REPORT NO: ~, PAGE OF
Type of In$1~ction Location In Non
Compliance Compliance
Check Bolt Tightening Procedure
oh.~ ~ne=n ~. R. uir. Siz. of ,olts ~h,° ~-~, ~, ~ ,~ i - ~ ~ ~
Check Connection fl~' Required NO. of Bolts !
Check Bolt Tightness wifl~ Torque Wrench
Visual Inspection of Tension Control Bolts
Beadng Bolted Connections / Snug Tigttt
Connection / Turn of Nut
Check
Bolted
Check Gap on Loaded Indicator Washers
Check Size. Leng~. and No. of Shear Studs
Check Gauge of Comlx~ite Deck
Check Gauge of Roof Deck
Check Size Lap Connection on Composite Deck
Check Size Lap on Roof Deck
Check Installation of Rddging on Joists / Oirdem
Check Installation of Expansion Anchors i
Check Grout
Repcrt. hand wdtt, en at time of inspection by Field Inspector ~' in box = In compliance
Report, will be submitted as is and not typed X in box = Non compliance } See Non compliaP, ce report
Inspected By: Doug Post, AWS/Certified Welding Inspector. ASNTICertified Level 2 (UT. MT)
STR-3
FUGRO SOUTH, INC.
2880 Virgo Lane: 0alias, Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
FIELD ERECTION - MEMBERS INSPECTED or TESTED
PROJECT:'
REPORT NO: PAGE OF
Type of In~pectlon I Location
In
Non
Compliance Compllanca
Check size and P¢ojec~on of Anchor Bott
Check Anchor Bolt Group
Check Nuts on Anchor BOlts / Tight
Check Ereclion Procedures
Check for Damaged Members
Check Welders Qualification Records
Check Fit-Up of Welded Connections
Visual Quality of Welds on Sl~uctuml Steel
Visual Quality of Welds on Joists / Girders
Visual Quality of Welds on Misc Steel
Visual Quality of Welds on Pm Cast Connection
Visual Quality of Welds on Composite Oec~
Visual Qualit~ of Welds on Roof Dec.~
Visual Quality of Welds on Shear Studs
Check Size of Welds on Structural Steel
Check Size of Welds on Joists / Girders
Check Size of Welds on Misc Steel
Check Size of Welds on Pre Cast Connection
Check Size of Welds on Composite ./Roof Deck
Check Size of Welds on Shear Studs :
Ultrasonic Testing of Welds
Mag Particte Testing of Welds
Re~ort hand written at time of inspection by Field Inspector ~' in box = in compliance
Re~o~ will 13e submitted as is and not typed X in box = Non compliance } See Non com;31[ance rei3o~
Inspected By: Doug Post, AWSiCertified Welding Inspector, ASNT.."Certified Level 2 (UT. MT)
S-Ri2
FUGRO SOUTH, INC. ~
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484-6301; Fax (972) 620-7328
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Coppell lSD, c/o Dal - Mac Construction Co. Report Date: November 29,1999
PROJECT: Coppell High School, Coppell, Texas Project No.: 0791-2208
SAMPLE DATE: October 28, 1999
CONTRACTOR: Dal Mac
TICKET NO.: 6110237 CONCRETE SUPPLIER: Lattimore
AMBIENT TEMP. (°F): 63 PLANT/TRUCK: 6/736
CONCRETE TEMP. (°F) (ASTM C-1064): 67 MIX ID NUMBER: 16
TIME BATCHED: 2:52 AIR (%) (ASTU C.231):
TIME SAMPLED: 3:30 WATER ADDED (gal): 5
WEATHER CONDITION: Partly cloudy SLUMP (in.) (ASTM C-143) · 4.50
LOCATION OF PLACEMENT: Slab, northeast corner of building, 10 feet north, 10 feet west
CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12", 28.27 square inches
TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE
CYLINDER AGE DATE LOAD STRENGTH STRENGTH
NUMBER (days) TESTED (pounds) (psi) (psi)
CHC 289 7 11/04/99 105000 3710 3000/28 days
CHC 290 28 11/25/99 142000 5020
CHC 291 28 11/25/99 140000 4950
CHC 292 Hold
Fracture mode is (A) unless otherwise noted
Specifications: Making & ASTM C-31 Testing ASTM C-143. Typesof r~ ~-]-~ [~-~ ~
Cudng: Methods: ASTM C-39 Fracture: AVXI ~/~J I/J I lB C D
REMARKS:
Technician: Pompey McGee FUGRO SOUTH INC.
