Loading...
1484SBeltline_75019_60903 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22271 Test Date: 12/13/2018 Result: Passed Reason for Test: Existing Account Name : Quick Trip #969 Address of Assembly : 1484 S Beltline Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts Model No :009M3 Size :3/4 Serial No :360638 Location At:stockroom Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:12/13/2018 Time:10:17 AM Held at 8.6 psid Closed Tight Leaked Held at 8 psid Closed Tight Leaked Opened at 2.1 psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Wilkins Model: TG-5 Serial No.: 06110069 Date Tested for Accuracy: 7/24/2018 Remarks : Firm Name : All Test Service Solutions Licensed Tester : Kolton Hodges Firm Address : 600 Henrietta Creek Rd.#100 BPAT License # : BP0017955 Firm Phone No : 817-379-0856 License Expiration Date : 07/06/2020 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.