Loading...
120SDentonTapRdSuite490_75019_60752 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-41142 Test Date: 12/5/2018 Result: Passed Reason for Test: Existing Account Name : Zoe's Kitchen Address of Assembly : 120 S Denton Tap Rd Suite 490 Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts Model No :009 Size :1/2 Serial No :42736 Location At:soda machine Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:12/5/2018 Time:9:45 AM Held at 6.5 psid Closed Tight Leaked Held at 7 psid Closed Tight Leaked Opened at 2.5 psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Midwest Model: 845-5 Serial No.: 03162339 Date Tested for Accuracy: 4/17/2018 Remarks : Firm Name : Dallas plumbing co Licensed Tester : David Farish Firm Address : 11055 Plano rd BPAT License # : BP0017714 Firm Phone No : (469)531-8777 License Expiration Date : 03/30/2020 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.