Reviewed By: - ,~
SMH/bg
Distribution: DaI-Mac Construction - Damon Norman
City of Coppell - Larry Davis --
Coppell lSD - Mickey Harper
SHW Group - Joe Craddock
SHW Group - Mike Elmore
JRJ Paving - Jeff Williford
FUGRO SOUTH, INC.
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Coppell lSD, c/o Dal - Mac Construction Co. Report Date: November 29,1999
PROJECT: Coppell High School, Coppell, Texas Project No.: 0791-2208
SAMPLE DATE: October 28, 1999
CONTRACTOR: Dal Mac
TICKET NO.: 709132 CONCRETE SUPPLIER: Lattimore
AMBIENT TEMP. (°F): 63 PLANT/TRUCK: 6/781
CONCRETE TEMP. (°F) (ASTM C-1064): 65 MIX ID NUMBER: 16
TIME BATCHED: 3:40 AIR (%) (ASTM C-231):
TIME SAMPLED: 4:30 WATER ADDED (gal): 0
WEATHER CONDITION: Partly cloudy SLUMP (in.) (ASTM C-143): 5
LOCATION OF PLACEMENT: Slab northeast corner of building, 10 feet north, 10 feet east
CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12", 28.27 square inches
TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE
CYLINDER AGE DATE LOAD STRENGTH STRENGTH
NUMBER (days) TESTED (pounds) (psi) (psi)
CHC 293 7 11/04/99 110000 3890 3000/28 days
CHC 294 28 11/25/99 131000 4630
CHC 295 28 11/25/99 129000 4560
CHC 296 Hold
Fracture mode is (A) unless otherwise noted
Specifications: Making & ASTM C-31 Testing ASTM C-143, Typesof [~] ~ ~
Cudng: Methods: ASTM C-39 Fracture: A B C D
REMARKS:
Technician: Pompey McGee FUGRO SOUTH INC.
Reviewed By: - /~'
SMH/bg
Distribution: DaI-Mac Construction - Damon Norman
City of Coppell - Larry Davis
Coppell lSD - Mickey Harper
SHW Group - Joe Craddock
SHW Group - Mike Elmore
JRJ Paving - Jeff Williford
FUGRO SOUTH, INC. ~
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Coppell lSD, c/o Dal- Mac Construction Co. Report Date: November 29,1999
PROJECT: Coppell High School, Coppell, Texas Project No.: 0791-2208
SAMPLE DATE: October 28, 1999
CONTRACTOR: Dal Mac
TICKET NO.: 709146 CONCRETE SUPPLIER: Lattimore
AMBIENT TEMP. (°F): 65 PLANT/TRUCK: 6/736
CONCRETE TEMP. (°F) (ASTM C-1064): 67 MIX ID NUMBER: 16
TIME BATCHED: 4:10 AIR (%) (ASTM C-231):
TIME SAMPLED: 5:00 WATER ADDED (gal): 0
WEATHER CONDITION: Partly cloudy SLUMP (in.) (ASTM C-143): 5
LOCATION OF PLACEMENT: Slab northeast corner of building, 10 feet north, 30 feet east
CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12", 28.27 square inches
TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE
CYLINDER AGE DATE LOAD STRENGTH STRENGTH
NUMBER (days) TESTED (pounds) (psi) (psi)
CHC 297 7 11/04/99 106000 3750 3000/28 days
CHC 298 28 11/25/99 127000 4490
CHC 299 28 11/25/99 130000 4600
CHC 300 Hold
Fracture mode is {A) unless otherwise noted
SpecJfications: Making & ASTM 0-31 Testincj ASTM C-143, Typesof [::~ ~-~ ~7~ [~
Curing' Methods: ASTM C-39 Fracture: A[/kJ L~ [."'~ ;.JB C D
REMARKS:
Technician: Pompey McGee FUGRO SOUTH INC.
Reviewed By: ' (
SMH/bg
Distribution: DaI-Mac Construction - Damon Norman
City of Coppell - Larry Davis
Coppell lSD - Mickey Harper
SHW Group - Joe Craddock
SHW Group - Mike Elmore
JRJ Paving - Jeff Williford
FUGRO SOUTH, INC.
