June 9, 2000
Mr. Kent Collins, P.E.
Engineering and Public Works
City of Coppell
255 Parkway Blvd.
Coppell, Texas 75019-4409
Coppell Road Reconstruction
SH 121 to Sandy Lake Road
Coppell Project #: ST 98-01
Dear Mr. Collins:
Enclosed for your review and approval is a concrete batch design from Texas Industries, Inc. for
3000 psi concrete. It is our intent to utilize this concrete for miscellaneous concrete flat work
and slip form concrete paving. Please inform us of your decision regarding this design.
Sincerely,
Robert D. Weber
Project Engineer
XC:
Mr. Kevin C. Young, E.I.T., Freese and Nichols, Inc., 1701 N. Market Street
Suite 500 LB51, Dallas, Texas 75202
AN EQUAL OPPORTUNITY EMPLOYER
1341 West Mockingbird Lane · Dallas, Texas 75247 · 972.647.6700 · www. txi.com
Ootober 5, 1999
Ed Bell Construction Company
P.O. Box 540787
Dallas, TX 75354-0787
Attn: Rob Weber
RE: Coppell Road
8272
The attached concrete mix designs utilizing the appropriate ASTM
C-33 or ASTM C-330 aggregate are proposed for use on the above
referenced project for ready-mixed concrete to be furnished by
TXI.
To ensure that the correct mix is delivered to your project,
please order by the mix design number which appears zn the upper
left hand corner of the mix design.
Texas Industries certifies that the above mix designs, when
ordered by specified design identity, and delivered by TXI, will
meet or exceed the indicated design strength at the designated
age when tested in accordance with the applicable and current
ASTM Standards C 31, C 39, C 78, C 172, C 293, applicable
provisions of C 94, and evaluated in accordance with applicable
provisions of ACI Building Code.
TXI would like to be included on your mailing list to receive all
test reports. ASTM C 94 entitles a manufacturer to receive
copies of all test reports when strength of concrete is used as a
basis for acceptance.
Please contact us if you have any questions or require any
additional information. Please notify TXI of approval of the
proposed mix designs prior to their use. Failure to notify us
prior to first placement shall constitute acceptance. To ensure
that the proper mix designs are ordered, please send a copy of
this letter, after approval, to the above referenced project to
be used by the person ordering the concrete for this job.
Sincerely,
TXI Operations, LP
Reedie Stone
Customer Service Representative
Mix #: 8272
Description: 5.00SK ADMIX/AEA
Strength: 3000 psi @ 28 Days
i"CS
PAVING & HANDWORK
Maximum Coarse Aggregate: 1" - #4 CRUSHED STONE
Maximum Water/Cement Ratio: 6.20 gal/sack or 0.549 lbs/lb
Cement/Cementitious Content: 5.00 sacks (per cubic yard)
Maximum Placement Slump: 4.00 inches
Air Entraining Agent: ASTM C-260
Admixture: ASTM C-494 Type A or D
MATERIAL QUANTITIES PER 1.0 CUBIC YARD AT S.S.D
470 lbs. ASTM C 150 TYPE I CEMENT
1840 lbs. 1" - #4 CRUSHED STONE
1352 lbs. CONCRETE SAND
258 lbs. or 31.0 Gallons of Water
2.0 to 4.0 oz/cwt of ASTM C-494 Type A
Specified Air Content: 3.0% - 6.0%
Placement Slump: 3.00 + or - 1.00 inches
PUMPING NOTES / RECOMMENDATIONS
1. 5" minimum diameter lines with no reduction to smaller
lines.
2. .Keep rubber hose to absolute minimum length and plan pipe
with as few 90 degree angles as possible.
3. Samples for slump and strength tests should be taken @
discharge end of hose for strength guarantee to be valid.
4. To prime pump lines, a minimum of 8.0 sack grout should be
used for lubrication. In the case of strength concrete,
equivalent strength grout should be used if the grout
remains in the placement.
5. Pump mixes are based on minimum cement content pumped at
ground level. As pump line increases in length or height
and/or layout configuration changes, additional cement may
be required to assure strength and pumpability at additional
cost to the contractor.
