Taco Bell-CS 950323DRC DATE:
CONTACT:
COMMENT STATUS:
DEVELOPMENT REVIEW COMMI EE
ENGINEERING COMMENTS
S-1095, Taco Bel~ zoning change from C (Commercial) to C-S.U.P.
(Commercial, Special Use Permit), to allow a drive4kmugk restaurant
located on the west side of Denton Tap Road, approximately 145' north
of Sandy Lake Rd., at the re, est of Huitt-Zollars, Inc.
March 23, 1995 & March 30, 1995
Ken Griffin, P.E., Assistant City Manager/~ Engineer (304-3679)
INI~?AL ~PRELIMINARY ~
Zoning Exhibit:
No Commems
Site
1.
Plan Comments:
The plan shows a 5 foot proposed right-of-way dedication, however, that is inadequate to
contain the deceleration lane and required sidewalks. Therefore, additional right-of-way
should be dedicated.
Site plan shows a proposed future driveway. That driveway should be constructed now to
allow two points of ingress and egress to the site. Therefore, off-site easements will be
required.
Your curb return radiis should be reevaluated.
the south side of the site as opposed to 15 foot.
on the south side of the site should be shown.
The minimum radius should be 20 foot on
Also, the radius for the existing driveway
The water line should be extended as an 8" water line not a 6" water line. You should loop
the 8" water line into the existing water line south of the site.
You are showing a stacking distance for over 10 vehicles for your drive through. Have you
considered some type of by-pass lane to allow vehicles to leave the drive through lane if
necessary instead of being trapped in the lane?
6. The dimensions of the proposed deceleration lane should be shown.