ED BELL CONSTRUCTION COMPANY
POST OFFICE BOX 540787 10605 HARRY HINES
DALLAS, TEXAS 75354-0787 DALLAS, TEXAS 75220
June 9,2000
Mr. Kent Collins, P.E.
Engineering and Public Works
City of Coppell
255 Parkway Blvd.
Coppell. Texas 75019-4409
Coppell Road Reconstruction
SH 121 to Sandy Lake Road
Coppell Project #: ST 98-01
Dear Mr. Collins:
Enclosed for your review and approval is a concrete batch design from Texas Industries, Inc. for
3000 psi concrete. It is our intent to utilize this concrete for miscellaneous concrete flat work
and slip tbrm concrete paving. Please inform us of your decision regarding this design.
Sincerely,
ell C nst ion Company
Robert D. Weber
Project Engineer
XC:
Mr. Kevin C. Young, E.I.T., Freese and Nichols, Inc., 1701 N. Market Street
Suite 500 LB5 l, Dallas, Texas 75202
AN EQUAL OPPORTUNITY E
1341 West Mockingbird Lane · Dallas, Texas 75247 · 972.647.6700 · www.txi.com
October 5, 1999
Ed Bell Construction Company
P.O. Box 540787
Dallas, TX 75354-0787
Attn: Rob Weber
RE: Coppell Road
8272
The attached concrete mix designs utilizing the appropriate ASTM
C-33 or ASTM C-330 aggregate are proposed for use on the above
referenced project for ready-mixed concrete to be furnished by
TXI.
To ensure that the correct mix is delivered to your project,
please order by the mix design number which appears in the upper
left hand corner of the mix design.
Texas Industries certifies that the above mix designs, when
ordered by specified design identity, and delivered by TXI, will
meet or exceed the indicated design strength at the designated
age when tested in accordance with the applicable and current
ASTM Standards C 31, C 39, C 78, C 172, C 293, applicable
provisions of C 94, and evaluated in accordance with applicable
provisions of ACI Building Code.
TXI would like to be included on your mailing list to receive all
test reports. ASTM C 94 entitles a manufacturer to receive
copies of all test reports when strength of concrete is used as a
basis for acceptance.
Please contact us if you have any questions or require any
additional information. Please notify TXI of approval of the
proposed mix designs prior to their use. Failure to notify us
prior to first placement shall constitute acceptance. To ensure
that the proper mix designs are ordered, please send a copy of
this letter, after approval, to the above referenced project to
be used by the person ordering the concrete for this job.
Sincerely,
TXI Operations, LP
Reedie Stone
Customer Service Representative
Mix #: 8272
Description: 5.00SK ADMIX/AEA I"CS
Strength: 3000 psi @ 28 Days
PAVING & HANDWORK
Maximum Coarse Aggregate: 1" - #4 CRUSHED STONE
Maximum Water/Cement Ratio: 6.20 gal/sack or 0.549 lbs/lb
Cement/Cementitious Content: 5.00 sacks (per cubic yard)
Maximum Placement Slump:' 4.00 inches
Air Entraining Agent: ASTM C-260
Admixture: ASTM C-494 Type A or D
MATERIAL QUANTITIES PER 1.0 CUBIC YARD AT S.S.D
470 lbs. ASTM C 150 TYPE I CEMENT
1840 lbs. 1" - #4 CRUSHED STONE
1352 lbs. CONCRETE SAND
258 lbs. or 31.0 Gallons of Water
2.0 to 4.0 oz/cwt of ASTM C-494 Type A
Specified Air Content: 3.0% - 6.0%
Placement Slump: 3.00 + or - 1.00 inches
PUMPING NOTES / RECOMMENDATIONS
1. 5" minimum diameter lines with no reduction to smaller
lines.
2. .Keep rubber hose to absolute minimum length and plan pipe
with as few 90 degree angles as possible.
3. Samples for slump and strength tests should be taken @
discharge end of hose for strength guarantee to be valid.
4. To prime pump lines, a minimum of 8.0 sack grout should be
used for lubrication. In the case of strength concrete,
equiyale~t strength grout should be used if the grout
remains in the placement.