6. TXI cannot control, and is therefore not responsible for
excessive loss of entrained air content when loss occurs as
a result of boom configuration or free fall discharge from
hose. To ensure minimum air loss when pumping, maintain a
continuous flow of concrete through the entire length of
pipe and do not subject concrete to free fall.
7. The term "pumpable concrete" refers to concrete which is
capable of being transported through an apparatus which
forces concrete to the placing position through a pipeline
or hose as long as the recommendations indicated above are
followed. The term "pu~pable concrete" does not relate to
concrete proportioned in a particular manner or containing a
specific type of product.
Unless otherwise indicated, when the concrete temperature at
point of placement exceeds 90 degrees Fahrenheit, TXI will
guarantee the strength performance of the mix design(s) herein
submitted up to a maximum placement temperature of 100 degrees
Fahrenheit using an ASTM C 494 Type D retarding water-reducer, as
long as the concrete is placed within 75 minutes from batch time.
Unless otherwise indicated, strength of plain concrete guaranteed
up to a maximum placement temperature of 85 degrees Fahrenheit.
We are enclosing all available back up data for the referenced
mix design(s). If the strength information is not available, or
is insufficient, confirmation tests may have to be conducted by
your laboratory.
Strength of lightweight mix designs valid provided strength
specimens are cured in accordance with ASTM Test Method C 567, as
referenced in section 8.1 of ASTM Specification C 330.
Date: 10/05/99
~ D~Igi ~ALUATIOM
** Statistics Compiled From Independent Laboratory Test Specimens **
Nix Ntmber: 8272
Strength: 30O0 l~i @ 28 Days
28 Day Test Data
~est
Number Date
1 05/05/99
2 05/05/99
3 05/05/99
4 05/05/99
5 05/05/99
6 05/06/99
7 05/06/99
8 05/06/99
9 05/07/99
10 05/07/99
11 05/07/99
12 05/12/99
13 05/21/99
14 05/24/99
15 05/24/99
16 05/24/99
17 05/24/99
18 05/24/99.
19 05/24/99
20 05/24/99
21 05/24/99
22 06/08/99
23 06/09/99
24 06/10/99
25 06/14/99
26 06/14/99
27 06/14/99
28 06/14/99
29 06/17/99
30 06/18/99
*** Averages ***
Temperature
Plant (Fahrenheit) Placement
Number Ambient Concrete Slump(in)
38 79
81
84
40 86
40 88
40 84
35 58
35 63
35 60
35 58
46 89
46 93
40 78
46 74
46 85
82 5.00
85 5.25
84 5.00
86 5.50
74 5.00
79 2,00
86 3.25
86 3.00
80 5.50
73 4.50
72 6.00
86 4.50
78 5.00
79 4.50
87 5.50
87 5.50
86 6,00
56 5.00
58 5.50
53 5.25
56 5.00
90 7,00
96 5,50
86 4.25
88 7.00
92 6.75
78 8.50
79 8.00
91 5.00
86 3.00
Percent ......... 28 Day ........ Cumulative
of Air
PSI 1 PSI 2 PSI Avg
3.5% 3420 3570 3495 3495
3.6t 3450 3560 3505 3500
3.4t 3790 3830 3810 3603
3.6t 3470 3840 3655 3616
2.2t 3750 4100 3925 3678
4.1% 4510 4680 4595 3831
4.0% 4680 4590 4635 3946
3.6% 4690 4900 4795 4052
4.5% 3610 3710 3660 4008
4.5% 4040 3710 3875 3995
4.3% 3310 3400 3355 3937
3.2% 4810 5110 4960 4022
4.6% 3660 3830 3745 4001
5.4% 4100 4470 4285 4021
4.0% 4740 4560 4650 4063
N/A 4280 4260 4270 4076
3.8% 3980 4020 4000 4071
4.8% 4630 5180 4905 4118
4.7% 4930 4360 4645 4146
5.01 4760 4590 4675 4172
5.0% 4750 5380 5065 4215
N/A 3880 4000 3940 4202
N/A 4590 5150 4870 4231
N/A 3850 3800 3825 4214
2.0% 4300 4380 4340 4219
3.9% 4110 4260 4185 4218
