700NDentonTapRd_75019_52255 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
Name of PWS:Coppell
PWS I.D.:0570040
Address:816 S.Coppell Road
Coppell,Texas 75019
Phone:972-462-5150
Contact Person:Jerry Davis
Catalog No: TXTCOP-22022
Test Date: 10/8/2018
Result: Passed
Reason for Test: Existing
Account Name : Market Street #564
Address of Assembly : 700 N Denton Tap Rd
Address Type : Commercial
Inspection
The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within
acceptable parameters.
Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? FireLine
Manufacturer :Watts Model No :009 Size :1/2 Serial No :A62840
Location At:meat dept under sink
Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes
Is the assembly installed on a non-potable water supply (auxiliary)?No
Reduced Pressure Principle Assembly Pressure Vacuum Breaker
Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly
1st check 2nd check Relief Valve Air Inlet Check Valve
Initial Test
Date:10/8/2018
Time:10:15 AM
Held at 6.1 psid
Closed Tight
Leaked
Held at 6 psid
Closed Tight
Leaked
Opened at 2.1 psid
Did not open
Opened at psid
Did it fully open
Yes No
Held at psid
Leaked
Repairs and Materials
Used **
Test After Repair
Date:
Time:
Held at psid
Closed Tight
Leaked
Held at psid
Closed Tight
Leaked
Opened at psid Opened at psid Held at psid
***2nd check:numeric reading required for DCVA only
Test gauge used: Potable Make: Wilkins Model: TG-5 Serial No.: 06110069
Date Tested for Accuracy: 7/24/2018
Remarks :
Firm Name : All Test Service Solutions Licensed Tester : Kolton Hodges
Firm Address : 600 Henrietta Creek Rd.#100 BPAT License # : BP0017955
Firm Phone No : 817-379-0856 License Expiration Date : 07/06/2020
The above is certified to be true at the time of testing.
* Test Records must be kept for at least three years.[30 TAC §290.46(B)]
** Use only manufacturer's replacement parts.