110WSandyLn,Ste150_75019_44267 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
Name of PWS:Coppell
PWS I.D.:0570040
Address:816 S.Coppell Road
Coppell,Texas 75019
Phone:972-462-5150
Contact Person:Jerry Davis
Catalog No: TXTCOP-33981
Test Date: 5/23/2018
Result: Passed
Reason for Test: Existing
Account Name : Senor Locos Tacos
Address of Assembly : 110 W Sandy Ln,Ste 150
Address Type : Commercial
Inspection
The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within
acceptable parameters.
Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic
Manufacturer :Watts Model No :009M2 Size :2 Serial No :066799
Location At:fire closet
Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes
Is the assembly installed on a non-potable water supply (auxiliary)?No
Reduced Pressure Principle Assembly Pressure Vacuum Breaker
Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly
1st check 2nd check Relief Valve Air Inlet Check Valve
Initial Test
Date:5/23/2018
Time:9:35 AM
Held at 8.9 psid
Closed Tight
Leaked
Held at 8.6 psid
Closed Tight
Leaked
Opened at 2.7 psid
Did not open
Opened at psid
Did it fully open
Yes No
Held at psid
Leaked
Repairs and Materials
Used **
Test After Repair
Date:
Time:
Held at psid
Closed Tight
Leaked
Held at psid
Closed Tight
Leaked
Opened at psid Opened at psid Held at psid
***2nd check:numeric reading required for DCVA only
Test gauge used: Potable Make: Longhorn Model: 845-3-0006 Serial No.: 04050499
Date Tested for Accuracy: 9/22/2017
Remarks :
Firm Name : North Texas Backflow Licensed Tester : John Davis
Firm Address : P.O.Box 597 BPAT License # : BP0003132
Firm Phone No : 469-231-6623 License Expiration Date : 06/12/2020
The above is certified to be true at the time of testing.
* Test Records must be kept for at least three years.[30 TAC §290.46(B)]
** Use only manufacturer's replacement parts.