5. Pump mixes are based on minimum cement content pumped at
ground level. As pump line increases in length or height
and/or layout configuration changes, additional cement may
be required to assure strength and pumpability at additional
cost to the contractor.
6. TXI cannot control, and is therefore not responsible for
excessive loss of entrained air content when loss occurs as
a result of boom configuration or free fall discharge from
hose. To ensure minimum air loss when pumping, maintain a
continuous flow of concrete through the entire length of
pipe and do not subject concrete to free fall.
7. The term "pumpable concrete" refers to concrete which is
capable of being transported through an apparatus which
forces concrete to the placing position through a pipeline
or hose as long as the recommendations indicated above are
followed. The term "pumpable concrete" does not relate to
concrete proportioned in a particular manner or containing a
specific type of product.
Unless otherwise indicated, when the concrete temperature at
point of placement exceeds 90 degrees Fahrenheit, TXI will
guarantee the strength performance of the mix design(s) herein
submitted up to a maximum placement temperature of 100 degrees
Fahrenheit using an ASTM C 494 Type D retarding water-reducer, as
long as the concrete is placed within 75 minutes from batch time.
Unless otherwise indicated, strength of plain concrete guaranteed
up to a maximum placement temperature of 85 degrees Fahrenheit.
We are enclosing all available back up data for the referenced
mix design(s). If the strength information is not available, or
is insufficient, confirmation tests may have to be conducted by
your laboratory.
Strength of lightweight mix designs valid provided strength
specimens are cured in accordance with ASTM Test Method C 567, as
referenced in section 8.1 of ASTM Specification C 330.
Date: 10/05/99
TEXAS INDUSTRIES
~g DESIGN EVALUATION
** Statistic~ Compiled From Independent Laboratory Test Specimens **
Mix Number: 8272
Strength: 3000 psi @ 28 Days
Temperature
Test Plant (Fahrenheit) Placement
Number Date Number Ambient Concrete Slump(in)
28. Day Test Data
Percent ......... 28 Day ........ Cumulative
of Air PSI 1 PSI 2 PSI Avg Average
Moving
Avg of 3 Range
1 05/05/99 82 5.QO 3.5% 3420
2 05/05/99 85 5.25 3.6% 3450
3 05/05/99 84 5.00 3.4% 3790
4 05/05/99 86 5.50 3.6% 3470
5 05/05/99 74 5.00 2.2% 3750
6 05/06/99 79 2.00 4.1% 4510
7 05/06/99 86 3.25 4.0% 4680
8 05/06/99 86 3.00 3.6% 4690
9 05/07/99 80 5.50 4.5% 3610
10 05/07/99 73 4.50 4.5% 4040
11 05/07/99 72 6.00 4.3% 3310
12 05/12/99 38 79 86 4.50 3.2% 4810
13 05/21/99 81 78 5.00 4.6% 3660
14 05/24/99 84 79 4.50 5.4% 4100
15 05/24/99 40 86 87 5.50 4.0% 4740
16 05/24/99 40 88 87 5.50 N/A 4280
17 05/24/99 40 84 86 6.00 3.8% 3980
18 05/24/99 35 58 56 5.00 4.8% .4630
19 05/24/99 35 63 58 5.50 4.7% 4930
20 05/24/99 35 60 53 5.25 5.0% 4760
21 05/24/99 35 58 56 5.00 5.01 4750
22 06/08/99 46 89 90 7.00 N/A 3880
23 06/09/99 46 93 96 5.50 N/A 4590
24 06/10/99 40 78 86 4.25 N/A 3850
25 06/14/99 SS 7.00 2.0% 4300
26 06/14/99 92 6.75 3.9% 4110
27 06/14/99 78 8.50 4.2% 4140
28 06/14/99 79 8.00 4.3% 4320
29 06/17/99 46 74 91 5.00 N/A 5780
30 06/18/99 46 85 86 3.00 N/A 5050
*** Averages *** 77 80 5.23 4.0%
3570 3495 3495 150
3560 3505 3500 110
3830 3810 3603 3603 40
3840 3655 3616 3657 370
4100 3925 3678 3797 350
4680 4595 3831 4058 170
4590 4635 3946 4385 90
4900 4795 4052 4675 210
