Gateway BP(1.4)-LR180510 (3)MORTAR COMPRESSIVE STRENGTH TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
Client
94171346.0236
05/10/18
05/21/18
8901 Carpenter Fwy, Ste 100
Dallas, TX 75247-4547
214-630-1010 Reg No: F-3272
Haverty Furniture Co Inc
Attn: Glenn Boone
780 Johnson Ferry Rd NE Ste 800
Atlanta, GA 30342
Coppell, TX 75019
770 Gateway Blvd
Haverty's Warehouse Expansion
Project
Project Number: 94171346
psi @ days
Mix ID:
Supplier:
Batch Time:
Material Information
Plant:
Field Test Data
Test
Mortar Temp. (F):
Ambient Temp. (F):
Result Specification
28
SpecMix
C & B Masonry
1530 On-site
82
86
Specified Strength: 2,500
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Size:
Sample Location:
Sample Time:05/10/18 1545
Scooter Day
Clear
2 x 2 x 2
See Placement Location
Placement Location:H.9-G/8-8.2
Test Mold Material:
Curing Procedure:
Brass
ASTM C 780
Laboratory Test Data
No.
Date Age Area
(lbs)
Load Strength
Compressive
ID Received
Date
Tested (days)(sq in)(psi)
Maximum
Set Specimen Tested
By
1 1 05/17/18 7 4.00 14,255 3,560
1 2 05/17/18 7 4.00 14,565 3,640
1 3 05/17/18 7 4.00 14,185 3,550
Average (7 days) 3,580
1 4 06/07/18 28
1 5 06/07/18 28
1 6 06/07/18 28
Initial Cure:Outside Final Cure:Moist Room
Comments:
Note: The indicated Specified Strength above is for laboratory batched and cast specimens under controlled conditions. Strength tests of field cast specimens are to be used to
monitor trends and batch to batch consistency of mortar per ASTM C 270 and are not intended as criteria to determine the acceptance or rejection of the mortar as installed.
Samples Made By: Terracon
Obtain a sample of masonry mortar used during construction and cast 2 inch cube specimens for compressive strength
determination.
Services:
Reported To:
Contractor:
Report Distribution:
(1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion
(1) Kajima Building & Design Group Inc., Craig
Farwick
(1) Kajima Building & Design Group Inc., Juan
Hernandez
(1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed
Dikko
Senior Project Manager
Joel Warriner, P.E.
Reviewed By:
ASTM C109Test Methods:
Terracon Rep.: Scooter Day
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0008, 11-16-12, Rev.6 Page 1 of 1