Loading...
477W_BethelRoad_75019_59204 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-21315 Test Date: 11/15/2018 Result: Passed Reason for Test: Existing Account Name : Local Diner (Coppell) Address of Assembly : 477 W.Bethel Road Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts Model No :SS009M3QT Size :1/2 Serial No :15223 Location At:Kitchen at carbonator Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:11/15/2018 Time:12:45 PM Held at 8.4 psid Closed Tight Leaked Held at 8 psid Closed Tight Leaked Opened at 2.1 psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: MacArthur Model: 844 Serial No.: 10021520 Date Tested for Accuracy: 10/3/2018 Remarks : Firm Name : A &A Active Backflow Licensed Tester : John Ansley Firm Address : 1611 N IH 35E BPAT License # : BP0006162 Firm Phone No : (972)242-2229 License Expiration Date : 04/04/2020 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.