3710 3660 4008 4363 100
3710 3875 3995 4110 330
3400 3355 3937 3630 90
5110 4960 '4022 4063 300
3830 3745 4001 4020 170
4470 4285 4021 4330 370
4560 4650 4063 4227 180
4260 4270 4076 4402 20
4020 4000 4071 4307 40
5180 4905 4118 4392 550
4360 4645 4146 4517 570
4590 4675 4172 4742 170
5380 5065 4215 4795 630
4000 3940 4202 4560 120
5150 4870 4231 4625 560
3800 3825 4214 4212 50
4380 4340 4219 4345 80
4260 4185 4218 4117 150
4000 4070 4212 4198 140
4280 4300 4216 4185 40
5560 5670 4266 4680 220
4800 4925 4288 4965 250
COMMENTARY OF STATISTICAL EVALUATION OF CONCRETE DESIGN RESULTS
Mix Num: 8272
Strength: 3000 psi @ 28 Days
Paragraph 5.5 of ACI 318-95 prQvi~es that as data becomes
available during construction, the amount by which (F'cr) must
exceed the specified value of (F'c) may be reduced, provided:
/
(a) 30 or more test results are available and average of
test results exceeds that required by Section 5.3.2.1,
using a standard deviation calculated in accordance
with Section 5.3.1.1, or
(b) 15 to 29 test results are available and average of test
results exceeds that required by Section 5.3.2.1, using
a standard deviation calculated in accordance with
Section 5.3.1.2.
The required average compressive strength has been calculated
using a standard deviation calculated xn accordance with
ACI 318-89 Section 5.3.1.1 or Section 5.3.1.2 and is the larger
value of these calculations:
F'cr = F'c
= 3000
= 3754
F'cr = F'c
= 3000
= 3811
+ 1.34(SD)
+ 1.34( 562.7)
+ 2.33(SD) - 500
+ 2.33( 562.7) - 500
SUMMARY OF STATISTICAL ANALYSIS
28 Day Test Data
Number of Tests .......................... 30
Maximum Value ............................ 5670 ps%
Minimum Value ............................ 3355 psx
Range .................................... 2315 psi
Average Strength ......................... 4288 psi
Standard Deviation ....................... 563 psi
Required Average Strength to satisfy
minimum probability conditions of
ACI 318-89 Section 5.3.2.1 ............... 3811 ps%
Design excess beyond code requirements... 477 psi
MIDLOTHIAN CEMENT PLANT · 245 Ward Road · Midlothian. Texas 76065 · w'.'r,'l, txi.corn
SPECIFICATIONS
Portland Cement
Type 1/11 (Low Alkali)
A.S.T.M. C150-97
Bin Number -
'Car Number'
Tons
Date of Sampling
;
lJuly 1999 Monthly Average
ASTM
SPECIFICATION
CHEMICAL REQUIREMENTS
·
Silica Oxide, Minimum Percent 20.0
Alumina Oxide, Maximum Percent 6.0
'Iron Oxide, Maximum Percent I 6.0
Magnesia Oxide, Maximum Percent I 6.0
SOs (CaA less than 8%). Maximum Percent
'Loss on Ignition, Maximum Percent I 3.0
'Insoluble Residue. Maximum Percent. I 0.75
'Tricalcium Atuminate, Maximum Percent ~ 8.0
OPTIONAL CHEMICAL REQUIREMENTS
Total Alkalies, Max. % (NazO equiv.} ~ 0.60
PHYSICAL RSQUIREMENTS
Specific surface, Blaine Minimum (m2/kg) I 280
Giltmore, Initial Set, Minimum (Minutes) I 60
Gillmore, Initial Set, blaximum (Minutes} I 600
Vicar, t Minimum (Minutes) t 45
Initial Set Maximum (Minutes) 375
Air Content, Volume, Maximum Percent 12
Autoclave Expansion, Maximum Percent 0.80
'3 Day Minimum Compressire S~.rength, MPa (psi) 12.0 (1740)
7 Day Minimum Compressive Strength, MPa (psi) I 19.0 (2760)
STATE OF TEXAS
TEST
RESULTS
20.6
4.2
3.8
1.2
3.3
0.9
0.16
5.0
0.41
345
159
282
94
5
0.01
21.4 (3097)
29.9 (4338)
ELLIS COUNTY
J.R. Wendel , being duly sworn deposes and says: that he is Quality Sen/ices
Manager of TXI Mid:o~hian Cement Plant, who prepared the above report, of tests
and that the same is true and correct.
