ST9601-SP 990315 (2)J - M PIPE Blue Brute "Factory Installed
Rings
Class 100, 150 and 200
Ring-Tite PVC Meets
water pipe AWWA C900
Short form
specification
Scope Pipe stiffness
This specification designates general The pipe stiffness using F/Ay for PVC
requirements for unplasticized polyvinyl class water pipe is contained in the table
chloride (PVC) plastic class water pipe below:
with integral bell and spigot joints for Class DR F/Ay (psi)
the conveyance of water and other fluids. 1 O0 25 129
150 18 364
Materials 200 14 815
Pipe shall meet the requirements of
AWWA C900, "Polyvinyl Chloride (PVC) Quick burst test
Pressure Pipe". All Class 100 pipe shall Randomly selected samples tested in
meet the requirements of DR 25, Class accordance with ASTM D 1599 shall
150 pipe shall meet the requirements of withstand, without failure, pressures
DR 18 and Class 200 the requirements listed below when applied in 60-70
of DR 14. seconds.
Minimum burst
Pipe Class pressure at 73°F (psi)
All pipe shall be suitable for use as
pressure conduit. Provisions must be 1 O0 535
made for expansion and contraction at 150 755
each joint with an elastomeric ring. 200 985
Accessories The bell shall consist of an integral wall
Blue Brute is backed up by all the items it section with a factory installed, solid Drop impact test
takes for smooth installation of water cross section elastomeric ring which Pipe shall withstand, without failure at
pipe. Direct taps can be made with proper meets the requirements of ASTM F-477. 73°F, an impact of a falling missile, Tup
tapping tools. (See detailed instructions The bell section shall be designed to C, at the following levels. (Per ASTM D
on tapping in the "Blue Brute Installation be at least as hydrostatically strong as 2444).
Guide", TR-704B.) the pipe wall and meet the requirements Pipe Impact
of AWWA C900. Sizes and dimensions size (in.) (ft./Ibs.)
shall be as shown in this specification. 4 1 O0
6 100
Hydro Testing 6 100
Each pipe shall be tested to four times
10 120
the pressure class of the pipe for a 12 120
minimum of 5 seconds. The integral
bell shall be tested with the pipe.
There shall be no visible evidence of
Standard Laying Lengths shattering or splitting when the energy is
Standard laying lengths shall be imposed.
20 feet (- 1 ") for all sizes.
Cast iron O.D.
Available in 4", 6", 8", 10" and 12" sizes,
this pipe can be connected directly into
cast and ductile iron fittings without
adaptors or complicated procedures.
5
Dimensions (average)
Class 100 (DR 25)*
Pipe Outside Nom. inside T (min.) E Approx. Wt.
size (in.) dia. (in.) dia. (in.)** thick. (in.) dim. (in.) D9 Ibs./ft.
4 4.80 4.39 .192 4.75 6.4 1.9
6 6.90 6.30 .276 5.50 8.8 3.9
8 9.05 8,28 .362 6.25 11,4 6.7
10 11.10 10.16 .444 7.00 13.8 10.1
12 ' 13.20 12.08 .528 7.80 15.9 14.4
Class 150 (DR 18)*
4 4,80 4.23 .267 4.75 6.5 2.6
6 6.90 6.09 .383 5.50 9.0 5.3
8 9.05 7.98 .503 6.25 11.6 9.2
10 11.10 9.79 , .617 7.00 14.1 13.9 '
12 13.20 11.65 .733 7.80 16.7 19.7
Class 200 (DR 14)*
4 4.80 4.07 .343 4.75 6.8 3.2
6 6.90 5.86 .493 5.50 9.4 6.7
8 ~ 9.05 7.68 .646 6.25 12.1 11.6
10 11.10 9.42 .793 7.00 14.3 17.6 ~'~
12 ' 13.20 11,20 .943 7.80 16.9 25.1
*DR (Dimension Ratio) is the outside diameter divided by the minimum wall thickness T (rain.).
**Nominal inside diameter equals the outside diameter minus twice thickness T (nora.).