Gateway BP(1.4)-LR180601Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0209 05/01/18 06/27/18 Revision 2 - 56-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0218 3239 Plant: Ticket No.: 141 4672106 Field Test Data Test Air Content (%): Result Specification 5 3-5 4.0 3-6 71 69 149.6 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:05/01/18 0315 Alex Miranda Cloudy, moderate wind 50/900 10 20 0 Location #1, see attached sketchSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Fire Lane, see attached sketchPlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 1 1 4.00 12.57 05/08/18 7 56,650 2 4,510 EAS 1 2 4.00 12.57 05/29/18 28 69,940 2 5,570 ZHG 1 3 4.00 12.57 05/29/18 28 71,985 5 5,730 ZHG 1 4 4.00 12.57 05/29/18 28 68,440 2 5,450 ZHG Average (28 days) 5,580 1 5 4.00 12.57 06/26/18 56 78,300 3 6,230 EAS Initial Cure:Final Cure:Outside Moist Room Comments:Compressive strength of 56 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Alex Miranda The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 8CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0209 05/01/18 06/27/18 Revision 2 - 56-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0325 3237 Plant: Ticket No.: 141 4672241 Field Test Data Test Air Content (%): Result Specification 5 3-5 4.5 3-6 72 69 149.2 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:05/01/18 0410 Alex Miranda Cloudy, windy 140/900 10 0 0 Location #2, see attached sketchSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Fire Lane, see attached sketchPlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 2 1 4.00 12.57 05/08/18 7 45,630 2 3,630 EAS 2 2 4.00 12.57 05/29/18 28 60,545 2 4,820 ZHG 2 3 4.00 12.57 05/29/18 28 62,930 2 5,010 ZHG 2 4 4.00 12.57 05/29/18 28 58,875 1 4,690 ZHG Average (28 days) 4,840 2 5 4.00 12.57 06/26/18 56 70,030 3 5,570 EAS Initial Cure:Final Cure:Outside Moist Room Comments:Compressive strength of 56 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Alex Miranda The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 8CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0209 05/01/18 06/27/18 Revision 2 - 56-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0412 8143 Plant: Ticket No.: 141 4672361 Field Test Data Test Air Content (%): Result Specification 4 3-5 3.2 3-6 71 69 150.3 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:05/01/18 0500 Alex Miranda Cloudy, moderate wind 230/900 10 0 0 Location #3, see attached sketchSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Fire Lane, see attached sketchPlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 3 1 4.00 12.57 05/08/18 7 55,080 2 4,380 EAS 3 2 4.00 12.57 05/29/18 28 65,570 1 5,220 ZHG 3 3 4.00 12.57 05/29/18 28 70,065 3 5,580 ZHG 3 4 4.00 12.57 05/29/18 28 70,575 5 5,620 ZHG Average (28 days) 5,470 3 5 4.00 12.57 06/26/18 56 79,540 3 6,330 EAS Initial Cure:Final Cure:Outside Moist Room Comments:Compressive strength of 56 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Alex Miranda The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 8CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0209 05/01/18 06/27/18 Revision 2 - 56-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0503 3239 Plant: Ticket No.: 141 4672513 Field Test Data Test Air Content (%): Result Specification 3 1/2 3-5 5.1 3-6 75 69 150.4 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:05/01/18 0615 Alex Miranda Cloudy, moderate wind 310/900 10 0 0 Location #4, see attached sketchSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Fire Lane, see attached sketchPlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 4 1 4.00 12.57 05/08/18 7 61,790 2 4,920 EAS 4 2 4.00 12.57 05/29/18 28 71,650 2 5,700 ZHG 4 3 4.00 12.57 05/29/18 28 74,845 5 5,960 ZHG 4 4 4.00 12.57 05/29/18 28 78,730 5 6,270 ZHG Average (28 days) 5,970 4 5 4.00 12.57 06/26/18 56 82,580 3 6,570 EAS Initial Cure:Final Cure:Outside Moist Room Comments:Compressive strength of 56 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Alex Miranda The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 8CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0209 05/01/18 06/27/18 Revision 2 - 56-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0620 6854 Plant: Ticket No.: 141 4672799 Field Test Data Test Air Content (%): Result Specification 4 1/2 3-5 5.1 3-6 77 69 149.9 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:05/01/18 0705 Alex Miranda Cloudy, moderate wind 410/900 10 0 0 Location #5, see attached sketchSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Fire Lane, see attached sketchPlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 5 1 4.00 12.57 05/08/18 7 56,400 2 4,490 EAS 