Gateway BP(1.4)-LR180510 (7)Report Number:
Service Date:
Report Date:
Task:
Client
Coppell, TX 75019
770 Gateway Blvd
Haverty's Warehouse ExpansionHaverty Furniture Co Inc
Attn: Glenn Boone
780 Johnson Ferry Rd NE Ste 800
Atlanta, GA 30342
214-630-1010 Reg No: F-3272
Dallas, TX 75247-4547
8901 Carpenter Fwy, Ste 100
94171346.0239
05/10/18
07/06/18 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: 94171346
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
R3136027
Martin Marietta
Material Information
0131
3247
Plant:
Ticket No.:
131
4691485
Field Test Data
Test
Air Content (%):
Result Specification
3 1/2 3 - 5
5.5 3 - 6
80
74
149.5
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:05/10/18 0210
Alex Miranda
Clear/moderate wind
10/500 10
Location #1, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement along S of bldg, see
attached sketch
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
Tested
By
1 1 4.00 12.57 05/17/18 7 50,350 3 4,010 EAS
1 2 4.00 12.57 06/07/18 28 61,860 2 4,920 EAS
1 3 4.00 12.57 06/07/18 28 61,200 2 4,870 EAS
1 4 4.00 12.57 06/07/18 28 60,420 5 4,810 EAS
Average (28 days) 4,870
1 5 4.00 12.57 07/05/18 56 67,575 3 5,380 LSB
Initial Cure:Final Cure:Outside Moist Room
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion
(1) Kajima Building & Design Group Inc., Craig
Farwick
(1) Kajima Building & Design Group Inc., Juan
Hernandez
(1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed
Dikko
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Alex Miranda
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client
Coppell, TX 75019
770 Gateway Blvd
Haverty's Warehouse ExpansionHaverty Furniture Co Inc
Attn: Glenn Boone
780 Johnson Ferry Rd NE Ste 800
Atlanta, GA 30342
214-630-1010 Reg No: F-3272
Dallas, TX 75247-4547
8901 Carpenter Fwy, Ste 100
94171346.0239
05/10/18
07/06/18 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: 94171346
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
R3136027
Martin Marietta
Material Information
0335
8853
Plant:
Ticket No.:
131
4691709
Field Test Data
Test
Air Content (%):
Result Specification
5 3 - 5
4.2 3 - 6
79
72
150.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:05/10/18 0900
Alex Miranda
Clear
136/500 10
25
0
Location #2, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement along S of bldg, see
attached sketch
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
Tested
By
2 1 4.00 12.57 05/17/18 7 50,980 2 4,060 EAS
2 2 4.00 12.57 06/07/18 28 60,250 2 4,790 EAS
2 3 4.00 12.57 06/07/18 28 54,330 2 4,320 EAS
2 4 4.00 12.57 06/07/18 28 60,440 3 4,810 EAS
Average (28 days) 4,640
2 5 4.00 12.57 07/05/18 56 67,295 3 5,360 LSB
Initial Cure:Final Cure:Outside Moist Room
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion
(1) Kajima Building & Design Group Inc., Craig
Farwick
(1) Kajima Building & Design Group Inc., Juan
Hernandez
(1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed
Dikko
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Alex Miranda
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client
Coppell, TX 75019
770 Gateway Blvd
Haverty's Warehouse ExpansionHaverty Furniture Co Inc
Attn: Glenn Boone
780 Johnson Ferry Rd NE Ste 800
Atlanta, GA 30342
214-630-1010 Reg No: F-3272
Dallas, TX 75247-4547
8901 Carpenter Fwy, Ste 100
94171346.0239
05/10/18
07/06/18 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: 94171346
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
R3136027
Martin Marietta
Material Information
0434
7885
Plant:
Ticket No.:
131
4691890
Field Test Data
Test
Air Content (%):
Result Specification
4 3 - 5
4.0 3 - 6
75
69
150.2
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:05/10/18 0510
Alex Miranda
Clear
214/500 9
Location #3, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement along S of bldg, see
attached sketch
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
Tested
By
