Town Center L1B2-LR 980604GEOTECHNICAL ENGINEERING
GEE Consultants, Inc.
CONSTRUCTION MATERIALS TESTING
10046 Monroe Drive
· Dallas, Texas 75229 · (214) 352-5433 · Fax (214) 352-6972
REINFORCING STEEL PLACEMENT
Report Date:
Client:
Project
Identification
Method of Teat
June 4, 1998
Ewing Properties
Town Center Shopping - Coppell, Tx.
Reinforcing Steel Inspection
Visual Inspection
Test Date: June 2, 1998
General Report No.: 7
Project No.: 298-0165
Page 1 of 1
Results
On June 2, 1998, reinforcing steel was inspected at the following locations:
Panel #'s: 2, 4, 5, 6, 7, 8, 9, 10, 12, 14, 15, 18, 20, 22, 23, 25 & 26
The following discrepancies were noted and called to the attention of Paul Johnson, a representative of Royal
General Contractors and Joe Rodriguez of TriCity:
1. Diagonal, horizontal & vertical #5's around scuppers, doors & openings missing.
2. Perimeter #5's missing at some locations.
The above discrepancies were being corrected when technician left site. Final check will be made prior to
concreting.
Tech: RG
cc:
Mr. John Maggiore - Ewing Properties
Mr. Hank Quigg - Richmond Group
Mr. Steve Dial - Hunt Joiner Engineering
Mr. Eric Royal - Royal General Contractors (2)
Mr. Larry Davis - City of Coppell (2)
· GEOTECHNICAL ENGINEERING
El. GEE Consultants, Inc.
10046 Monroe Drive
· Dallas, Texas 75229 · (214) 352-5433 · Fax (214) 352-6972
REPORT OF IN-PLACE DENSITY AND MOISTURE OF SOIL
Density Report No. 17 (298-0165) Method: ASTM D2922 D3017 D698 Page of 1
Client: Ewing Properties Material Description Maximum Optimum
Dry Moisture
Density Contem
Project: Town Center Shopping-Coppell (Lbs/CuFt) Percent
1. Olive Gray Clay 103.2 17.6
2. Reddish Brown Sandy Clay 99.6 18.4
Test Date: June 2, 1998 3. Brown & Yellowish Brown Silty Clay 98.2 17.8
4. Yellowish Brown Clayey Sand (select lrdl) 115.0 11.5
Report Date: June 4, 1998
Required Density (%): Min. 95%
Required Moisture (%): Opt -I-5%/-t-3%
Mat Location/Elevation ~and/or) Lift In-Place In-Place Percent
No. Dry Density Moistur~ Compaction
Test (Lbs/CuFO Contem (%)
No.
Probe
Depth
2 Retest #26
47 103.6 10.5 * 104.0
8"
* Test does not meet project specifications
cc: Mr. John Maggiore - Ewing Properties
Mr. Hank Quigg - Richmond Group
Mr. Steve Dial - Hunt & Joiner Engineering
Mr. Eric Royal - Royal General Contractors (2)
Mr. Larry Davis - City of Coppell (2)