1580PointWestBlvd__75019_52780 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
Name of PWS:Coppell
PWS I.D.:0570040
Address:816 S.Coppell Road
Coppell,Texas 75019
Phone:972-462-5150
Contact Person:Jerry Davis
Catalog No: TXTCOP-22116
Test Date: 10/19/2018
Result: Passed
Reason for Test: Existing
Account Name : Four Points by Sheraton Dallas/Ft.Worth North
Address of Assembly : 1580 Point West Blvd.
Address Type : Commercial
Inspection
The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within
acceptable parameters.
Type of Assembly :Double Check Valve Frequency :Annual What does this serve? FireLine
Manufacturer :Wilkins Model No :950 Size :3/4 Serial No :3941715
Location At:In Vault /Front Pkwy
Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes
Is the assembly installed on a non-potable water supply (auxiliary)?No
Reduced Pressure Principle Assembly Pressure Vacuum Breaker
Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly
1st check 2nd check Relief Valve Air Inlet Check Valve
Initial Test
Date:10/19/2018
Time:1:00 PM
Held at 2.2 psid
Closed Tight
Leaked
Held at 2 psid
Closed Tight
Leaked
Opened at psid
Did not open
Opened at psid
Did it fully open
Yes No
Held at psid
Leaked
Repairs and Materials
Used **
Test After Repair
Date:
Time:
Held at psid
Closed Tight
Leaked
Held at psid
Closed Tight
Leaked
Opened at psid Opened at psid Held at psid
***2nd check:numeric reading required for DCVA only
Test gauge used: Potable Make: Midwest Model: 835 Serial No.: 10071103
Date Tested for Accuracy: 11/7/2017
Remarks :
Firm Name : Cantu Fire Protection Licensed Tester : Daniel Cantu
Firm Address : 1605 East Park Blvd.BPAT License # : BP0009580
Firm Phone No : 214-554-3105 License Expiration Date : 02/22/2022
The above is certified to be true at the time of testing.
* Test Records must be kept for at least three years.[30 TAC §290.46(B)]
** Use only manufacturer's replacement parts.