Freeport NIP(2.2)-LR011016CONCRETE COMPRESSIVE STRENGTH TEST .H.,~ ENGIN EEE.ING, INC. 8901 Carpenter Frwy., Suite #100 Report Number: 94011204.0044 Dallas, Texas 75247 Service Date: October 8, 2001 (214) 63O-lOlO Client: TNA North American, Inc. Report Date: October 16, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 4:22am Date Cast: October 8, 2001 Technician: Marlo Villanueva Batch Time: 3:48am Plant: 31 Weather Conditions: Clear Supplier: TXI Accumulative Yards: 20 Truck No: 139 ~r'icket No: 2995596 Placement Method: Mix I.D. No.: 9505 V J~ Sample Locations: Grid line 6.5/B Placement Location: Floor slab-on-grade on lines 1-6/A-D, 6-7/A-B Field Test Data Test Result Specification Test Method Slump, inches: 5.25 3-5 ASTM C-143 Air Content, %: Concrete Temperature, o F: 68 ASTM C1064 Ambient Temperature, o F: 54 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 10/15/2001 7 104,450 3,690 1 2 6.00 28.27 10/15/2001 7 100,850 3,570 Average 3,630 I 3 11/05/2001 28 1 4 11/05/2001 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 7 0~.~,~,~,-F,,,,.~ Key CONCRETE COMPRESSIVE STRENGTH TEST 8g01 Carpenter Frwy., Suite #100 Report Number: 94011204.0044 Dallas, Texas 75247 Service Date: October 8, 2001 (214) 63O-lOlO Client: TNA North American, Inc. Report Date: October 16, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 5:22am Date Cast: October 8, 2001 Technician: Marlo Villanueva Batch Time: 4:51 am Plant: 31 Weather Conditions: Clear Supplier: TXI Accumulative Yards: 110 Truck No: 722 Ticket No: 2995627 Placement Method: Mix I.D. No.: 9505 Sample Locations: Grid line 5/D Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.00 3-5 ASTM C-143 Air Content, %: Concrete Temperature, o F: 69 ASTM C1064 Ambient Temperature, o F: 56 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 2 1 6.00 28.27 10/15/2001 7 98,890 3,500 2 2 6.00 28.27 10/15/2001 7 100,380 3,550 Average 3,530 2 3 11/05/2001 28 2 4 11/05/2001 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 7 o, .~,~,..o, CONCRETE COMPRESSIVE STRENGTH TEST 8901 Carpenter Frwy., Suite #100 Report Number: 94011204.0044 Dallas, Texas 75247 Service Date: October 8, 2001 (214) 63O-lOlO Client: TNA North American, Inc. Report Date: October 16, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 6:55am Date Cast: October 8, 2001 Technician: Marlo Villanueva Batch Time: 6:05am Plant: 31 Weather Conditions: Clear Supplier: TXI Accumulative Yards: 220 Truck No: 101 Ticket No: 2995685 Placement Method: Mix I.D. No.: 9505 Sample Locations: Grid line 4/A Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.25 3-5 ASTM C-143 Air Content, %: Concrete Temperature, o F: 67 ASTM C1064 Ambient Temperature, o F: 55 ASTM C-1064 Plastic Unit Weight, pcf: Laboratorlf Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 3 1 6.00 28.27 10/15/2001 7 97,440 3,450 3 2 6.00 28.27 10/15/2001 7 98,010 3,470 Average 3,460 3 3 11/05/2001 28 3 4 11/05/2001 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 7 o~ ~ CONCRETE COMPRESSIVE STRENGTH TEST ~"'i'~ ? ENGINEERING, Report Number: 94011204.0044 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Service Date: October 8, 2001 (214) 63O-lOlO Client: TNA North American, Inc. Report Date: October 16, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 8:00am Date Cast: October 8, 2001 Technician: Mario Villanueva Batch Time: 7:16am Plant: 31 Weather Conditions: Cloudy Supplier: TXI Accumulative Yards: 310 Truck No: 081 Ticket No: 2995798 Placement Method: Mix I.D. No.: 9505 Sample Locations: Grid line 3/D Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.00 3-5 ASTM C-143 Air Content, %: Concrete Temperature, o F: 67 ASTM C1064 Ambient Temperature, o F: 54 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 4 1 6.00 28.27 10/15/2001 7 81,060 2,870 4 2 6.00 28.27 10/15/2001 7 85,420 3,020 Average 2,950 4 3 11/05/2001 28 4 4 11/05/2001 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 7 o, ~,~o, CONCRETE COMPRESSIVE STRENGTH TEST ~--i~"~'~'~''"~" ENGI N EEAIN~, I'h~. 