Loading...
120SDentonTapSuite120_75019_60552 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-41266 Test Date: 12/7/2018 Result: Passed Reason for Test: Existing Account Name : Current Water Customer Address of Assembly : 120 S Denton Tap Suite 120 Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts Model No :009M3 Size :3/4 Serial No :219649 Location At:In closet Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:12/7/2018 Time:8:00 AM Held at 8.1 psid Closed Tight Leaked Held at 8 psid Closed Tight Leaked Opened at 3 psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Non-Potable Make: Midwest Model: 845-5 Serial No.: 11130531 Date Tested for Accuracy: 3/12/2018 Remarks : Firm Name : .01 Accuracy Backflow Licensed Tester : Brian Cox Firm Address : P.O.Box 6832 BPAT License # : BP0017066 Firm Phone No : 972.699.7156 License Expiration Date : 02/23/2019 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.