Verizon-LR 981027CONCRETE COMPRELoIVE STRENGTH TES' Date of Service: 10/16/1998 Client No.: THE BECK Client: The Beck Group Attn: Gillett Berger 1700 Pacific Ave., Suite 3800 Dallas TX 75201-4619 Report No.: Project No.: Project: ENGINEERING, INC. 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 9828241 Report Date 10/27/1998 43-2333-98 GTE Shared Services Coppell Road & Corporate Drive Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required field test and cast compressive strength samples. CONTRACTOR: BECK CONCRETE SUPPLIER: TXI PLANT: 42 SPECIFICATION REQUIREMENTS STRENGTH: 3000 psi @ 28 Days SLUMP: 5.0" AIR: N/A METHOD: ASTM C- 143 ASTM C-172 ASTM C-39 PROJECT DATA CONCRETE CLASS: N/A PLACEMENT DATE: 10/16/1998 RATCI~ TreE: 9: 14am Tm SAMPLED: 10:15am aY: Brian Otis WEATHER CONDITIONS: TEMPERATURE (F)- AIR TRUCK NO: 538 AIR CONTENT (%): N/A PLACEMENT LOCATION: Piers Clear/Mild 74 F CONCRETE: 80 F TICKET NO: 1162000 UNIT WEIGHT (pct')..' N/A SAMPLE LOCATION: Piers- D-4 CYLINDER MARKED SET NO. MEASURED SLUMP (inches) 1 1 6.0 1 2 6.0 I 3 6.0 I 4 6.0 DATE TESTED 10/23/1998 10/23/1998 REPORT OF TESTS ACCUMULATIVE YARDS: MAXIMUM COMPRESSIVE AGE LOAD STRENGTH (days) (lbs. force) (psi) 7 85200 3010 7 86730 3070 Average 3040 11/13/1998 11/13/1998 28 28 1 5 6.0 12/11/1998 56 Technician time: See Technician: Brian Otis Report Distribution: (1) The Beck Group 0,LGromatzky Dupree & Assoc. rockette Davis Drake, h~c. . he Beck Group Report #9828240 Started: (1) Brockette Davis Drake, lac. (1) Dalcan, Inc. (1) The Beck Group Finished: ~ E~ing, Inc. Eugene Harbour Vice President 10 FRACTURE TYPE This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, lac. O1LL Page 1 of 1 'REPORT OF DRILLED PIER INSPECTION 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Date of Service: 10/14/1998 Client No.: THE BECK Client: The Beck Group Attn: Gillett Berger 1700 Pacific Ave., Suite 3800 Dallas TX 75201-4619 Report No.: 9828000 Project No.: 43-2333-98 Report Date 10/27/1998 Project: GTE Shared Services Coppell Road & Corporate Drive Coppell, Texas Services: Drilled pier inspection. On this date, an HBC jobsite as scheduled recorded data. Engineering for drilled technician arrived at pier inspection. See the above referenced attached sheet for Technician Time: 6:00 Technician: Brian Otis -SZeport Distribution: fhe Beck Group ~ ~ ) Gromatzky Dupree & Assoc. (I) Brockette Davis Drake, inc. (1) The Beck Group am to 6:00 pm (I) Brockette Davis Drake, Inc. (I) N.L. Schutte Foundation Drilling (1) The Beck Group ~ En~ng, Inc. Eugene Harbour Vice President This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, inc. 99TM~P Pa~e 1 of 1