Gateway BP(1.4)-LR180406FLOOR FLATNESS TESTING REPORT Report Number:94171346.0181 Service Date:04/06/18 8901 Carpenter Fwy Ste 100 Report Date:04/10/18 Dallas, TX 75247-4547 214-630-1010 Reg No: F-3272 Client Project Haverty Furniture Co Inc Haverty's Warehouse Expansion Attn: Glenn Boone 770 Gateway Blvd 780 Johnson Ferry Rd NE Ste 800 Coppell, TX 75019 Atlanta, GA 30342 Project Number: 94171346 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 9-28-10, Rev.8 Page 1 of 2 Location Surveyed SOG, Placement 2, E – H / 4 - 6 Date of Placement 4/6/18 Approximate Area 14,500 square feet ASTM Standard ASTM E 1155 Instrument Used Dipstick 2277, manufactured by Face Technologies Sampling Method Point elevations were measured at regular 12 inch intervals along 6 straight lines up to 103 feet in length. The elevation differences between all adjacent reading points, the arithmetic differences between all adjacent 12 inch elevation differences, and the elevation differences between all points separated 10 feet were then calculated. Estimates of the floor's flatness and levelness F-Numbers (FF and FL) were obtained through a statistical analysis of these calculated profile values. See attached pages for individual measurement line results. Overall Value (FF/FL)50 / 30 Specified Limits Minimum Local Value (FF/FL)30 / 18 *Combined Flatness F-Number (FF)*Combined Levelness F-Number (FL) 64.62 ( 61.74 – 67.51 )38.31 (36.49 – 40.12)Measured Results *Based upon the number of samples taken, there is a 90% certainty that the actual F-Numbers of the surface surveyed will fall within the ranges which follow the respective estimated Flatness and Levelness F-Numbers. Comments: FLOOR FLATNESS TESTING REPORT Report Number:94171346.0181 Service Date:04/06/18 8901 Carpenter Fwy Ste 100 Report Date:04/10/18 Dallas, TX 75247-4547 214-630-1010 Reg No: F-3272 Client Project Haverty Furniture Co Inc Haverty's Warehouse Expansion Attn: Glenn Boone 770 Gateway Blvd 780 Johnson Ferry Rd NE Ste 800 Coppell, TX 75019 Atlanta, GA 30342 Project Number: 94171346 Services: Floor flatness/levelness testing. Terracon Rep.: Mohammad Hassan Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez Reviewed By:____________________________________ (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko Joel Warriner, P.E. Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 9-28-10, Rev.8 Page 2 of 2 4 6 E H N 43 5 6 2 1