8901 Carpenter Frwy., Suite #100 Report Number: 94011204.0044 Dallas, Texas 75247 Service Date: October 8, 2001 (214) 63O-lOlO Client: TNA North American, Inc. Report Date: October 16, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 9:50am Date Cast: October 8, 2001 Technician: Marlo Villanueva Batch Time: 9:00am Plant: 31 Weather Conditions: Cloudy Supplier: TXI Accumulative Yards: 410 Truck No: 179 Ticket No: 2995996 Placement Method: Mix I.D. No.: 9505 Sample Locations: Grid line 2/B Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.25 3-5 ASTM C-143 Air Content, %: Concrete Temperature, o F: 70 ASTM C1064 Ambient Temperature, o F: 56 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 5 1 6.00 28.27 10/15/2001 7 81,140 2,870 5 2 6.00 28.27 10/15/2001 7 82,800 2,930 Average 2,900 5 3 11/05/2001 28 5 4 11/05/2001 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 5 of 7 o,.~,.o~.F~.~ Key CONCRETE COMPRESSIVE STRENGTH TEST 8901 Carpenter Frwy., Suite #100 Report Number: 94011204.0044 Dallas, Texas 75247 Service Date: October 8, 2001 (214) 63O-lOlO Client: TNA North American, Inc. Report Date: October 16, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 11:00am Date Cast: October 8, 2001 Technician: Marlo Villanueva Batch Time: 10:17am Plant: 31 Weather Conditions: Cloudy Supplier: TXI Accumulative Yards: 500 Truck No: 103 Ticket No: 2996187 Placement Method: Mix I.D. No.: 9505 Sample Locations: Grid line 1/A Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.00 3-5 ASTM C-143 Air Content, %: Concrete Temperature, o F: 69 ASTM C1064 Ambient Temperature, o F: 57 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 6 1 6.00 28.27 10/15/2001 7 100,040 3,540 6 2 6.00 28.27 10/15/2001 7 99,080 3,500 Average 3,520 6 3 11/05/2001 28 6 4 11/05/2001 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 6 of 7 o, ~.,~,,~, F~..,<.y CONCRETE COMPRESSIVE STRENGTH TEST ENG~N EER/NG, INC. 8901 Carpenter Frwy., Suite #100 Report Number: 94011204.0044 Dallas, Texas 75247 Service Date: October 8, 2001 (214) 63O-lOlO Client: TNA North American, Inc. Report Date: October 16, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 1:18pm Date Cast: October 8, 2001 Technician: Marlo Villanueva Batch Time: 12:33pm Plant: 31 Weather Conditions: Cloudy Supplier: TXI Accumulative Yards: 630 Truck No: 663 Ticket No: 2996407 Placement Method: Mix I.D. No.: 9505 Sample Locations: Grid line 1/D Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.25 3-5 ASTM C-143 Air Content, %: Concrete Temperature, o F: 71 ASTM C1064 Ambient Temperature, o F: 58 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 7 I 6.00 28.27 10/15/2001 7 76,670 2,710 7 2 6.00 28.27 10/15/2001 7 78,120 2,760 Average 2,740 7 3 11/05/2001 28 7 4 11/05/2001 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Mario Villanueva Report Distribution: /,~/ering, Inc. (1) TNA North American, Inc. (1) FACServices Inc (1) Carrell Poole & Yost Architecture (1) David Kent Reviewed by: (1) R L Goodson Consulting Engineers (1) City of Coppell- Bldg Insp (,-.,'/ ~'~ric J. Cleveland, P.E. (1) Pacific Builders Inc (1) City of Coppell- Constr Insp Senior Project Engineer The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terraccn. Test results transmitted herein are only applicable to the actual samples tested at the Iccation(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 7 of 7 Ol