SC-Town Center E8-LR 930830 Rone F_nglneers RoneE !ineers
Geotechnical Consu,~ants
Materials Testing
!Concrete Cylinder Test Report
Projec~ IIPUrchase CXder
TOWN CENTER ELEMENTARY - COPPELL, Tw. XAS !
Number " Da4e of Observa~on IReport Dine
D3-080C-01-23650 ! JULY 30, 1993 i AUGUST 30, 1993
Fo
I COPPELL I S D.
GRADE BEAM BETWEEN PIERS 7M & 10M
iC.o~b-a~or
K. A. SPARKS CONTRACTORS, INC.
!Supp,~er iP~nt iTruck !'ricke!
! U~TT~MORE ' 6 i 409 ! 098929
!Mix Number i.M.'k Description
Weather Ccnci;bons iA,mbiem Tem.::~.ramre ¢'F),, !Concrete Tempem,~re (0~
CLEAR ~ 98 ! 94
~,me Sampled i Water Adoed
13.=20 AM ~ 3.0.0 GAf,S
Physical Data
AC ;U, ,,- SPECIFICA~ONS
SLUMP (in.) 4
Concrete Cylinder Test(s)
ACTUAL SPECIFICATIONS
Specimen Age i Tct Load I Comc~ressive S~ng~ S,-"enc3~ Required
No. (Days) Test, Date I
I I I I
3.16 7 08/06/93 85000 3010 3000
117 28 08/27/93 111000 3930
118 28 08/27/93 104000 3680
Curing Me,in. od Test MethOO iS.~.'~card S" x 12' JFEngineer/Tecnnician
. iAtea 28.27 sq. in. , GEORGE BEALL (RONE)
ASTM C 31 IASTM C 39 ~ ,.
Ren'm~s and/or Dism-ou'don :
COPPELL T.S.D./MTCKEY HARPER (1), CITY OF COPPELL/LARRY DAVIS (1),
K. A. SPARKS CONTRACTORS, INC./E. J. WI~.LIAMS (~), S.H.W.T.N.C./
MIKE E~ORE (1), S.H.W.I.N.C./JOE CRADDOCK, V.P. (~),
K. A. SPARKS CONTRACTORS, INC./E.J.WZLLIAMS (~)
Ron er.,