4.2% 4140 4000 4070 4212
4.31 4320 4280 4300 4216
N/l 5780 5560 5670 4266
N/A 5050 4800 4925 4288
Moving
Average Avg of 3 Range
150
110
3603 40
3657 370
3797 350
4058 170
4385 90
4675 210
4363 100
4110 330
3630 90
4063 300
4020 170
4330 370
4227 180
4402 20
4307 40
4392 550
4517 570
4742 170
4795 630
4560 120
4625 560
4212 50
4345 80
4117 150
4198 140
4185 40
4680 220
4965 250
77 80 5.23 4.0%
COMMENTARY OF STATISTICAL EVALUATION OF CONCRETE DESIGN RESULTS
Mix Num: 8272
Strength: 3000 psi @ 28 Days
Paragraph 5.5 of ACI 318-95 provides that as data becomes
available during construction, the amount by which (F'cr) must
exceed the specified value of (F'c) may be reduced, provided:
(a) 30 or more test results are available and average of
test results exceeds that required by Section 5.3.2.1,
using a standard deviation calculated in accordance
with Section 5.3.1.1, or
(b) 15 to 29 test results are available and average of test
results exceeds that required by. Section 5.3.2.1, using
a standard deviation calculated in accordance with
Section 5.3.1.2.
The required average compressive strength has been calculated
using a standard deviation calculated an accordance with
ACI 318-89 Section 5.3.1.1 or Section 5.3.1.2 and is the larger
value of these calculations:
F'cr = F'c
= 3000
= 3754
F'cr = F'c
= 3000
= 3811
+ 1.34(SD)
+ 1.34( 562.7)
+ 2.33(SD) - 500
+ 2.33( 562.7) - 500
SUMMARY OF STATISTICAL ANALYSIS
28 Day Test Data
Number of Tests .......................... 30
Maximum Value ............................ 5670 ps%
Minimum Value ............................ 3355 ps~
Range .................................... 2315 psi
Average Strength ......................... 4288 psi
Standard Deviation ....................... 563 psi
Required Average Strength to satisfy
minimum probability conditions of
ACI 318-89 Section 5.3.2.1 ............... 3811 ps%
Design excess beyond code requirements... 477 psx
MIDLOTHIAN CEMENT PLANT · 245 Ward Road · Midlothian, Texas 76065 · www.txi.com
SPECIFICATIONS
Portland Cement
Type 1/11 (Low Alkali)
A,S.T.M. C150-97
Bin Number.
Car Number'
Tons
Date of Sampling
July 1999 Monthly Average
ASTM
SPECIFICATION
CHEMICAL REQUIREMENTS
Silica Oxide, Minimum Percent
Alumina Oxide, Maximum Percent
Iron Oxide, Maximum Percent
Magnesia Oxide, Maximum Percent
SOs (CsA less than 8%), Maximum Percent
Loss on Ignition, Maximum Percent
Insoluble Residue, Maximum Percent
Tricalcium Aluminate, Maximum Percenl
OPTIONAL CHEMICAL REQUIREMENTS
Total Alkalies, Max. % (Na20 equiv.)
PHYSICAL REQUIREMENTS
Specific surface, Blaine Minimum (m2/kg)
Gillmore, Initial Set, Minimum (Minutes)
Gillmore, Initial Set, Maximum (Minutes)
Vicar, ~Minimum (Minutes)
Initial Set Maximum (IVlinutes)
Air Content, Volume, Maximum Percent
Autodave Expansion, Maximum Percent
3 Day Minimum Compressire Strength, MPa (psi)
7 Day Minimum Compressive Strength, MPa (psi)
STATE OF TEXAS
TEST
RESULTS
20.0 t 20.6
6.0 4.2
6.0 3.8
6.0 1.2
* ~ 3.3,
3.0 I 0.9
o.75 I o.16
8.0 i 5.o
0.60 i 0.41
280 I 345
60 I 159
600 I 282
375 94
12 i5
0.80 I0.01
12.0 (1740) I21.4 (3097}
19.0 (2760) i29.9 (4338)
ELLIS COUNTY
J.R. Wendel , being duly sworn deposes and says: that he is Quality Services
Manager of TXI Midlothian Cement Plant, who prepared the above report of tests
and that the same is true and correct.
