Town Center L4B1-LR011024 · -ALPHA TESTING, INC. Concrete Compression Test
2209 Wisconsin St., Suite 100
Dallas, Texas 75229 "t' De"or*
(972) 620-8911
Tested For: CONSTRUCTION MANAGEMENT GROUP Our Repo;t No.: 01612-10
ATTN: MR. JEFF MILLER Issue Date: 10/24/2001
5207 MCKINNEY AVENUE, SUITE 12
DALLAS, TX 75205
Fax Number: (214) 521-1279
Project Desc: COPPELL TOWN CENTER
120 N. DENTON TAPP- COPPELL, TX
FIELD DA TA
Placement Location: STORM SEWER INLET, 18' RCP ~ STATION 2+39
Date Placed: 9/10/01 Plant Number: 29-4000
Time Placed: 1:45 PM Delivery Ticket No.: 814160
Slump (ASTM C-143): 3 Made By: ALPHA
Air Content: N/A
Air Temperature: 78 Cured Specification: ASTM C-31
Specimen Temperature: 80
Date Received: 9/11/01
Delivery Method: PICKED UP BY ALPHA
Field Data Submitted By: SULLIVAN, JASON
Mix Data Submitted By: HANSON
CYLINDER COMPRESSION TEST RESULTS
Lab Cure Cap Date Age Avg. Avg. Avg Depth/ Area: Max
No.: Type: Spec: Tested: (Days): Length Width Diameter Sq. In. Load: PSI:
9 LAB C-1231 9/17/01 7 12 N/A 6 28.27 101254 3580
10 LAB C-1231 10/8/01 28 12 N/A 6 28.27 119140 4210
11 LAB C-1231 10/8/01 28 12 N/A 6 28.27 118617 4190
12 LAB HOLD HOLD 12 N/A 6 28.27 0
Specifications: 28 4000
Results to Date: PASS
Notes:
CC: his, CITY OF COPPELL, CONSTRUCTION MANAGEMENT GROUP
Respectfully Submitted By: . .//_~' //"~,/ of Alpha Testing, Inc.
Our test results and reports are for the exclusive.use of the 6eat (and~elr designated receplents o~1 file In our office) and shall not be reproduced and/or distributed except
wish express approval of ALPHA. The use of our name and te~t resulfs must receive our written approval. Test results and reports apply only to the samples tested and/or
observed, and are not Indicative of the qualities of apparently Identical or similar spedmens.
ALPHA TESTING, INC.
Concrete
Test
2209 Wisconsin St., Suite 10 ompress on
Dallas, Texas 75229 ,Oe"or*
(972) 620-8911
Tested For: CONSTRUCTION MANAGEMENT GROUP Our Report No.: 01612-15
ATTN: MR. JEFF MILLER Issue Date: 10/24/2001
5207 MCKINNEY AVENUE, SUITE 12
DALLAS, TX 75205
Fax Number: (214) 521-1279
Project Desc: COPPELL TOWN CENTER
120 N. DENTON TAPP-- COPPELL, TX
FIELD DA TA
Placement Location: PIERS; D-l, D.5-5, E.1-2, A-3
Date Placed: 9/14/01 Plant Number: 89-3000
Time Placed: 2:00 PM Delivery Ticket No.: 89002166
Slump (ASTM C-143): 4.0 Made By: ALPHA
Air Content: N/A
Air Temperature: 86 Cured Specification: ASTM C-31
Specimen Temperature: 88
Date Received: 9/15/01
Delivery Method: PICKED UP BY ALPHA
Field Data Submitted By: CANNON, KEVIN J
Mix Data Submitted By: BEALL
CYLINDER COMPRESSION TEST RESUL TS
Lab Cure Cap Date Age Avg. Avg. Avg Depth/ Area: Max
No.: Type: Spec: Tested: (Days): Length Width Diameter Sq. In. Load: PSI:
5 LAB C-1231 9/21/01 7 12 N/A 6 28.27 86490 3050
6 LAB C-1231 I0/12/01 28 12 N/A 6 28.27 141150 4990
7 LAB C-1231 10/12/01 28 12 N/A 6 28.27 146830 5190
8 LAB HOLD HOLD 12 N/A 6 28.27 0
Specifications: 28 3000
Results to Date: PASS
Notes:
CC: HIS, CITY OF COPPELL, CONSTRUCTION MANAGEMENT GROUP
Respectfully Submitted By: /~P~' /./'_ f of Alpha Testing, Inc.
Our test resul~ and report~ are ~r~e exdu,lve u,e °f~e Clle~ (and ~eir de,i~a~d receplen, on file In our office)and ,hall not~ reproduced and/or di,~buted except
wl~ expr~s approval of ALPHA. The u~e of~r name and ~st resul~ mus~ receive our wrl~n approval. Test resul~ and repo~ apply only m ~e ~mples ~s~d and/or
o~ed, and are not Indl~e of ~e qualities of apparently Identical or similar specimens.
, ,?,~otechni~l Engineering Constru~lon Materials Testing * :' Environ~b~IEngin~dng~'~' .......... * Consulting ;~ ..... ~ :~';~t .,~,';. 11281
ALPHA TESTING, INC.
Concrete
Test
2209 Wisconsin St., Suite 10 ompress.on
Dallas, Texas 75229 °e' or,
(972) 620-89'1 `1
Tested For: CONSTRUCTION MANAGEMENT GROUP Our Report No.: 01612-13
ATTN: MR. JEFF MILLER Issue Date: 10/24/2001
5207 MCKINNEY AVENUE, SUITE 12
DALLAS, TX 75205
Fax Number: (214) 521-1279
Project Desc: COPPELL TOWN CENTER
120 N. DENTON TAPP-- COPPELL, TX
FIELD DA TA
Placement Location: PIERS; C-4, D.5-3.5, D.5-4.5, D.5-4, B-5
Date Placed: 9/13/01 Plant Number: 89
Time Placed: 3:05 PM Delivery Ticket No.: 24164
Slump (ASTM C-143): 4.0 Made By: ALPHA
Air Content: N/A
Air Temperature: 85 Cured Specification: ASTM C-31
Specimen Temperature: 86
Date Received: 9/14/01
Delivery Method: PICKED UP BY ALPHA
Field Data Submitted By: CANNON, KEVIN J
Mix Data Submitted By: BEALL
CYLINDER COMPRESSION TEST RESUL TS
Lab Cure Cap Date Age Avg. Avg. Avg Depth/ Area: Max
No.: Type: Spec: Tested: (Days): Length Width Diameter Sq. In. Load: PSI:
1 LAB C-1231 9/20/01 7 12 N/A 6 28.27 106330 3760
2 LAB C-1231 10II1/01 28 12 N/A 6 28.27 127330 4500
3 LAB C-1231 10/11/01 28 12 N/A 6 28.27 126910 4480
4 LAB HOLD HOLD 12 N/A 6 28.27 0
Specifications: 28 3000
Results to Date: PASS
Notes:
CC: HIS, CITY OF COPPELL, CONSTRUCTION MANAGEMENT GROUP
Respectfully Submitted By: . . _ of Alpha Testing, Inc.
Our test results and reports are for the exclusive use of the C4nt (and~eir designated receplents on file in our office) and shall not be reproduced and/or distributed except
with express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply only to the samples tested and/or
observed, and are not Indicative of the qualities of apparently Identical or sim#ar specimens.