110WSandyLake_75019_44771 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
Name of PWS:Coppell
PWS I.D.:0570040
Address:816 S.Coppell Road
Coppell,Texas 75019
Phone:972-462-5150
Contact Person:Jerry Davis
Catalog No: TXTCOP-22049
Test Date: 5/31/2018
Result: Failed
Reason for Test: Existing
Account Name : Sprouts
Address of Assembly : 110 W Sandy Lake
Address Type : Commercial
Inspection
The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within
acceptable parameters.
Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic
Manufacturer :Watts Model No :009 Size :1/2 Serial No :A84426
Location At:mop sink
Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes
Is the assembly installed on a non-potable water supply (auxiliary)?No
Reduced Pressure Principle Assembly Pressure Vacuum Breaker
Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly
1st check 2nd check Relief Valve Air Inlet Check Valve
Initial Test
Date:5/31/2018
Time:9:30 AM
Held at 6.7 psid
Closed Tight
Leaked
Held at 7 psid
Closed Tight
Leaked
Opened at 1.2 psid
Did not open
Opened at psid
Did it fully open
Yes No
Held at psid
Leaked
Repairs and Materials
Used **
Test After Repair
Date:
Time:
Held at psid
Closed Tight
Leaked
Held at psid
Closed Tight
Leaked
Opened at psid Opened at psid Held at psid
***2nd check:numeric reading required for DCVA only
Test gauge used: Non-Potable Make: Mid-West Model: 845-5 Serial No.: 02181000
Date Tested for Accuracy: 3/15/2018
Remarks :relief valve neeeds to be replace
Firm Name : American Fire Protection Group Licensed Tester : Rikki Jupp
Firm Address : 10575 Vista Park Rd BPAT License # : BP0018277
Firm Phone No : 214-283-2150 License Expiration Date : 02/08/2021
The above is certified to be true at the time of testing.
* Test Records must be kept for at least three years.[30 TAC §290.46(B)]
** Use only manufacturer's replacement parts.