Subscribed nd sworn to before me this 11th day of August, 1999.
QualmServices Manager
· See ASTM C150 Table 1, Footnote B.
K. C. COKER
NOTARY PUBLIC )
SI'ATE OF TEXAS )'
My Co.mL;ss;on E~p;r=s ~,
i" I f
'!
Concrete Products
W.R. Grace & Co.
200t East Randol Mill, Suite
Arlington, TX 760t t
Janua~ 8,1998
(817) 46t-4t0t
(8t7) 459-t084
Texas Industries, Inc.
Dallas, Texas'
Gentlemen:
This is to certify that DARATARD-17, a water-reducing set-retarding
admixture, supplied by the Construction Products Division, W.R. Grace &
Co.-Conn., is formulated to comply with Specifications for Chemical
Admixtures for Concrete, ASTM Designation: C-494, as a Type B & D
admixture; and the Standard'Specifications of the Texas Highway
Department.
No chlorides or halogens are added to DARATARD-17 as functional
ingredients during manufacture.
Material supplied for the above referenced project is identical in all respects,
including concentration;-to-the one originally-submitted-to and-approved by-'
the State of Texas, Dept. of Transportation.
The above is in addition to and not in substitution for our standard Conditions
of Sale printed on the reverse side hereof.
Sincerely,
Tom C. Henson
District Manager
Subscribed and swam to, before me,
this 8th day of January, 1998 A.D.
Lorene B.Raso, Notary Public.
In and For the State of T~jxas
We hope the information given here will be helpful. tt is basea on our best knowledge. and we believe it to be true and accurate. Rease read all slatemenls.
reccx-nmendations or suggestions herein in conjuction vtith our c3r~itions of sale which apply to all gcxx:ls supIdled by us. We assume no responsibility for the use
of these statements, recommendations. or suggestions. nor do .,re Intend them as o recommendation for any use which would Infringe any patent or copyright.
Grace Construction Products
W.R. Grace & Co. - Corm
4323 Crltes Street
P.O. Box 2585.77252
Houslon. TX 77003
December 16, 1998
Texas. Industries, Inc.
1341 West Mockingbird Lane
Dallas, Texas 75247
Gentlemen:
This is to certify that WRDA with HYCOL, a water-reducing admixture, as
manufactured and supplied by the Construction Products Division, W. FL
Grace & Co.-Conn., is formulated to comply with Specifications for Chemical
Admixtures for Concrete,.. ASTM Designation: C-494, Type A (AASHTO
M194, Type A).
WRDA with HYCOL does not contain calcium chloride or chloride containing
compounds as a functional ingredient. Chloride ions may be present in trace
amounts contributed from the domestic water supply used during the
manufacturing process.
The above is in addition to and not in substitution for our standard Conditions
of Sale printed on the reverse side hereof.
· -. ~ ncerely, ~
Tom C. Hanson
District Manager
Subscribed and sworn to, before me,
this 16th day of December, 1998 A.D
L~so,/~o~
In and For the State of Texas
LORENE B. RASO
MY COMMISSION EXPIRES
March 28. 2002 -
.... . .- - _ ;_ _~ _~, ........
We hope the information given her~ will be heli~ful. It is based on our best knowledge. and we believe it to be true and. accurate· P. lease read ,all slatetents,,
, recommendations. or suggestions herein In c~njunction with oul'condifiOns of sole which apply to oll g~>ocls supplied by us. We assume no ;esp~nslbili~y for Ihe use
o~ Ihese slatemenls. recommendations or suggestions nor do we inland Ihern as recommendation lot any use which would infringe any patent or copyright
I "'r .... T i "[
Concrete Products
W.R. Grace & Co.
