435SouthwesternBlvdBldgG_75019_62697 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22974 Test Date: 1/16/2019 Result: Passed Reason for Test: Existing Account Name : Current Water Customer Address of Assembly : 435 Southwestern Blvd Bldg G Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Double Check Valve Frequency :Annual What does this serve? Domestic Manufacturer :Watts Model No :LF007M1QT Size :2 Serial No :024437 Location At:front pkwy at meter Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:1/16/2019 Time:3:00 PM Held at 1.2 psid Closed Tight Leaked Held at 1 psid Closed Tight Leaked Opened at psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Wilkins Model: TG_5 Serial No.: 07090476 Date Tested for Accuracy: 1/3/2019 Remarks : Firm Name : Action Fire Pros Licensed Tester : Allen Stevens Firm Address : 3709 S I-35 E BPAT License # : BP0009860 Firm Phone No : 800-550-2287 License Expiration Date : 07/31/2021 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.