Freeport NIP(2.2)-LR011016CONCRETE COMPRESSIVE STRENGTH TEST .H.,~
ENGIN EEE.ING, INC.
8901 Carpenter Frwy., Suite #100
Report Number: 94011204.0044 Dallas, Texas 75247
Service Date: October 8, 2001 (214) 63O-lOlO
Client: TNA North American, Inc. Report Date: October 16, 2001
Attn: Terry Raley Project: Sales Office & Warehouse Fac.
1321 Valwood Parkway, Suite 440 Coppell, Texas
Carrollton TX 75006
Project Number: 94011204
Material Information Sample Information
Specified Strength: 3000 psi @ 28 Days Sample Time: 4:22am Date Cast: October 8, 2001
Technician: Marlo Villanueva
Batch Time: 3:48am Plant: 31 Weather Conditions: Clear
Supplier: TXI Accumulative Yards: 20
Truck No: 139 ~r'icket No: 2995596 Placement Method:
Mix I.D. No.: 9505 V J~ Sample Locations: Grid line 6.5/B
Placement Location: Floor slab-on-grade on lines 1-6/A-D,
6-7/A-B
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.25 3-5 ASTM C-143
Air Content, %:
Concrete Temperature, o F: 68 ASTM C1064
Ambient Temperature, o F: 54 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
1 1 6.00 28.27 10/15/2001 7 104,450 3,690
1 2 6.00 28.27 10/15/2001 7 100,850 3,570
Average 3,630
I 3 11/05/2001 28
1 4 11/05/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 7 0~.~,~,~,-F,,,,.~ Key
CONCRETE COMPRESSIVE STRENGTH TEST
8g01 Carpenter Frwy., Suite #100
Report Number: 94011204.0044 Dallas, Texas 75247
Service Date: October 8, 2001 (214) 63O-lOlO
Client: TNA North American, Inc. Report Date: October 16, 2001
Attn: Terry Raley Project: Sales Office & Warehouse Fac.
1321 Valwood Parkway, Suite 440 Coppell, Texas
Carrollton TX 75006
Project Number: 94011204
Material Information Sample Information
Specified Strength: 3000 psi @ 28 Days Sample Time: 5:22am Date Cast: October 8, 2001
Technician: Marlo Villanueva
Batch Time: 4:51 am Plant: 31 Weather Conditions: Clear
Supplier: TXI Accumulative Yards: 110
Truck No: 722 Ticket No: 2995627 Placement Method:
Mix I.D. No.: 9505 Sample Locations: Grid line 5/D
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.00 3-5 ASTM C-143
Air Content, %:
Concrete Temperature, o F: 69 ASTM C1064
Ambient Temperature, o F: 56 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
2 1 6.00 28.27 10/15/2001 7 98,890 3,500
2 2 6.00 28.27 10/15/2001 7 100,380 3,550
Average 3,530
2 3 11/05/2001 28
2 4 11/05/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 7 o, .~,~,..o,
CONCRETE COMPRESSIVE STRENGTH TEST
8901 Carpenter Frwy., Suite #100
Report Number: 94011204.0044 Dallas, Texas 75247
Service Date: October 8, 2001 (214) 63O-lOlO
Client: TNA North American, Inc. Report Date: October 16, 2001
Attn: Terry Raley Project: Sales Office & Warehouse Fac.
1321 Valwood Parkway, Suite 440 Coppell, Texas
Carrollton TX 75006
Project Number: 94011204
Material Information Sample Information
Specified Strength: 3000 psi @ 28 Days Sample Time: 6:55am Date Cast: October 8, 2001
Technician: Marlo Villanueva
Batch Time: 6:05am Plant: 31 Weather Conditions: Clear
Supplier: TXI Accumulative Yards: 220
Truck No: 101 Ticket No: 2995685 Placement Method:
Mix I.D. No.: 9505 Sample Locations: Grid line 4/A
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.25 3-5 ASTM C-143
Air Content, %:
Concrete Temperature, o F: 67 ASTM C1064
Ambient Temperature, o F: 55 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratorlf Test Data
Age at
Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
3 1 6.00 28.27 10/15/2001 7 97,440 3,450
3 2 6.00 28.27 10/15/2001 7 98,010 3,470
Average 3,460
3 3 11/05/2001 28
3 4 11/05/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 3 of 7 o~ ~
CONCRETE COMPRESSIVE STRENGTH TEST ~"'i'~ ?
ENGINEERING,
Report Number: 94011204.0044 8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
Service Date: October 8, 2001 (214) 63O-lOlO
Client: TNA North American, Inc. Report Date: October 16, 2001
Attn: Terry Raley Project: Sales Office & Warehouse Fac.
