Loading...
1501E_BeltlineRd__75019_68303 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22339 Test Date: 4/8/2019 Result: Passed Reason for Test: Existing Account Name : Valley Ranch Baptist Church Address of Assembly : 1501 E.Beltline Rd. Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Double Check Valve Frequency :Annual What does this serve? FireLine Manufacturer :Watts Model No :774X Size :8 Serial No :100142 Location At:N.E.Vault Fireline Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:4/8/2019 Time:8:00 AM Held at 2 psid Closed Tight Leaked Held at 1.8 psid Closed Tight Leaked Opened at psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Mid-West Model: 845 Serial No.: 06142853 Date Tested for Accuracy: 9/4/2018 Remarks : Firm Name : Allied Fire Protection Licensed Tester : LARRY WORLOW Firm Address : 3361 Boyington Dr BPAT License # : BP0010000 Firm Phone No : 972-840-1700 License Expiration Date : 02/28/2022 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.