Loading...
Freeport NIP(2.2)-LR011129CONCRETE COMPRESSIVE STRENGTH TEST Repo, rt Number: 94011204.0051 ~,,~,.o.~. 8901 Carpenter Frwy., Suite #100 Service Date: October 26, 2001 Dallas, Texas 75247 (214) 630-1010 Client: TNA North American, Inc. Report Date: November 29, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3500 psi (~ 28 Days Sample Time: 6:55am Date Cast: October 26, 2001 Technician: Albert Garcia Batch Time: 6:08am Plant: 18 Weather Conditions: Clear Supplier: TXI Accumulative Yards: 80 Truck No: 126 Ticket No: 3009843 Placement Method: Direct Discharge Mix i.D. No.: 8273 Sample Locations: See placement location Placement Location: Paving - See attached sketch Field Test Data Test Result Specification Test Method Slump, inches: 5.00 3-5 ASTM C-143 Air Content, %: 4.5 3-6 ASTM C-231 Concrete Temperature, o F: 68 ASTM C1064 Ambient Temperature, o F: 50 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 11/02/2001 7 99,570 3,520 1 2 6.00 28.27 11/02/2001 7 100,920 3,570 Average 3,550 1 3 6.00 28.27 11/23/2001 28 138,420 4,900 1 4 6.00 28.27 11/23/2001 28 137,390 4,860 Average 4,880 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 4 CONCRETE COMPRESSIVE STRENGTH TEST ~-'i~ Report Number: 94011204.0051 ~,~,~c 8901 Carpenter Frwy., Suite #100 Service Date: October 26, 2001 Dallas, Texas 75247 (214) 630-1010 Client: TNA North American, Inc. Report Date: November 29, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3500 psi @ 28 Days Sample Time: 7:55am Date Cast: October 26, 2001 Technician: Albert Garcia Batch Time: 6:57am Plant: 18 Weather Conditions: Clear Supplier: TXI Accumulative Yards: 170 Truck No: 96 Ticket No: 3009930 Placement Method: Direct Discharge Mix I.D. No.: 8273 Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.25 3-5 ASTM C-143 Air Content, %: 4.5 3-6 ASTM C-231 Concrete Temperature, o F: 67 ASTM C1064 Ambient Temperature, o F: 52 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 2 1 6.00 28.27 11/02/2001 7 91,680 3,240 2 2 6.00 28.27 11/02/2001 7 93,860 3,320 Average 3,280 2 3 6.00 28.27 11/23/2001 28 127,700 4,520 2 4 6.00 28.27 11/23/2001 28 129,760 4,590 Average 4,560 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical rnatedals. Page 2 of 4 o,-~w~,~,, Ko~ CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94011204.0051 8901 Carpenter Frwy., Suite #100 SerVice Date: October 26, 2001 Dallas, Texas 75247 (214) 630-1010 Client: TNA North American, Inc. Report Date: November 29, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3500 psi @ 28 Days Sample Time: 9:20am Date Cast: October 26, 2001 Technician: Albert Garcia Batch Time: 8:01am Plant: 18 Weather Conditions: Clear Supplier: TXI Accumulative Yards: 260 Truck No: 125 Ticket No: 3010055 Placement Method: Direct Discharge Mix I.D. No.: 8273 Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.50 3-5 ASTM C-143 Air Content, %: 4.25 3-6 ASTM C-231 Concrete Temperature, o F: 72 ASTM C1064 Ambient Temperature, o F: 60 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 3 1 6.00 28.27 11/02/2001 7 86,440 3,060 3 2 6.00 28.27 11/02/2001 7 88,200 3,120 Average 3,090 3 3 6.00 28.27 11/23/2001 28 122,290 4,320 3 4 6.00 28.27 11/23/2001 28 122,970 4,350 Average 4,340 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 4 °l~LLW'~01~Cuture Key CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94011204.0051 ~,~E~.~ 8901 Carpenter Frwy., Suite #100 SerVice Date: October 26, 2001 Dallas, Texas 75247 (214) 630-1010 Client: TNA North American, Inc. Report Date: November 29, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project Number: 94011204 Material Information Sample Information Specified Strength: 3500 psi @ 28 Days Sample Time: 10:50am Date Cast: October 26, 2001 Technician: Albert Garcia Batch Time: 9:00am Plant: 18 Weather Conditions: Clear Supplier: TXI Accumulative Yards: 340 Truck No: 93 Ticket No: 3010174 Placement Method: Direct Discharge Mix I.D. No.: 8273 Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 4.75 3-5 ASTM C-143 Air Content, %: 4.5 3-6 ASTM C-231 Concrete Temperature, o F: 78 ASTM Cl 064 Ambient Temperature, o F: 60 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 4 1 6.00 28.27 11/02/2001 7 99,010 3,500 4 2 6.00 28.27 11/02/2001 7 99,510 3,520 Average 3,510 4 3 6.00 28.27 11/23/2001 28 131,490 4,650 4 4 6.00 28.27 11/23/2001 28 132,020 4,670 Average 4,660 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Albert Garcia Report Distribution: /~pgineering, Inc. (1) TNA North American, Inc. (1) FACServices Inc (1) Carrell Poole & Yost Architecture (1) David Kent Reviewed b . (1) R L Goedson Consulting Engineers (1) City of Coppell - Bldg Insp (Eric J. Cleveland, P.E. (1) Pacific Builders Inc (1) City of Coppell - Constr Insp Senior Project Engineer The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 4 o,-~w,~,-~,o ~.~ PROJECT NO.: q Z~ ~ ~ \ ~.C~ ~'~'. ~ ,~ { CHKD BY: DATE: ENGINEERING, INC. REPORT OF STRUCTURAL STEEL OBSERVATION Report. Number: 94011204.0068 JL J_.~'~ 8901 Carpenter Rwy., Suite #100 Service Date: November 16, 2001 Dallas, Texas 75247 (214) 630-1010 Client: TNA North American, Inc. Report Date: November 29, 2001 Attn: Terry Raley Project: Sales Office & Warehouse Fac. 1321 Valwood Parkway, Suite 440 Coppell, Texas Carrollton TX 75006 Project~M Number: Services: Structural steel observation. On this date, an HBC Engineering technician arrived atthee ablov~ referenced jobsite as scheduled for structural steel observation. A visual observation was conducted as noj~d below. 1. Reobservation Items from Structural Steel Observation 1204.0056, dated 11/10/01' a. Item 3, joist bridging at the Roof Level was now found to be compliant at tie-in to panel. b. Item 4, beam to column and beam to seat connections were now found to be compliant. c. Welder certifications were still unavailable for review. 2. Initial Observation, Mezzanine Framing: a. Anchor bolts were found to be compliant except for one (1) location which was missing a bolt in a four (4) bolt pattern. b. Bolted connections were found to be compliant. c. Beam to panel connections were found to be compliant. d. Joist seat welds were found to be compliant. e. Joist bridging installation was found to be compliant. f. Metal deck installation and puddle welds were found to be compliant. Technician: Melvin Lutt tell Report Distribution: H ' er' g, Inc. (1) TNA North American, Inc. (1) FACServices Inc (1) Carrell Poole & Yost Architecture (1) David Kent Reviewed by: (1) R L Goodson Consulting Engineers (1) City of Coppell - Bldg Insp Eric J Cleveland P E (1) Pacific Builders Inc (1) City of Coppell- Constr Insp Senior Project Engineer The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1