St Ann Catholic-LR001129CONCRETE COMPK_.,SSIVE STRENGTH TE , F
a division
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
Date of Service: 10/27/2000 Report No.: 0028095 Report Date
11/29/2000
Client No.: 2310 Project No.: 94001152
Client: St. Ann's Catholic Community Project: St. Ann's Catholic Church
Attn: Monsignor Kilian Broderick 180 Samuel Boulevard
180 Samuel Boulevard
Coppell TX 75019 Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required field test and cast
compressive strength samples.
PROJECT DATA
CONTRACTOR: Centex Construction MIX i.D.: N/A
CONCRETE SUPPLIER: TXI PLACEMENT DATE: 10/27/2000 BATCH TI3IE: 11:00am
PLANT: 38 TIME SAMPLED: 11:50am BY: Shane Spinks
SPECIFICATION REQUIREMENTS WEATHER CONDITIONS: Partly cloudy, warm
STRENGTH: 3000 psi @ 28 Days TEMPERATURE (F) - AIR N/A F CONCRETE: N/A r
SLUMe: 3-5" TRUCK NO: N/A TICKET NO: N/A
AIR: N/A AIR CONTENT (%): 1.8 UNIT WEIGIIT (pcf): N/A
TEST METHOD: ASTM C- 143 PLACEMENT LOCATION:
Pier information and technician time: See Report #0028094
ASTM C-172
ASTM C-39
SAMPLE LOCATION: B-2, C-2, D-2
REPORT OF TESTS ACCUMULATIVE YARDS: 10
CYLINDER MEASURED MAXI3'IU~! COMPRESSIVE
MARKED SLU3'IP DATE AGE LOAD STRENGTH FP,~.*,CTURE
SET NO. (inches) TESTED (days) (lbs. force) (psi) TYPE
1 1 5.25 11/03/2000 7 112570 3980
1 2 5.25 11/03/2000 7 120250 4250
Average 4120
1 3 5.25 11/24/2000 28 158250 5600
1 4 5.25 11/24/2000 28 158260 5600
Average 5600
Technician: Shane Spinks Started: Finished:
Report Distribution: leering, Inc.
(I) St. Ann's Catholic Community ( I ) Datum Engineering, Inc.
(1 } Centex Construction (I) City of Coppell leveland, P.E.
(I) City of Coppell Senior Project Engineer
( I ) Alliance Architects
This report is exclusively for the use of the client indicated above and shall not bc reproduced except in full without the written approval of HBC Engineering, Inc.
0ILL Page I of 1