Loading...
200E_BeltLineRd_Ste102_75019_53930 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22420 Test Date: 11/8/2018 Result: Failed Reason for Test: Existing Account Name : Ingle Rentals Address of Assembly : 200 E.Belt Line Rd.Ste 102 Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts Model No :009M2QT Size :1 1/2 Serial No :65802 Location At:N.side of building #5 Is the assembly installed in accordance with manufacturer recommendations and/or local codes?No Is the assembly installed on a non-potable water supply (auxiliary)?Yes Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:11/8/2018 Time:9:20 AM Held at 9 psid Closed Tight Leaked Held at 9.2 psid Closed Tight Leaked Opened at 0 psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Wilkins Model: TG5 Serial No.: 05112209 Date Tested for Accuracy: 1/11/2018 Remarks :This device is an PR BF in ground.Not in compliance,either need to remove and install a dc or raise above ground with a hot box. Firm Name : Action Fire Pros Licensed Tester : John Garcia Firm Address : 3709 S I-35 E BPAT License # : BP0015351 Firm Phone No : 800-550-2287 License Expiration Date : 07/11/2019 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.