St Ann Catholic-LR000914CONCRETE COMPRLoSIVE STRENGTH TEE
09-20-00A09:45 RCVD adivisionofl~rl-~l=on
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
Date of Service: 09/01/2000 Report No.: 0023000 Report Date
09/14/2000
Client No.: 2310 Project No.: 94001152
Client: St. Ann's Catholic Community Project: St. Ann's Catholic Church
Attn: Monsignor Kilian Broderick 180 Samuel Boulevard
180 Samuel Boulevard
Coppell TX 75019 Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required field test and cast
compressive strength samples.
PROJECT DATA
CONTRACTOR: Centex Construction MIX I.D.: N/A
CONCRETE SUPPLIER: TXI PLACEMENT DATE: 09/01/2000 BATC}~ TIME: N/A
PLANT: 38 TI3,1ESAMPLED: 2:00pm BY: Shane Spinks
SPECIFICATION REQUIREMENTS WEATHER CONDITIONS: Sunny, warm
STRENC, Tm 3000 psi @ 28 Days TEMPE~O, TUP~
SLUMP: 3-5" TRUCK NO: N/A TICKET NO: N/A
AIR: N/A .AIR CONTERT (~): 1.2 UNIT WEIGHT (pcf): N/A
TESI METIiOD: ASTM C- 143 PLACEMENT LOCATION:
Pier information and technician time: See Report #0022999
ASTM C-172
ASTM C-39
SAMPLE LOCATION: B-I.5. D-I.5. E-I.5
REPORT OF TESTS ACCUMULATIVE YARDS: l0
CYLINDER MEASURED MAXIMLIM COMPRESSIVE
MARKED SLU%'IP DATE AGE LOAD STRENGTH FRACTURE
SET NO. (inches) TESTED (days) (lbs. force) (psi) TYPE
I 1 6.25 09/08/2000 7 95250 3370
I 2 6.25 09/08/2000 7 91980 3250
Average 3310
I 3 6.25 09/29/2000 28
I 4 6.25 09/29/2000 28
Technician: Shane Spinks Started: Finished: ~r
Report Distribution: ' ing, Inc.
(1) St. Ann's Catholic Community (1) Datum Engineering. Inc.
(1) Centex Construction (1) Ci~' of Coppell Eric J. Cleveland, P.E.
(1) City of Coppell Senior Project Engineer
( 1 ) Alliance Architects
This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, Inc.
0ILL Page I of 1