3 1 4.00 12.57 05/17/18 7 42,320 2 3,370 EAS
3 2 4.00 12.57 06/07/18 28 53,060 5 4,220 EAS
3 3 4.00 12.57 06/07/18 28 59,890 3 4,770 EAS
3 4 4.00 12.57 06/07/18 28 54,060 2 4,300 EAS
Average (28 days) 4,430
3 5 4.00 12.57 07/05/18 56 61,255 1 4,870 LSB
Initial Cure:Final Cure:Outside Moist Room
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion
(1) Kajima Building & Design Group Inc., Craig
Farwick
(1) Kajima Building & Design Group Inc., Juan
Hernandez
(1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed
Dikko
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Alex Miranda
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client
Coppell, TX 75019
770 Gateway Blvd
Haverty's Warehouse ExpansionHaverty Furniture Co Inc
Attn: Glenn Boone
780 Johnson Ferry Rd NE Ste 800
Atlanta, GA 30342
214-630-1010 Reg No: F-3272
Dallas, TX 75247-4547
8901 Carpenter Fwy, Ste 100
94171346.0239
05/10/18
07/06/18 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: 94171346
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
R3136027
Martin Marietta
Material Information
0535
3243
Plant:
Ticket No.:
131
4692135
Field Test Data
Test
Air Content (%):
Result Specification
5 3 - 5
5.4 3 - 6
76
70
148.9
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:05/10/18 0617
Alex Miranda
Clear/moderate wind
312/500 10
30
0
Location #4, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement along S of bldg, see
attached sketch
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
Tested
By
4 1 4.00 12.57 05/17/18 7 48,680 2 3,870 EAS
4 2 4.00 12.57 06/07/18 28 53,040 2 4,220 EAS
4 3 4.00 12.57 06/07/18 28 53,260 3 4,240 EAS
4 4 4.00 12.57 06/07/18 28 56,300 3 4,480 EAS
Average (28 days) 4,310
4 5 4.00 12.57 07/05/18 56 67,125 2 5,340 LSB
Initial Cure:Final Cure:Outside Moist Room
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion
(1) Kajima Building & Design Group Inc., Craig
Farwick
(1) Kajima Building & Design Group Inc., Juan
Hernandez
(1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed
Dikko
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Alex Miranda
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client
Coppell, TX 75019
770 Gateway Blvd
Haverty's Warehouse ExpansionHaverty Furniture Co Inc
Attn: Glenn Boone
780 Johnson Ferry Rd NE Ste 800
Atlanta, GA 30342
214-630-1010 Reg No: F-3272
Dallas, TX 75247-4547
8901 Carpenter Fwy, Ste 100
94171346.0239
05/10/18
07/06/18 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: 94171346
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
R3136027
Martin Marietta
Material Information
0706
7885
Plant:
Ticket No.:
131
4692174
Field Test Data
Test
Air Content (%):
Result Specification
3 - 5
3 - 6
3,500 psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:05/10/18 0800
Alex Miranda
Sunny/clear
438/500 9
Location #5, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement along S of bldg, see
attached sketch
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
Tested
By
5 1 4.00 12.57 05/17/18 7 47,860 2 3,810 EAS
5 2 4.00 12.57 06/07/18 28 58,820 2 4,680 EAS
5 3 4.00 12.57 06/07/18 28 56,140 2 4,470 EAS
5 4 4.00 12.57 06/07/18 28 58,790 5 4,680 EAS
Average (28 days) 4,610
5 5 4.00 12.57 07/05/18 56 62,690 2 4,990 LSB
Initial Cure:Final Cure:Outside Moist Room
Comments:Compressive strength of 56 day cylinders complies with the specified strength. Not tested for plastic unit weight.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) Haverty Furniture Co Inc, Glenn Boone (1) City of Coppell TX, Marcus Marion
(1) Kajima Building & Design Group Inc., Craig
Farwick
(1) Kajima Building & Design Group Inc., Juan
Hernandez
(1) Kent Companies, George Sellers (1) Macgregor Assoc Architects, Muhammed
Dikko
Joel Warriner, P.E.
Senior Project Manager
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Alex Miranda
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 5CR0001, 11-16-12, Rev.6