2880 virgo Lane; Dallae, Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Coppell lSD, c/o Dal- Mac Construction Co. Report Date: November 29, 1999
PROJECT: Coppell High School, Coppell, Texas Project No.: 0791-2208
SAMPLE DATE: October 28, 1999
CONTRACTOR: Dal Mac
TICKET NO.: 709156 CONCRETE SUPPLIER: Lattimore
AMBIENT TEMP. (°F): 66 PLANT/TRUCK: 7/804
CONCRETE TEMP. (°F) (ASTM C-1064): 67 MIX ID NUMBER: 16
TIME BATCHED: 4:20 AIR
TIME SAMPLED: 6:00 WATER ADDED (gal): 10
WEATHER CONDITION: Partly cloudy SLUMP (in.) (ASTM C-143): 5
LOCATION OF PLACEMENT: Slab northeast corner of building, 10 feet north, 90 feet east
CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12", 28.27 square Inches
TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE
CYLINDER AGE DATE LOAD STRENGTH STRENGTH
NUMBER (days) TESTED (pounds) (psi) (psi)
CHC 301 7 11/04/99 107000 3780 3000/28 days
CHC 302 28 11/25/99 136000 4810
CHC 303 28 11125/99 134000 4740
CHC 304 Hold
Fracture mode is (A) unless otherwise noted
Specifications: Making & ASTM C-31 Testing ASTM C-143. Typesof [~ [~ ~
Curing: Methods: ASTM C-39 Fracture: A B C D
REMARKS:
Technician: Pompey McGee FUGRO SOUTH INC.
Reviewed By:' ,~
SMH/bg
Distribution: Dal-Mac Construction - Damon Norman
City of Coppell - Larry Davis
Coppell lSD - Mickey Harper
SHW Group - Joe Craddock
SHW Group - Mike Elmore
JRJ Paving - Jeff Williford
FUGRO SOUTH, INC. ~
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Coppell lSD, c/o Dal - Mac Construction Co. Report Date: November 29, 1999
PROJECT: Coppell High School, Coppell, Texas Project No.: 0791-2208
SAMPLE DATE: October 28, 1999
CONTRACTOR: Dal Mac
TICKET NO.: 7079154 CONCRETE SUPPLIER: Lattimore
AMBIENT TEMP. (°F): 66 PLANT/TRUCK: 7/1045
CONCRETE TEMP. (°F) (ASTM C-1064): 70 MIX ID NUMBER: 16
TIME BATCHED: 5:27 AIR (%) (ASTM C-231):
TIME SAMPLED: 6:20 WATER ADDED (gal): 0
WEATHER CONDITION: Partly cloudy SLUMP (in.) (ASTM C-143) .' 5
LOCATION OF PLACEMENT: Slab norheast corner of building, 10 feet north, 50 feet east
CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12", 28.27 square inches
TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE
CYLINDER AGE DATE LOAD STRENGTH STRENGTH
NUMBER (days) TESTED (pounds) (psi) (psi)
CHC 305 7 11/04/99 104000 3680 3000~28 days
CHC 306 28 11/25/99 125000 4420
CHC 307 28 11/25/99 127000 4490
CHC 308 Hold
Fracture mode is (A) unless otherwise noted
Specifications: Making & ASTM C-31 Testing ASTM C-143, Typesof ~1 ~-] r~ r-]
Cudng: Melhods: ASTM C-39 Fracture: AV~I ~xJ [/I I lB C D
REMARKS:
Technician: Pompey McGee FUGRO SOUTH INC.
Reviewed By: - ~f
SMH/bg
Distribution: DaI-Mac Construction - Damon Norman
City of Coppell - Larry Davis
Coppell lSD - Mickey Harper
SHW Group - Joe Craddock
SHW Group - Mike Elmore
JRJ Paving - Jeff Williford
FUGRO SOUTH, INC.
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Coppell lSD, c/o Dal - Mac Construction Co. Report Date: November 29, 1999
PROJECT: Coppell High School, Coppell, Texas Project No.: 0791-2208
SAMPLE DATE: October 28, 1999
CONTRACTOR: Dal Mac
TICKET NO.: 7079164 CONCRETE SUPPLIER: Lattimore
AMBIENT TEMP. (°F): 67 PLANT/TRUCK: 7/1008
CONCRETE TEMP. (°F) (ASTM C-1064): 71 MIX ID NUMBER: 16
TIME BATCHED: 6:45 AIR (%) (ASTM C-231) .'
TIME SAMPLED: 7:30 WATER ADDED (gal): 0
WEATHER CONDITION: Partly cloudy SLUMP (in.) (AS?M C-~43): 5
LOCATION OF PLACEMENT: Slab northeast comer 10 feet north, 70 feet east
CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12", 28.27 square inches
TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE
CYLINDER AGE DATE LOAD STRENGTH STRENGTH
NUMBER (days) TESTED (pounds) (psi) (psi)
CHC 309 7 11/04/99 95000 3360 3000/28 days
CHC 310 28 11/25/99 122000 4320
CHC 311 28 11/25/99 119000 4210
CHC 312 Hold
Fracture mode is (A) unless otherwise noted
Specifications: Making & ASTM 0-31 Testing ASTM C-143, Typesof ~-'1 [-]-] ]'~ r--]
Curing: Methods: ASTM C-39 Fracture: AI/XJ V~ I/'] LJB c D
REMARKS:
Technician: Pompey McGee FUGRO SOUTH INC.
