Loading...
514RaintreeCircle_75019_46292 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-37057 Test Date: 7/3/2018 Result: Failed Reason for Test: Existing Account Name : Current Water Customer Address of Assembly : 514 Raintree Circle Address Type : Residential Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Double Check Valve Frequency :Only on Installation What does this serve? Irrigation Manufacturer :Watts Model No :LF007M3 Size :1 Serial No :062291 Location At:Meter Is the assembly installed in accordance with manufacturer recommendations and/or local codes?No Is the assembly installed on a non-potable water supply (auxiliary)?Yes Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:7/3/2018 Time:2:10 PM Held at 2.5 psid Closed Tight Leaked Held at 1.6 psid Closed Tight Leaked Opened at psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Longhorn Model: 845-3-0006 Serial No.: 04050499 Date Tested for Accuracy: 9/22/2017 Remarks :No isolation valve Firm Name : North Texas Backflow Licensed Tester : John Davis Firm Address : P.O.Box 597 BPAT License # : BP0003132 Firm Phone No : 469-231-6623 License Expiration Date : 06/12/2020 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.