Loading...
Freeport NIP(2.2)-LR011119CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94011204.0046 8901 Carpenter Frwy., Suite #100 Service Date: October 19, 2001 Dallas, Texas 75247 (214) 630-1010 Client: TNA North American, Inc. Report Date: November 19, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 2:41pm Date Cast: October 19, 2001 Technician: Arley McCullar Batch Time: 1:52pm Plant: 41 Weather Conditions: clear Supplier: TXI Accumulative Yards: 40 Truck No: 451 Ticket No: 3005004 Placement Method: Mix I.D. No.: 9505 Sample Locations: Grade beams @ SW corner of bldg. Placement Location: Grade beams- C/6 to C/7 to D/7 to D/6 Field Test Data Test Result Specification Test Method Slump, inches: 5.00 2-5 ASTM C-143 Air Content, %: N/A Concrete Temperature, o F: 80 ASTM C1064 Ambient Temperature, 0 F: 82 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 10/26/2001 7 84,810 3,000 1 2 6.00 28.27 10/26/2001 7 88,200 3,120 Average 3,060 1 3 6.00 28.27 11/16/2001 28 108,840 3,850 1 4 6.00 28.27 11/16/2001 28 109,790 3,880 Average 3,870 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician:Arley McCullar f, / // Report Distribution: ~/~ng, Inc. (1) TNA Nodh American, Inc. (1) FACServices Inc (1) Carrell Peele & Yost Architecture (1) David Kent Reviewed by: (1) R L Goodson Consulting Engineers (1) City of Coppell - Bldg Insp Eric J Cleveland P E (1) Pacific Builders Inc (1) City of Coppell - Constr I nsp Senior Project Engineer The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 a,-~Lw~,