Town Center L1B3-LR 980824 Information
.To Build On
REPORT OF CONCRETE COMPRESSION TEST
TESTED FOR: MIKE MORGAN PROJECT: COPPELL TOWN CENTER
LEE LEWIS CONSTRUCTION COPPEL, TX
16660 NORTH DALLAS PARKWAY
DALLAS, TX 75248
REVISION #1
DATE: August 24, 1998 OUR REPORT NO.: 341-80053-21
........ .. 3%----~ ....... ' ........................ - .. ' .... . ~ .............. ~'-'~: .... _--- .....~7 ..................
FIELD DATA:
LOCATION OF PLACEMENT GRADE BEAMS
GP~DE BEAMS 1.0 AND 7.0
DATE PLACED August 17, 1998 SUPPLIER REDI-MIX
TIME 02:00 pm DELIVERY TICKET NO./TRUCK NO. 51135
SLUMP, IN. 4 1/2 MIX NUMBER AND PROPORTIONS 718
AIR CONTENT, % - - - CEMENT 4.5
AIR TEMPERATURE, °F 9 8 WATER
CONCRETE TEMPERATURE. °F 9 1 FINE AGGREGATE
DATE RECEIVED IN LAB August 18, 1998 COARSE AGGREGATE - - -
FIELD DATA SUBMITI'ED BY" PSI \JERRY RENFRO ADMIXTURE
MIX DATA SUBMI'I-FED BY REDI -MIX
COMPRESSION TEST RESULTS
ASTM C39-94
{ SPECIMEN TEST TOTAL CYLINDER CYLINDER COMPRESSIVE i
LABORATORY i IDENTIFICATION AGE DATE OF LOAD DIAMETER AREA STRENGTH
NUMBER · OR SETNO. (DAYS) TEST (LBS.) (IN.) (SQ. IN.) (PSI) TYPE OF BREAK
368 A 7 08/24/98 75000 5.98 28.09 2670 i Cone
368 B 28 09/14/98 95000 6.00 28.27 3360 Cone
368 C 28 09/14/98 93000 6.00 28.27 3290 Cone
368 D H HOLD
SPECIFICATIONS
28 3000
Cylinders picked up by PSI TSSI results comply with applicable
REMARKS: X_ Cylinders made by PSI representative. _.,,~.__ represmllative, specifications.
Cylinders made by Architect's or Test results do not comply wilh
Contractm'$ representative. Cylinders delivered to PSI laboratory, applicable specifications
TECHNICIAN: JERRY RENFRO Respectfully submitted,
Professional Service Industries, Inc.
THESE TEST RESULTS APPt. Y ONLY TO THE SPECIFIC SAMPLES TESTED AND MAY NOT BE INDICATI~/E OF THE ENTIRE CONCRETE Pt.ACEMENT.
REPORTS MAY NOT BE REPRODUCED. EXCEPT IN FULL, W1THOCIT %%i~ITTEN PERMISSION BY PROFESSIONAL SERVICE INDUSTRIES. INC.
Ps, ^.=oo-4 (4)F Professional Service Industries, Inc. · 4087 Shilling Way · Dallas, TX 75237 · Phone 214/330-9211 · Fax 214/263-2612
Information
I. To Build On
REPORT OF coNCRETE COMPRESSION TEST
TESTED FOR: MIKE MORGAN PROJECT: COPPELL TOWN CENTER
LEE LEWIS CONSTRUCTION COPPEL, TX
16660 NORTH DALLAS PARKWAY
DALLAS, TX 75248
DATE: August 24, 1998 OURREPORTNO.: 341-80053-21
FIELD DATA:
LOCATION OF PLACEMENT GRADE BEAMS
GRADE BEAMS 1.0 AND 7.0
DATE PLACED August 17, 1998 SUPPLIER REDI-MIX
TIME 02: 00 pm DELIVERYTICKETNO./TRUCKNO. 51135
SLUMP, IN. 4 1/2 MIX NUMBER AND PROPORTIONS 718
AIR CONTENT, % CEMENT 4.5
AIR TEMPERATURE, °F 9 8 WATER - - -
CONCRETE TEMPERATURE, °F 91 FINE AGGREGATE - - -
DATE RECEIVED IN LAB August 18, 1998 COARSE AGGREGATE - - -
FIELD DATA SUBMll-rED BY PS I \JERRY RENFRO ADMIXTURE - - -
MIX DATA SUBMII'rED BY REDI -MIX
_NOTE: AP~.I.J~BLE ASTM ~,~.D~.UNLF S~ OTH _E __~ INDI~F-D: eL [.1~: C14S-I)0s: AIR CONTENT: C231-91 b: TEMPERATURE: C10~4-Mt93k CAP. JP!NG.' ~4L231 - 9_3 ...........
COMPRESSION TEST RESULTS
ASTM C39-94
' LABORATORY ~ IDENTIFICATION~ AGE ' DATE OF LOAD ..... DIAMETER AREA STRENGTH
_ NUMBER OR SET NO. (DAYS); TEST (LBS.) (IN.) (SQ. IN.) (PSI) TYPE OF BREAK
- 368 : A 7 08/24/98 75000 i 5.98 28.09 2670 Cone
368 28 09/ .4/98
368 C 28 09/14/98
368 I D }{ HOLD
SPECIFICATIONS
28 3000
Cylinders picked up by PSI Test results comply wilh applicable
Cylinders made by Archilect's or Test results do not comply with
-- C~'¢rectofe rep~serttetive. Cylinders delivered fo PSI lebo~tor),. _. __ apfllicable specifications.
TECHNICIAN: JERRY RENFRO Respectfully submitted,
Professional Service Industries, Inc.
THESE TEST RES%q. TS ~=Pt.Y ONLY TO THE SPECIFIC SANIPI.E$ TF-~TED AND MAY NOT ~E INOICATI%'E GF THE ENTIRE CONC.~ETE PLACEMENT.
REPORT8 MAY NOT BE REPROOIJCED, EXCEPT IN FULL WITHOUT WRITTEN PERMIBEION BY PROFE$81ONAL SERVICE INO[~TR ES, INC.
PSI A.200-4 (4)F
Professional Service Industries, Inc. · 4087 Shilling Way · Dallas, TX 75237 · Phone 214/330-9211 · Fax 214/263-2612