20.0t East Randol Mill, Suite t t t5
Arlington, TX 760t t
January 8,1998
[817) 46t-410t
[817] 459-t084
Texas Industries, Inc;
Dallas,, Texas
Gentlemen:
This is to certify that DARACEM-19, a high range water-redudng admixture,
as manufactured and supplied by the Construction Products Division, W. R.
Grace. & Co.-Conn., is formulated to comply with Specifications for Chemical'
Admixtures for Concrete, ASTM Designation: C--494, Types A & F (AASHTO
M 194, Types A & F).
DARACEM-19 does not contain caldum chloride Or chloride containing
compounds as a functional ingredient. Chloride ions may be present in trace
amounts contributed from the domestic water supply used during the
manufacturing process.
The ab, ove is in addition to and not in substitution for our Standard Conditions
of Sale pdnted on the reverse side hereof.
Sincerely, ':
Tom C. Henson
Distdct Manager.
Subscribed and sworn ~o, before me,
this 8th. day of January, 1998 A.D.
~'; '~S~ Notary Public, Sta~e of Texas
,~ 0~4y Commission ~plres 03-28-I G9~
Lorene B. Raso, o
In and For the State of Texas
...',
We hope the Infofmation given here will be helpful. It is based on our best knowledge, and we believe It to be true akd accurate. Rease read all statements,
recommendations of suggesllons hereln In conjuctlon with our conc~tions of sale which apply to all goods supplied Dy us. We assume no responsibility fox Ihe use
d Ihese statements. recommendatlcx'~s, or suggestions, nor do we Intend them as o recommendation fof any Use which would Infringe any paten! of copyright.
Date: 04/28/99
Size: 3__3
Project: *,****ALL TESTS*"**
SIEVE CUMULATIVE
SIZE WT. RETAINED
2.0"
1.5"
1.0"
3/8"
#8
#10
#16
#30
#-40
#50
#100
#200
PAN WT.
M.C. 5.3%
DECANT
S.E. 91.2%
100% of tests: 93 Size: 33
TEXAS INDUSTRIES
QUALITY CONTROL DEPT.
AGGREGATE SIEVE ANALYSIS
Production Facility:
Grading Designation:
Sample Location:
CUMULATIVE CUMULATIVE
% RETAINED % PASSING.
PARADISE
ASTM C-33
REQUIRED
% RETAINED
FINE AGG.
SPECIFICATION
% PASSING
.81 99.19 0 - 5
19.02 80.98 0 - 20
95-100
80-100
35.23 64.77 15- 50 50- 85
51.87 48.13 40- 75 25- 60
72.74 27.26 70- 90
96.05 3.95 90- 98
98.88 1.12
2.76 FINENESS MODULUS
10 - 30
2-10
PLANT: PARADISE
Job: *******ALL JOBS** .... *
Date:
Size:
Project:
SIEVE
SIZE
2.0"
1.0"
4II
3/8"
#8
#10
#16
#30
#40
#50
#100
#200
PAN VVT.
Decant
100% of
07/17/99
5..Z7
*****ALL TESTS*****
CUMULATIVE
Wq'. RETAINED
TEXAS INDUSTRIES
QUALITY CONTROL DEPT,
AGGREGATE SIEVE ANALYSIS
Production Facility:
Grading Designation:
Sample Location:
CUMULATIVE -CUMULATIVE
% RETAINED % PASSING
TXI - BRIDGEPORT, TEXAS
ASTM C-33 1" - ff-4.
REQUIRED
% RETAINED
.89%
tests: 151 'Size: 57
SPECIFICATION
% PASSING
0 100 0 100
1.72 98.28 0 - 5 95 - 100
17.46 82.54
55.43 44.57 40 - 75 25 - 60
79.30 20.70
97.20 2.80 90 - 100 0 - 10
98.83 1.17 95 - 100 0 - 5
99.13 0.87
PLANT: BRIDGEPORT
Job: ** ..... ALL JOBS******~ .'