CF-Coppell Rd SC-LR011003 Hooper Engineering Laboratories, Inc. Construction Materials Testing REPORT OF WATER PRESSURE INJECTION CLIENT: Texas Unified Constructors, Inc. DATE: 3 October 2001 PROJECT: Field Service Offices & Maintenance Fac. JOB NO.: 01.1054 for City of Coppell, TX TIME: 7:30am-1:00pm SUPPLIER: Kenneth Moore 5.50 hours LOCATION: Covered Storage pad (three-fourths of Pass //5) NUMBER OF RIGS USED: 1 PROCEDURE: On 3 October 2001, a representative of Hooper Engineering Laboratories, Inc. visited the above named project during the time in which water pressure injection was taking place. During that time, he noted the following: SPECIFICATION REQUIREMENTS INSPECTION RESULTS: 1. Injection pressure 50 psi to 200 psi. 200, 200 2. Injection downward in approx. 12" intervals until refusal Yes (If No, see remarks below.) 3. Total depth of injection - 10 feet Yes (If No, see remarks below.) 4. Spacing for injection approx. 5 feet maximum. Yes (If No, see remarks below.) TECHNICIAN:CBC DISTRIBUTION: (3) City of Coppell (1) Vidaud & Associates (1) Texas Unified Constructors, Inc. (1) Doyle Engineering Group 2870 Walnut Hill Lane Dallas, Texas 75229 (214) 351-6419 Fax (214) 351-5148