1321 Valwood Parkway, Suite 440 Coppell, Texas
Carrollton TX 75006
Project Number: 94011204
Material Information Sample Information
Specified Strength: 3000 psi @ 28 Days Sample Time: 8:00am Date Cast: October 8, 2001
Technician: Mario Villanueva
Batch Time: 7:16am Plant: 31 Weather Conditions: Cloudy
Supplier: TXI Accumulative Yards: 310
Truck No: 081 Ticket No: 2995798 Placement Method:
Mix I.D. No.: 9505 Sample Locations: Grid line 3/D
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.00 3-5 ASTM C-143
Air Content, %:
Concrete Temperature, o F: 67 ASTM C1064
Ambient Temperature, o F: 54 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at
Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
4 1 6.00 28.27 10/15/2001 7 81,060 2,870
4 2 6.00 28.27 10/15/2001 7 85,420 3,020
Average 2,950
4 3 11/05/2001 28
4 4 11/05/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 4 of 7 o, ~,~o,
CONCRETE COMPRESSIVE STRENGTH TEST ~--i~"~'~'~''"~"
ENGI N EEAIN~, I'h~.
8901 Carpenter Frwy., Suite #100
Report Number: 94011204.0044 Dallas, Texas 75247
Service Date: October 8, 2001 (214) 63O-lOlO
Client: TNA North American, Inc. Report Date: October 16, 2001
Attn: Terry Raley Project: Sales Office & Warehouse Fac.
1321 Valwood Parkway, Suite 440 Coppell, Texas
Carrollton TX 75006
Project Number: 94011204
Material Information Sample Information
Specified Strength: 3000 psi @ 28 Days Sample Time: 9:50am Date Cast: October 8, 2001
Technician: Marlo Villanueva
Batch Time: 9:00am Plant: 31 Weather Conditions: Cloudy
Supplier: TXI Accumulative Yards: 410
Truck No: 179 Ticket No: 2995996 Placement Method:
Mix I.D. No.: 9505 Sample Locations: Grid line 2/B
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.25 3-5 ASTM C-143
Air Content, %:
Concrete Temperature, o F: 70 ASTM C1064
Ambient Temperature, o F: 56 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at
Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
5 1 6.00 28.27 10/15/2001 7 81,140 2,870
5 2 6.00 28.27 10/15/2001 7 82,800 2,930
Average 2,900
5 3 11/05/2001 28
5 4 11/05/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 5 of 7 o,.~,.o~.F~.~ Key
CONCRETE COMPRESSIVE STRENGTH TEST
8901 Carpenter Frwy., Suite #100
Report Number: 94011204.0044 Dallas, Texas 75247
Service Date: October 8, 2001 (214) 63O-lOlO
Client: TNA North American, Inc. Report Date: October 16, 2001
Attn: Terry Raley Project: Sales Office & Warehouse Fac.
1321 Valwood Parkway, Suite 440 Coppell, Texas
Carrollton TX 75006
Project Number: 94011204
Material Information Sample Information
Specified Strength: 3000 psi @ 28 Days Sample Time: 11:00am Date Cast: October 8, 2001
Technician: Marlo Villanueva
Batch Time: 10:17am Plant: 31 Weather Conditions: Cloudy
Supplier: TXI Accumulative Yards: 500
Truck No: 103 Ticket No: 2996187 Placement Method:
Mix I.D. No.: 9505 Sample Locations: Grid line 1/A
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.00 3-5 ASTM C-143
Air Content, %:
Concrete Temperature, o F: 69 ASTM C1064
Ambient Temperature, o F: 57 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
6 1 6.00 28.27 10/15/2001 7 100,040 3,540
6 2 6.00 28.27 10/15/2001 7 99,080 3,500
Average 3,520
6 3 11/05/2001 28
6 4 11/05/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 6 of 7 o, ~.,~,,~, F~..,<.y
CONCRETE COMPRESSIVE STRENGTH TEST
ENG~N EER/NG, INC.
8901 Carpenter Frwy., Suite #100
Report Number: 94011204.0044 Dallas, Texas 75247
Service Date: October 8, 2001 (214) 63O-lOlO
Client: TNA North American, Inc. Report Date: October 16, 2001
Attn: Terry Raley Project: Sales Office & Warehouse Fac.
1321 Valwood Parkway, Suite 440 Coppell, Texas
Carrollton TX 75006
Project Number: 94011204
Material Information Sample Information
Specified Strength: 3000 psi @ 28 Days Sample Time: 1:18pm Date Cast: October 8, 2001
Technician: Marlo Villanueva
Batch Time: 12:33pm Plant: 31 Weather Conditions: Cloudy
Supplier: TXI Accumulative Yards: 630
Truck No: 663 Ticket No: 2996407 Placement Method:
Mix I.D. No.: 9505 Sample Locations: Grid line 1/D
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.25 3-5 ASTM C-143
Air Content, %:
Concrete Temperature, o F: 71 ASTM C1064
Ambient Temperature, o F: 58 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at
Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
7 I 6.00 28.27 10/15/2001 7 76,670 2,710
7 2 6.00 28.27 10/15/2001 7 78,120 2,760
Average 2,740
7 3 11/05/2001 28
7 4 11/05/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Mario Villanueva
Report Distribution: /,~/ering, Inc.
(1) TNA North American, Inc. (1) FACServices Inc
(1) Carrell Poole & Yost Architecture (1) David Kent Reviewed by:
(1) R L Goodson Consulting Engineers (1) City of Coppell- Bldg Insp (,-.,'/ ~'~ric J. Cleveland, P.E.
(1) Pacific Builders Inc (1) City of Coppell- Constr Insp Senior Project Engineer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terraccn. Test results transmitted herein are only applicable
to the actual samples tested at the Iccation(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 7 of 7 Ol