Subscribed nd sworn to before me this 11 th day o1' August, 1999.
Nota~ Public QuaK__----d'Services Mana,.:er
· See ASTM C150 Table 1. Foolnote B.
li) K.C. COKER
5:.-',T5 OF TF_X.~Z,;'
i"' ]"'
Concrete Products
W.R. Grace & Co.
200t East Randol Mill, Suite e t t5
Adington, TX 760t I
January 8,1998 .."'
[8¢7] 46t-4t0t
[8t7] 459-t084
Texas Industries, Inc.
Dallas, Texas'
Gentlemen:
This is to certify that DARATARD-17, a water-reducing set-retarding
admixture, supplied by the Construction Products Division, W.R. Grace &
Co.-Conn., is formulated to comply with Specifications for Chemical
Admixtures for Concrete, ASTM Designation: C--494, as a Type B & D
admixture; and the Standard Spedfications of the Texas Highway
Department.
No chlorides or halogens are added to DARATARD-17 as functional
ingredients during manufacture.
Material supplied for the above referenced project is identical in all respects,
including concentration;-to'the one originally' submitted to and 'approved by-'
the State of Texas, Dept. of Transportation.
The above is in addition to and not in substitution for our standard Conditions
of Sale printed on the reverse side hereof.
Sincerely,
Tom C. Henson
District Manager
Subscribed and sworn to, before me,
this 8th day of January, 1998 A.D.
Lorene B..Raso, Notary Public_
In and For the State of Te~xas
We hope the infc~mation given here will ioe helpful. It =s IDczsec on our IDest knowledge. oncl we believe it to be true and accurate. Rease read all statements.
recommendations at suggestions herein in contucticn ~,rth Our ~dions of sale which c}p~y h3 all goods supplied by us. We assume no responslbilllV fat' the use
of these statements. recommend<3lions. or sugges,~3r'.s. ncr Cc ,'9 inlend them as a reccx'nrnendafion for any use which woulcj infringe any Izx3tenl cy copyright.
December 16, 1998
Grace Construction Products
W.R. Grace & Co. - Corm
4323 Crires Street
P.O. Box 2585.77252
Houston. TX 77003
Texas. Industries, Inc.
1341 West Mockingbird Lane
Dallas, TeXas 75247
Gentlemen:
This is to certify that WRDA with HYCOL, a water-reducing admixture, as
manufactured and supplied by the Construction Products Division, W.R.
Grace & Co.-Conn.. is formulated to comply with Specifications for Chemical
Admixtures for Concrete,-. ASTM Designation: C--494, Type A (AASHTO
M194, Type A).
WRDA with HYCOL does not contain calcium chloride or chloride containing
compounds as a functional ingredient. Chloride ions may be present in trace
amounts contributed from the domestic water supply used during the
manufacturing process.
The above is in addition to and not in substitution for our standard Conditions
of Sale printed on the reverse side hereof.
//~ncerely~ ~
Tom C. Henson
District Manager
Subscribed and sworn to, before me,
this 16th day of December, 1998 A.D
L~so,'~~~')~~~
in and For the State of Texas
~,Ve hope Ihe ;nEartact,an given here will be help[ul. Ir is ba'.e~ on cur besz ~.nawle~ge. anc~ w~ before il to be true and accurate· P~e:se fec~ all ~aeemeNs..
- ~ecommenSc ,ons at :u~gestlons he~e,n In coniuncficn wilh our cc~d::,ons a~ ~fe which apply ~o all goads sup=l;e~ by 3~ V/e cssu-e no resp~ns~b,l;~/[cr the use
oF ~ese s:]:em~n~s :~ :;mmendcr:3ns or ~u~.]es:.cns nor ~o we :nmend lhem cs recommendclion ~or any u:e wh,ch would in[nnge cny pcrenl ol copyrighl.
