Loading...
330SDentonTapRd_75019_54180 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22224 Test Date: 11/13/2018 Result: Passed Reason for Test: Existing Account Name : Legacy ER and Urgent Care Address of Assembly : 330 S Denton Tap Rd Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Double Check Valve Frequency :Annual What does this serve? FireLine Manufacturer :Wilkins Model No :350 Size :8 Serial No :1592B Location At:pit at road Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:11/13/2018 Time:10:30 AM Held at 2.4 psid Closed Tight Leaked Held at 2.5 psid Closed Tight Leaked Opened at psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: MID WEST Model: 845-5 Serial No.: 06090509 Date Tested for Accuracy: 7/20/2018 Remarks : Firm Name : Allied Fire Protection Licensed Tester : WALTER JACOBY Firm Address : 12630 E Northwest Hwy #303 BPAT License # : BP0008088 Firm Phone No : 972-840-1700 License Expiration Date : 01/23/2019 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.