Loading...
515GreenwichLn_75019_44639 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22944 Test Date: 5/31/2018 Result: Passed Reason for Test: Existing Account Name : Current Water Customer Address of Assembly : 515 Greenwich Ln Address Type : Residential Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Zurn Model No :375 Size :1 Serial No :B128743 Location At:garage Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:5/31/2018 Time:1:10 PM Held at 9.8 psid Closed Tight Leaked Held at 9.4 psid Closed Tight Leaked Opened at 2.2 psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Watts Model: TK-99E Serial No.: 0146577 Date Tested for Accuracy: 1/9/2018 Remarks : Firm Name : All STar Backflow &Plumbing LLC Licensed Tester : Steven Sellar Firm Address : 508 Cozby Ave BPAT License # : BP0017629 Firm Phone No : 469-524*9924 License Expiration Date : 01/15/2019 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.