SC-Coppell HS-LR000623FUGRO SOUTH, INC. 2880 V*lrgo Lane; Dallas, Texas 75229 Ph (972) 484-8301; Fax (972) 620-7328 COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: PROJECT: Coppell lSD, cio Dal - Mac Construction Co. Coppell High School, Stadium Expansion Coppell, Texas Report Date: June 23 2000 Project No.: 0791-2208 SAMPLE DATE: May 25, 2000 CONTRACTOR: TICKET NO.: AMBIENT TEMP. (°F): 82 CONCRETE TEMP. (°F) (ASTM C-1064): 84 TIME BATCHED: 7:01 am TIME SAMPLED: 8:15 am WEATHER CONDITION: Sunny LOCATION OF PLACEMENT: The Cortez Group CONCRETE SUPPLIER: LMC PLANT/TRUCK: 7/1039 MIX ID NUMBER: 42 AIR (%) (ASTM C-231): WATER ADDED (gal): 5 SLUMP (in.) (ASTM C-143): 5.50 Slab for Press Box location 18-D CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12", 28.27 square inches TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE CYLINDER AGE DATE LOAD STRENGTH STRENGTH NUMBER . tdays) TESTED (pounds) (psi) (psi) CHC 1200 5 05/30/00 71300 2520 4000/28 days CHC 1201 7 06/01/00 76500 2710 CHC 1202 28 06/22/00 97400 3450* CHC 1203 28 06t22/00 101200 3580* CHC 1204 56 07/20~00 CHC 1205 Hold Fracture mode is (A) unless otherWise noted Specifications: Making & ASTM C-31Curing: Testing ASTM C-143,Methods: ASTM C-39 Typesof ~;~] ~ ~ ~Fracture: A B C D REMARKS: Technician: SMH/rm Distribution: * Does not meet required compressive strength at 28 days. Yancey Bivings FUGRO SOUTH INC. Reviewed By: ~'~ _~ DaI-Mac Construction - Damon Norman City of Coppell - Lee Stone City of Coppell - Larry Davis Coppell lSD - Mickey Harper SHW Group - Joe Craddock SHW Group - Mike Elmore JRJ Paving - Jeff Williford FUGRO SOUTH, INC. CLIENT: PROJECT: 2880 Virgo Lane; Dallas. Texas 75229 I:'h (972) 484-8301; Fax (972) 620-7328 COMPRESSIVE STRENGTH OF CONCRETE REPORT Coppell lSD, c/o Dal - Mac Construction Co. Report Date: June 23, 2000 Coppell High School, Stadium Expansion Project No.: 0791-2208 Coppell, Texas SAMPLE DATE: May 25, 2000 CONTRACTOR: TICKET NO.: AMBIENT TEMP. (°F): CONCRETE TEMP. (°F) (ASTM C.1064)-' TIME BATCHED: TIME SAMPLED: WEATHER CONDITION: LOCATION OF PLACEMENT: The Cortez Group 087441 85 81 8:42 am 9:15 am Sunny CONCRETE SUPPLIER: LMC PLANT/TRUCK: 7/938 MIX ID NUMBER: 42 AIR (%) (ASTM C-231): WATER ADDED (gal): 5 SLUMP (in.) (ASTM C-t43): 6 Slab for Press Box location 15-G CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12", 28.27 square inches TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE CYLINDER AGE DATE LOAD STRENGTH STRENGTH NUMBER (days) TESTED (pounds) (psi) (psi) CHC 1206 5 05/30t00 75900 2690 4000~28 days CHC 1207 7 06/01/00 84700 3000 .... CHC 1208 28 06/22/00 116600 4120 CHC 1209 28 06/22/00 114900 4060 CHC 1210 Hold CHC 1211 Hold Fracture mode is (A) unless otherwise noted Specifications: Making & ASTM C-31 Testing ASTM C-143, Typesof ~] [~] ~ r""] Cudng: Methods: ASTM C-39 Fracture: A B C D REMARKS: Technician: SMH/bg Distribution: Yancey Bivings FUGRO SOUTH INC. Reviewed By: ~ DaI-Mac Construction - Damon Norman City of Coppell - Lee Stone / City of Coppell Larry Davis/ Coppell lSD - Mickey Harper SHW Group - Joe Craddock SHW Group - Mike Elmore JRJ Paving - Jeff Williford FUGRO SOUTH, INC. 2880 Vlrgo Lane; Dallas, Texas 75229 PM (972) 484.8301; Fax (972) 620-7328 COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Coppell lSD, c2o Dal - Mac Construction Co. Report Date: June 23, 2000 PROJECT: Coppell High School, Stadium Expansion Project No.: 0791-2208 Coppell, Texas SAMPLE DATE: May 25, 2000 CONTRACTOR: TICKET NO.: AMBIENT TEMP. (°F): CONCRETE TEMP. (°F) (ASTM C.1064): TIME BATCHED: TIME SAMPLED: WEATHER CONDITION: LOCATION OF PLACEMENT: The Cortez Group 087447 91 83 9:49 am 10:30 am Sunny CONCRETE SUPPLIER: LMC PLANT/TRUCK: 7t959 MIX ID NUMBER: 42 AIR (%) (AS?M C-251): WATER ADDED (gal): 5 SLUMP (in.) (ASTM C.143) -' 5 Slab for Press Box location 6-F CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12", 28.27 square inches TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE CYLINDER AGE DATE LOAD STRENGTH STRENGTH NUMBER (days) TESTED (pounds) (psi) (psi) CHC 1212 5 .05/30100 81400 2880 4000/28 days CHC 1213 7 06/01/00 85600 3030 CHC 1214 28 06/22/00 115100 4070 CHC 1215 28 06/22/00 118000 4170 CHC 1216 Hold CHC 1217 Hold Fracture mode is (A) unless otherwise noted Specifications: Making & ASTM C-31 Testing ASTM C-143, Typesof ~ [~ [~ ~ Curing: Methods: ASTM C-39 Fracture: A B C D REMARKS: Technician: SMH/bg Distribution: Yancey Bivings FUGRO SOUTH INC. Reviewed By: ~ DaI-Mac Construction - Damon Norman City of Coppell - Lee Stone City of Coppell - Larry Davis Coppell lSD - Mickey Harper SHW Group - Joe Craddock SHW Group - Mike Elmore JRJ Paving - Jeff Williford