Reviewed By: ,,'- ,/
SMH/bg
Distribution: DaI-Mac Construction - Damon Norman
City of Coppell - Larry Davis
Coppell lSD - Mickey Harper
SHW Group - Joe Craddock
SHW Group - Mike Elmore
JRJ Paving - Jeff Williford
FUGRO SOUTH, INC.
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Coppell lSD, c/o Dal- Mac Construction Co. Report Date: November 29, 1999
PROJECT: Coppell High School, Coppell, Texas Project No.: 0791-2208
SAMPLE DATE: November 18, 1999
CONTRACTOR: The Cortez Group
TICKET NO.: 6111783 CONCRETE SUPPLIER: Lattimore
AMBIENT TEMP. (°F): 82 PLANT/TRUCK: 6 / 980
CONCRETE TEMP. (°F) (ASTM C-1064): 80 MIX ID NUMBER: 38
TIME BATCHED: 11:07 AIR (%) (ASTM C-231): 5.0
TIME SAMPLED: 12:10 WATER ADDED (gal):
WEATHER CONDITION: Clear SLUMP (in.) (ASTM C-143): 3.5
LOCATION OF PLACEMENT: Parking Lot - 5 feet east off stairs on east side of Band Hall
CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12", 28.27 square inches
TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE
CYLINDER AGE DATE LOAD STRENGTH STRENGTH
NUMBER (days) TESTED (pounds) (psi) (psi)
CHC 376 7 11-25-99 90000 3180 3000/28 days
CHC 377 28 12-16-99
CHC 378 28 12-16-99
CHC 379 Hold
Fracture mode is (A) unless otherwise noted
Specifications: Making & ASTM C-31 Testing ASTM C-143, Typesof ~7~ ~-~ ~1 ~-"~
Cudng: Methods: ASTM C-39 Fracture: AI/~J ~/xJ [/~ L_JB C D
REMARKS:
Technician: Greg Forsythe FUGRO SOUTH INC.
Reviewed By:- ~'
SMH/bg
Distribution: Dal-Mac Construction - Damon Norman
City of Coppell - Larry Davis
Coppell lSD - Mickey Harper
SHW Group - Joe Craddock
SHW Group - Mike Elmore
JRJ Paving - Jeff Williford
--I:; . ~ -- ..
FUGRO SOUTH, INC. ~
2880 Virgo Lane; Dallas. Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Coppell lSD, c/o Dal - Mac Construction Co. Report Date: November 29, 1999
PROJECT: Coppell High School, Coppell, Texas Project No.: 0791-2208
I SAMPLE DATE: November 18, 1999 I
CONTRACTOR: Cortez Group
TICKET NO.: 6111767 CONCRETE SUPPLIER: Lattimore
AMBIENT TEMP. (°F): 77 PLANT/TRUCK: 6 / 976
CONCRETE TEMP. (°F) (ASTM C-10S4): 79 MIX ID NUMBER: 38
TIME BATCHED: 9:43 AIR (%) (ASTM C-231) .' 4.8
TIME SAMPLED: 10:25 WATER ADDED (gal): 40
WEATHER CONDITION: Clear SLUMP (in.) (ASTM C-143): 5.0
LOCATION OF PLACEMENT: Parking Lot - Parking Area 20 feet southeast off of southeast corner of
Band Hall
CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12", 28.27 square inches
TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE
CYLINDER AGE DATE LOAD STRENGTH STRENGTH
NUMBER (days) TESTED (pounds) (psi) (psi)
CHC 372 7 11-25-99 80000 2830 3000/28 days
CHC 373 28 12-16-99
CHC 374 28 12-16-99
CHC 375 Hold
Fracture mode is (A) unless otherwise noted
Specifica,ons: Making & ASTM C-31 Testing ASTM C-143, Typesof [~ ~] ~ ~
Cudng: Methods: ASTM C-39 Fracture: A B C D
REMARKS:
Technician: Greg Forsythe FUGRO SOUTH INC.
Reviewed By:
SMH/bg
Distribution: DaI-Mac Construction - Damon Norman
City of Coppell - Larry Davis
Coppell lSD - Mickey Harper
SHW Group - Joe Craddock
SHW Group - Mike Elmore
JRJ Paving - Jeff Williford