Freeport NIP(2.2)-LR011128FIELD DENSITY TESTING
Report Number: 94011204.0071
8901 Carpenter Frwy., Suite #100
Service D~ate.~~ber 14, 2001 Dallas, Texas 75247
(214) 630-1010
Cli~l~t:/NA North Ameri(Jan, Inc. Report Date: November 28, 2001
~ 'Attn'.Terry Raley~ Project: Sales Office & Warehouse Fac.
~, 1321 Valwood P~rkway, Suite 440 Coppell, Texas
006
Project Number: 94011204
Material Information Lab Test Data Project Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Material Laboratory Content Weight Range Unit Weight
No. Test Method Description and Classification (%) (pct') (%) (% compaction)
1. ASTM D-698 Dk & med brown clay 23.0 97.0 -1/+3 95
Field Test Data Probe Water Dry Unit Dry Unit
Test Lift/ Mat. Depth Content Weight Weight
No. Test Location Elevation No. (inches) (%) (pcf) (% compaction)
Fire Lane, Parking Area
42 Fire lane, 250' W of E, 3' S of curb line, Final 1 6 22.0 95.0 98
N side of building
43 Parking, 6' N of S, 36' W of E, N side of Final I 6 22.6 94.2 97
building
44 Fire lane, 45' E of W, 18' N of S, N side Final 1 6 23.0 95.1 98
of building
45 Parking, 48' N of S, 30' E of W, N side of Final 1 6 23.9 94.2 97
building
Comments:
Test results on this report meet project specification.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method;ASTM D2922, ASTM D3017
Gauge ID: 31787
Field Results Reported To: Contractor / ////J/
Technician: Roy Montgomery
Report Distribution: c.
(1) TNA North American, Inc. (1) FACServices Inc Reviewed by:
(1) Carrell Poole & Yost Architecture (1) David Kent
(1) R L Goodson Consulting Engineers (1) City of Coppell - Bldg Insp Eric J. Cleveland, P.E.
(1) Pacific Builders Inc (1) City of Coppell - Constr Insp Senior Project Engineer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terrecon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.