Loading...
585SRoyalLnSte200_75019_47802 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22085 Test Date: 7/26/2018 Result: Passed Reason for Test: Existing Account Name : Dexas International Address of Assembly : 585 S Royal Ln Ste 200 Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? FireLine Manufacturer :Ames Model No :4000B Size :2 Serial No :06008 Location At:@ ceiling by offices Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:7/26/2018 Time:12:12 PM Held at 8 psid Closed Tight Leaked Held at 8 psid Closed Tight Leaked Opened at 2.4 psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Wilkins Model: TG-5 Serial No.: 06110075 Date Tested for Accuracy: 8/25/2017 Remarks : Firm Name : Action Fire Pros Licensed Tester : Jason Huston Firm Address : 3709 S I-35 E BPAT License # : BP0010651 Firm Phone No : 800-550-2287 License Expiration Date : 07/03/2019 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.