-~ '- 'I' ~!: I' '! ' ~ T
January 8, 1998
Concrete Products
W.R. Grace & Co.
200t East Randol Mill, Suite · I `15
klington, TX 760'1 `1
(8t7] 46t-4t0t
(8 t 7] 459-t084
Texas Industries, Inc.
Dallas: Texas
Gentlemen:
This is to certify that DARACEM-19, a high range water-reducing admixture,
as manufactured and supplied by the Construction Products Division, W. R.
Grace & Co.-Conn.. is formulated to comply with Specifications for Chemical'
Admixtures for Concrete. ASTM Designation: C--494, Types A & F (AASHTO
M 194, Types A & F).
DARACEM-19 does not contain calcium chloride or chloride containing
compounds as a functional ingredient. Chloride ions may be present in trace
amounts contributed from the domestic water supply used during the
manufacturing process.
The above is in addition to and not in substitution for our Standard Conditions
of Sale pdnted on the reverse side hereof·
Sincerely, '-"
Tom C. Henson
District Manager
Subscribed and swam t~o, before me,
this 8th day of January, 1998 A.D.
, LORENE B. PASO
· r.
Notary Public. State ef Texas
~y C~mm[ssien Expires 03-28-IG9~
Lorene B. Raso,
In and For the State of Texas
We hol::~ Ihe infcxmation given here well N helpful. It is t:x3secl on our best knowledge. and we believe I! to ~ true and accurate. Please read all s~atements.
rec. o'nrne,ndations cf suggestions herein In c~j~ti~ ~th ~r c~tions of sale ~ich a~y ro au ~ su~i~ ~ us. we a~ume ~ res~nsl~li~ f~ ~ use
~ t~se state~nls. r~cmmen~ti~s. or su~Hons. nor ~ we inte~ them as a r~ation for any use which would ~nfringe any Cctenl ar ccCydghr.
a ~ T !
Date:
Size:
Project:
SIEVE
SIZE
2.0"
1.0"
3/8"
#8
#10
#16
#30
#-40
#50
#100
#200
PAN WT.
~.C.
DECANT
S.~.
~00% of
04/28/99
33
.... *ALL TESTS .....
C U M U LATIVE
WT. RETAINED
5.3%
91.2%
tests: 93
TEXAS INDUSTRIES
QUALITY CONTROL DEPT.
AGGREGATE SIEVE ANALYSIS
Production" Facility:
Grading Designation:
Sample Location:
CUMULATIVE CUMULATIVE
% RETAINED % PASSING
PARADISE
ASTM C-33
REQUIRED
% RETAINED
.81 99.19 0-5
19.02 80.98 0-20
FINE AGG.
SPECIFICATION
% PASSING
35.23
51.87
I
72.74
96.05
98.88
2.76
95-100
80-100
Size: 33 PLANT: PARADISE
64.77 15 - 50 50 - 85
48.13 40 - 75 25 - 60
27.26 70-90
3.95 90-98
1.12
FINENESS MODULUS
10-30
2-10
Job: ....... ALL JOBS .......
Date:
Size:
Project:
SIEVE
SIZE
%-
3/8 '
#10
#16
#30
#~40
#50
#100
#200
PAN WT.
Decant
100% of
07/17/99
TEXAS INDUSTRIES
QUALITY CONTROL DEPT.
AGGREGATE SIEVE ANALYSIS
Production'Facility:
57
Grading Designation:
..... ALL TESTS ..... ,, Sample Location:
CUMULATIVE
WT. RETAINED
CUMULATIVE
% RETAINED
CUMULATIVE
% PASSING
TXI - BRIDGEPORT. TEXAS
ASTM C-33 1 ' - #4.
REQUIRED
% RETAINED
.89%
tests: 151 'Size: 57
SPECIFICATION
% PASSING
0 100 0 100
1.72 98.28 0 - 5 95 - 100
17.46 82.54
55.43 44.57 40 - 75 25 - 60
79.30 20.70
97.20 2.80 90 - 100 0 - 10
98.83 1.17 95 - 100 0 - 5
99,13 ~ 0.87
PLANT: BRIDGEPORT
Job: ....... ALL JOBS