462HoustonSt_75019_43056 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
Name of PWS:Coppell
PWS I.D.:0570040
Address:816 S.Coppell Road
Coppell,Texas 75019
Phone:972-462-5150
Contact Person:Jerry Davis
Catalog No: TXTCOP-22311
Test Date: 4/24/2018
Result: Passed
Reason for Test: Existing
Account Name : Frost
Address of Assembly : 462 Houston St
Address Type : Commercial
Inspection
The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within
acceptable parameters.
Type of Assembly :Double Check Valve Frequency :Annual What does this serve? Irrigation
Manufacturer :Febco Model No :850 Size :1 Serial No :HE33862
Location At:@ Meter
Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes
Is the assembly installed on a non-potable water supply (auxiliary)?No
Reduced Pressure Principle Assembly Pressure Vacuum Breaker
Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly
1st check 2nd check Relief Valve Air Inlet Check Valve
Initial Test
Date:4/24/2018
Time:1:00 PM
Held at 2.2 psid
Closed Tight
Leaked
Held at 2 psid
Closed Tight
Leaked
Opened at psid
Did not open
Opened at psid
Did it fully open
Yes No
Held at psid
Leaked
Repairs and Materials
Used **
Test After Repair
Date:
Time:
Held at psid
Closed Tight
Leaked
Held at psid
Closed Tight
Leaked
Opened at psid Opened at psid Held at psid
***2nd check:numeric reading required for DCVA only
Test gauge used: Potable Make: Mid-West Model: 845-5 Serial No.: 08160372
Date Tested for Accuracy: 9/5/2017
Remarks :
Firm Name : A.C.E.Companies Licensed Tester : Daniel Klein
Firm Address : 150 E Highway 67,Ste 210 BPAT License # : BP0014132
Firm Phone No : 469-899-6050 License Expiration Date : 06/08/2019
The above is certified to be true at the time of testing.
* Test Records must be kept for at least three years.[30 TAC §290.46(B)]
** Use only manufacturer's replacement parts.