751Plaza_75019_69624 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-36218 Test Date: 5/9/2019 Result: Passed Reason for Test: Existing Account Name : NACM Southwest Address of Assembly : 751 Plaza Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Double Check Valve Frequency :Annual What does this serve? FireLine Manufacturer :Febco ByPass : Model No :805YB ByPass : Size :3/4"ByPass : Serial No :H006586 ByPass : Location At:Location in vault next to dumpster west side Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Type II Assembly Pressure Vacuum Breaker Spilled-Resistant Vacuum BreakerDoubleCheckValveAssembly 1st check 2nd check Relief Valve Bypass Check Air Inlet Check Valve Initial Test Date:5/9/2019 Time:12:45 PM Held at 2.2 psid Closed Tight Leaked Held at 2.3 psid Closed Tight Leaked Opened at psid Did not open Held at psid Closed Tight Leaked Opened at psid Did it fully open Yes No Held at psid Leaked Repairs andMaterialsUsed ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Held at psid Closed Tight Leaked Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Midwest Model: 845-5 Serial No.: 10101531 Date Tested for Accuracy: 8/31/2018 Remarks : Firm Name : Metro Fire Protection,Inc.Licensed Tester : Patrick Odom Firm Address : 11301 Indian Trail BPAT License # : BP0013440 Firm Phone No : 972-247-1305 License Expiration Date : 11/18/2019 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.