5 2 4.00 12.57 05/29/18 28 66,260 1 5,270 EAS 5 3 4.00 12.57 05/29/18 28 69,190 1 5,510 EAS 5 4 4.00 12.57 05/29/18 28 64,450 3 5,130 EAS Average (28 days) 5,300 5 5 4.00 12.57 06/26/18 56 79,600 3 6,330 EAS Initial Cure:Final Cure:Outside Moist Room Comments:Compressive strength of 56 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Alex Miranda The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 5 of 8CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0209 05/01/18 06/27/18 Revision 2 - 56-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0737 6854 Plant: Ticket No.: 141 4673262 Field Test Data Test Air Content (%): Result Specification 4 1/2 3-5 5.1 3-6 77 69 152.5 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:05/01/18 0835 Alex Miranda Cloudy 540/720 10 0 0 Location #6, see attached sketchSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Pavement, see attached sketchPlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 6 1 4.00 12.57 05/08/18 7 59,820 2 4,760 EAS 6 2 4.00 12.57 05/29/18 28 64,290 1 5,120 EAS 6 3 4.00 12.57 05/29/18 28 63,510 3 5,050 EAS 6 4 4.00 12.57 05/29/18 28 65,370 3 5,200 EAS Average (28 days) 5,120 6 5 4.00 12.57 06/26/18 56 68,060 3 5,420 EAS Initial Cure:Final Cure:Outside Moist Room Comments:Compressive strength of 56 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Alex Miranda The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 6 of 8CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0209 05/01/18 06/27/18 Revision 2 - 56-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0819 8831 Plant: Ticket No.: 141 4673433 Field Test Data Test Air Content (%): Result Specification 5 3-5 4.4 3-6 76 71 147.5 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:05/01/18 0925 Alex Miranda Cloudy, windy 610/720 10 0 0 Location #7, see attached sketchSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Pavement, see attached sketchPlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 7 1 4.00 12.57 05/08/18 7 50,970 2 4,060 EAS 7 2 4.00 12.57 05/29/18 28 62,700 3 4,990 EAS 7 3 4.00 12.57 05/29/18 28 62,370 3 4,960 EAS 7 4 4.00 12.57 05/29/18 28 59,070 3 4,700 EAS Average (28 days) 4,880 7 5 4.00 12.57 06/26/18 56 71,650 3 5,700 EAS Initial Cure:Final Cure:Outside Moist Room Comments:Compressive strength of 56 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Alex Miranda The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 7 of 8CR0001, 11-16-12, Rev.6 Report Number: Service Date: Report Date: Task: Client Coppell, TX 75019 770 Gateway Blvd Haverty's Warehouse ExpansionHaverty Furniture Co Inc Attn: Glenn Boone 780 Johnson Ferry Rd NE Ste 800 Atlanta, GA 30342 214-630-1010 Reg No: F-3272 Dallas, TX 75247-4547 8901 Carpenter Fwy, Ste 100 94171346.0209 05/01/18 06/27/18 Revision 2 - 56-day results CONCRETE COMPRESSIVE STRENGTH TEST REPORT Project Project Number: 94171346 Specified Strength:28 days Mix ID: Supplier: Batch Time: Truck No.: R3136027 Martin Marietta Material Information 0935 3244 Plant: Ticket No.: 141 4674005 Field Test Data Test Air Content (%): Result Specification 3 3-5 4.5 3-6 77 72 150.0 3,500 Slump (in): psi @ Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Sample Information Sample Date: Sampled By: Weather Conditions: Sample Time:05/01/18 1030 Alex Miranda Cloudy, windy 710/780 10 0 0 Location #8, see attached sketchSample Location: Placement Method:Pump Water Added Before (gal): Water Added After (gal): Accumulative Yards:Batch Size (cy): Pavement, see attached sketchPlacement Location: Laboratory Test Data Set Avg Diam.Area DateDate Test Age at Load Maximum Strength Compressive Fracture No.ID Specimen Received Tested (days)Type(in)(sq in)(lbs)(psi) Tested By 8 1 4.00 12.57 05/08/18 7 53,440 3 4,250 EAS 8 2 4.00 12.57 05/29/18 28 64,400 1 5,120 EAS 8 3 4.00 12.57 05/29/18 28 67,110 3 5,340 EAS 8 4 4.00 12.57 05/29/18 28 67,270 3 5,350 EAS Average (28 days) 5,270 8 5 4.00 12.57 06/26/18 56 79,440 3 6,320 EAS Initial Cure:Final Cure:Outside Moist Room Comments:Compressive strength of 56 day cylinders complies with the specified strength. Samples Made By: Terracon Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Services: Reported To: Contractor: Report Distribution: (1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion (1) Kajima Building & Design Group Inc., Craig Farwick (1) Kajima Building & Design Group Inc., Juan Hernandez (1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed Dikko Joel Warriner, P.E. Senior Project Manager Reviewed By: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods: Terracon Rep.: Alex Miranda The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 8 of 8CR0001, 11-16-12, Rev.6