Gateway BP(1.4)-LR180418 (3)Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0197 04/18/18 05/21/18 Revision 1 - 28-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0240 8810 Plant: Ticket No.: 131 4639612 Field Test Data Test Air Content (%): Result Specification 4 3/4 3 - 5 5.4 3 - 6 75 67 147.7 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:04/18/18 0319 Steven Maumalanga Clear 10/600 10 0 0 10' N of building & 15' W of retaining wall Sample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Pavement, NE FireLanePlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 1 1 4.00 12.57 04/25/18 7 49,685 2 3,950 1 2 4.00 12.57 05/16/18 28 58,540 2 4,660 EAS 1 3 4.00 12.57 05/16/18 28 57,930 2 4,610 EAS 1 4 4.00 12.57 05/16/18 28 56,590 2 4,500 EAS Average (28 days) 4,590 1 5 4.00 12.57 06/13/18 56 Initial Cure:Final Cure:Outside Moist Room Comments:Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Steven Maumalanga The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0197 04/18/18 05/21/18 Revision 1 - 28-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0443 4856 Plant: Ticket No.: 131 4639884 Field Test Data Test Air Content (%): Result Specification 5 1/4 3 - 5 4.7 3 - 6 76 67 145.3 * * = Field Test Results do not meet project specifications. 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:04/18/18 0509 Steven Maumalanga Clear 130/600 10 0 0 50' N of building & 100' W of retaining wall Sample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Pavement, NE FireLanePlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 2 1 4.00 12.57 04/25/18 7 49,120 2 3,910 2 2 4.00 12.57 05/16/18 28 57,880 3 4,610 EAS 2 3 4.00 12.57 05/16/18 28 53,740 3 4,280 EAS 2 4 4.00 12.57 05/16/18 28 56,570 3 4,500 EAS Average (28 days) 4,460 2 5 4.00 12.57 06/13/18 56 Initial Cure:Final Cure:Outside Moist Room Comments:Average compressive strength of 28 day cylinders complies with the specified strength. NOTE: The concrete sample for this set of cylinders was obtained prior to the concrete going into the pump. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Steven Maumalanga The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0197 04/18/18 05/21/18 Revision 1 - 28-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0552 6854 Plant: Ticket No.: 131 4640096 Field Test Data Test Air Content (%): Result Specification 5 3 - 5 6.0 3 - 6 75 65 146.0 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:04/18/18 0633 Steven Maumalanga Clear 210/600 10 0 0 25' N of building & 200' W of retaining wall Sample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Pavement, NE FireLanePlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 3 1 4.00 12.57 04/25/18 7 54,865 2 4,370 3 2 4.00 12.57 05/16/18 28 62,280 3 4,960 EAS 3 3 4.00 12.57 05/16/18 28 62,260 2 4,950 EAS 3 4 4.00 12.57 05/16/18 28 62,840 2 5,000 EAS Average (28 days) 4,970 3 5 4.00 12.57 06/13/18 56 Initial Cure:Final Cure:Outside Moist Room Comments:Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Steven Maumalanga The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0197 04/18/18 05/21/18 Revision 1 - 28-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0701 7884 Plant: Ticket No.: 131 4640467 Field Test Data Test Air Content (%): Result Specification 4 1/2 3 - 5 5.2 3 - 6 77 65 148.0 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:04/18/18 0740 Steven Maumalanga Clear 310/700 10 0 0 0' N of building & 50' W of retaining wall Sample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Pavement, NE FireLanePlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 4 1 4.00 12.57 04/25/18 7 53,150 2 4,230 4 2 4.00 12.57 05/16/18 28 63,420 2 5,050 EAS 4 3 4.00 12.57 05/16/18 28 61,250 2 4,870 EAS 4 4 4.00 12.57 05/16/18 28 67,110 2 5,340 EAS Average (28 days) 5,090 4 5 4.00 12.57 06/13/18 56 Initial Cure:Final Cure:Outside Moist Room Comments:Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Steven Maumalanga The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0197 04/18/18 05/21/18 Revision 1 - 28-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0856 8005 Plant: Ticket No.: 131 4641254 Field Test Data Test Air Content (%): Result Specification 5 3 - 5 4.9 3 - 6 76 67 149.5 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:04/18/18 0931 Steven Maumalanga Clear, sunny 410/600 10 0 0 125' N of building & 125' W of retaining wall Sample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Pavement, NE FireLanePlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 5 1 4.00 12.57 04/25/18 7 55,475 2 4,410 5 2 4.00 12.57 05/16/18 28 62,240 2 4,950 EAS 5 3 4.00 12.57 05/16/18 28 67,270 2 5,350 EAS 5 4 4.00 12.57 05/16/18 28 61,310 3 4,880 EAS Average (28 days) 5,060 5 5 4.00 12.57 06/13/18 56 Initial Cure:Final Cure:Outside Moist Room Comments:Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Steven Maumalanga The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 5 of 6CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0197 04/18/18 05/21/18 Revision 1 - 28-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 1035 5862 Plant: Ticket No.: 131 4641822 Field Test Data Test Air Content (%): Result Specification 5 3 - 5 5.4 3 - 6 78 69 148.6 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:04/18/18 1116 Steven Maumalanga Clear, sunny 520/600 10 0 0 125' N of building & 200' W of retaining wall Sample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Pavement, NE FireLanePlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 6 1 4.00 12.57 04/25/18 7 53,465 5 4,250 6 2 4.00 12.57 05/16/18 28 60,710 2 4,830 EAS 6 3 4.00 12.57 05/16/18 28 64,250 2 5,110 EAS 6 4 4.00 12.57 05/16/18 28 59,470 2 4,730 EAS Average (28 days) 4,890 6 5 4.00 12.57 06/13/18 56 Initial Cure:Final Cure:Outside Moist Room Comments:Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko Joel Warriner, P.E. Senior Project Manager Reviewed By: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Steven Maumalanga The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 6 of 6CR0001, 11-16-12, Rev.6